11 

Optima 310

2. Function

2.1 Description Optima 310

A Combi unit is used for heating up domestic water and 
supply air, to provide partial cover of the ventilation and 
basic ventilation heating needs in the home. 

1: Domestic water heating

The domestic water temperature is controlled by sensor 
T8, which is mounted at the base of the tank. When 
the need for heating of domestic water arises, the 
compressor starts, the magnetic valve MA 3 and MA 
6opens and the water is heated to the temperature set 
(point 5 in the operating menu).

2: Room heating

By room heating the magnetic valve MA 2 and MA 5 is 
activated.The room temperature is controlled by room 
sensor T2, mounted on the control panel. If, for example, 
this temperature has been set to 21°C, the compressor 
will start up when the room temperature has fallen to 
20.6°C. When the compressor has heated the room 
temperature up to 21.4°C, the compressor will stop. If 
the compressor cannot maintain the room temperature, 
the motor valve (unit with water after heating coil) will 
begin to perform temperature control (PID control) when 
the room temperature has fallen to 20°C. For units with 
electric after heating coils (level 1), this will cut in when 
the room temperature has fallen to 20°C. When the room 
temperature again reaches 20°C, the electric heat will 
switch off. Units with electric pre-heating coils will control 
the same way as units with after heating coils.

3: No heating needs

When there is no need for either water heating or room 
heating, the compressor will stop, while the fans continue 
to run. The heat in the extract air is recovered in the 
counter current heat exchanger and transferred to the 
supply air.

4: Defrosting

When the temperature difference between the 
temperature upstream of the cooling coil and the 
temperature of the cooling coil becomes too large, as 
happens when ice is formed on the cooling surface, the 
unit goes into defrost mode. The magnetic valve MA 4 
opens and the supply air fan and the electric heating coil, 
stops until the ice has melted and the cooling coil has 
reached a temperature of app. 5°C. Then the magnetic 
valve closes again and the supply air fan and electric 
heating coil restart operation.

2.2 Extra capacity

Electric element:

If the hot water need is larger than the coverage of the 
Combi, the electric heating element may be set to ON 

in the main menu with a short-cut key. When the electric 
heating element is ON, sensor T7, mounted in the middle 
of the tank, will control heating up the upper half to the 
set temperature (point 7 in the operating menu)

2.3 Operation safety

High pressure switch:

To prevent the compressor exceeding its range of 
application, there is an integral high pressure switch, 
which interrupts when the pressure becomes too large. 
Activate the red reset button once the cause of the error 

has been identified.

Circuit safety breaker:

If an error should occur in the electric heating element, 
the safety breaker thermostat will disable the heater. To 
reset the safety breaker the centre button of the safety 
breaker must be pressed. The safety breaker is located 
on the heater. (Remember to disconnect the power 
supply to the unit, before any work is carried out)

Override control of supply air fan:

If the supply air temperature rises to over 45°C, the 
speed of the supply air fan will begin to rise, in attempt to 
stabilise the supply air temperature at 45°C.

2.4 Warnings

Filter timer

To ensure that the filters are changed, and an optimal 

operation is maintained, the controller has a filter timer 

(please se point 14 and 15). When the timer reaches 

the chosen value the display will read “change filter” and 

the red Genvex logo will flash until the filters has been 

changed.

Data error

This error will be shown, if no communication is possible 
between the display and controller. Please control the 
cable connection on the clips 21 – 24.

Frost alert

This error is shown if a water coil is installed in the 
system and the temperature of the water coil is to low. 
Then there is a risk of frost damage. The controller will 
stop the unit and open the valve to the water coil to keep 
the coil warm.

Pressure switch error

When the high pressure switch interrupts, the display will 
read “Pressure switch error” and the red Genvex logo will 

flash until the red reset button is activated.

Содержание Combi 185

Страница 1: ...Version 3 04 0208 GB User Manual Combi 185 L LS S Optima 310 Heat Pump and Domestic Hot Water...

Страница 2: ...ry default scheme 10 2 Function 2 1 Controller Optima 310 11 2 2 Extra capacity 11 2 3 Operation safety 11 2 4 Warnings 11 3 Maintaining 3 1 Connecting to computer 12 3 2 Servicing 12 3 3 Water circui...

Страница 3: ...when the display shows 1 T1 Supply air T2 Room T3 Fresh air T4 Exhaust air T5 Before coil cooling coil T6 Coil cooling T7 D water top T8 D water bottom T9 Solar collector R1 Compressor R3 Air heating...

Страница 4: ...tank while the heat pump continues heating up the lower part to the operating temperature adjusted in menu point 5 8 R8 function This relay may be used as follows If the set point is 0 a circulation p...

Страница 5: ...w suppl It is recommended that the supply air volume is adjusted to 20 lower than the set value in menu point 22 14 Filter change The control system contains an integral timer which counts the time fo...

Страница 6: ...the relevant number of minutes 31 36 When the marker is pointing to menus between 18 and 23 the display heading changes to show actual changing point according to the following format Changepoint Wee...

Страница 7: ...ly from the outside 38 Default values Please notice Before resetting the values please ensure that the actual set points are noted in the scheme page 43 Here is an option for re adjusting the set poin...

Страница 8: ...8 Optima 310 53 Danish Select language 54 English Select language 55 German Select language 56 Polish Select language Danish 54 English 55 German 56 Polish Set point Operations menu Exit OK 5...

Страница 9: ...esday Hours Minutes Le vel Red T2 1 2 3 4 5 6 7 8 9 10 Thursday Hours Minutes Le vel Red T2 1 2 3 4 5 6 7 8 9 10 Friday Hours Minutes Le vel Red T2 1 2 3 4 5 6 7 8 9 10 Saturday Hours Minutes Le vel R...

Страница 10: ...Arrow Up or Arrow Down This will change the clock hour by 1 hour in the desired direction Contrast adjustment Contrast of the display can be changed by pressing the Info button while the program info...

Страница 11: ...il has reached a temperature of app 5 C Then the magnetic valve closes again and the supply air fan and electric heating coil restart operation 2 2 Extra capacity Electric element If the hot water nee...

Страница 12: ...n unbalance and thereby a higher noise level and abrasion of the fans Supply and extract valves Clean the valves by wiping with a dry cloth Make sure the valve does not rotate causing a change in the...

Страница 13: ...t to check that the anode is intact at all times This should be done by inspecting the anode every 2 years and replacing it if it is corroded and measures only 6 10 mm in diameter To inspect the anode...

Страница 14: ...e heating element dismantled The reset button can now be pressed Please notice Be careful not to damage or tear the cables to the control 4 3 Heat pump will not operate Unit has stopped Please control...

Страница 15: ...15 Optima 310...

Страница 16: ...erslev Tel 45 73 53 27 00 Fax 45 73 53 27 07 E Mail salg genvex dk Germany Novelan GmbH D 95359 Kasendorf Tel 49 0 92 28 99 60 7 0 Fax 49 0 92 28 99 60 7 189 E Mail info novelan de Great Britain Total...

Отзывы: