Optima 310

to 0, the unit will run at the 3rd speed until a lower speed 
has been selected manually.

18: Hour

If automatic stepdown at 3rd speed, is in use, the number 
of hours at which the unit is to operate with forced 
air, may be adjusted here. The set point may be adjusted 
between 1 – 10 hours.

19: Suppl .heating (El. or water heated airflow)

By adjusting the set point to 0, the supplementary heat 
will not cut in, even if there is a need for it. If the 
set point is adjusted to 1, the supplementary heat will 
cut in, as needed. This is controlled by the room sensor 
in the control panel.

20: Solar col hyst

If a solar collector has been connected, a temperature 
difference may be set, which must be between the 
water temperature in the solar collector and the 
operating thermostat of the hot water tank, before 
the circulation pump of the solar collector is running. 
When the set temperature of the operating thermostat 
has been reached, the solar collector circulation 
pump will not run, even if the temperature difference 
is larger than the set value. The set point may be set 
between 0 - 5°C.

21: Airflow 1 SUP

Level 1 is the lowest speed which may be used when 
being out of the home, e.g. on holidays or weekends. 
Both fans may be set independently at all levels, to 
achieve the same air volume on the supply side as on the 
extract side, thus giving optimum operation. Initial 
adjustment of the unit must be performed with technical 
air measurement equipment, and may be done without using 
the main adjustment damper. Remember if the air volume is 
set lower than the minimum air volume in point 16, the 
heat pump will switch off. The provisional factory 
setting is 40%.

22: Airflow 2 SUP

Level 2 is the normal operating speed for the unit, 
providing the optimum internal climate and must be 
regulated to the ventilation needs of the individual home. 
The provisional factory setting is 70%.

12: Reduce sup. Air

If set point 1 has been selected under point 11, it is 
recommended that the external temperature is set to -
10°C.The set point may be set between 0 - -15°C.

13: Airflow suppl.

It is recommended that the supply air volume is adjusted 
to 20% lower than the set value in menu point 22.

14: Filter change

The control system contains an integral timer which 
counts the time for which the unit has been in operation 

since the last filter change. It is recommended that the 

set point is initially set to 3, meaning three months. If the 

filters are too dirty, the set point may be reduced. If it is 

unnecessary to change the filters after three months, 

the set point may be increased. The set point may be 
adjusted between 1-6, equal to 1-6 months. When the 

timer reaches the set value for filter change, the red 

Genvex logo will begin to flash on the control panel and 

the words “change filter” will appear on the display. The 

Genvex logo will continue to flash until the filters are 

changed. When the filters are changed the filter timer 

can be reset by pressing ”enter ” in 10-15 sec. until the 

Genvex logo begins to flash again and the equipment is 

back in normal operation.

15: Hold ON-OFF

To avoid forgetting the change of filters allthough the 

Genvex logo is flashing on the control panel, the set 

point may be adjusted to 1. In this case, the unit will 

automatically stop after 14 days, if the filters have not 

been changed in the meantime. If this safety feature is 
not desired, the set point may be adjusted to 0, and the 

Genvex logo will keep on flashing until the filters are 

changed.

16: Min. airflow

To achieve optimum operation of the unit, the unit air 
volume must, as a minimum, conform to the values 
described in the brochure dealing with the actual unit. 
If the air volumes are set lower than the minimum 
requirement, the heat pump will stop and only pre-heated 
air will be blown from the heat exchanger into all rooms. 
The minimum air volume is set by the initial adjustment 
of the unit. The provisional factory setting, is meanwhile 
30%.

17: Extended airflow

At 3rd speed, there is an option of making the unit step 
down automatically to the 2nd speed, after a number of 
hours, by adjusting to set 1. If the set point is adjusted 

>>Min. out. cool. ON

14Filter change

15Hold ON-OFF

16Min. airflow

Set point  

  

Operations menu

Exit

OK

<

>

40

>>Airflow 1 SUP

22Airflow 2 SUP

23Airflow 3 SUP

24Airflow 1 EXT

Set point  

  

Operations menu

Exit

OK

<

>

40

Содержание Combi 185

Страница 1: ...Version 3 04 0208 GB User Manual Combi 185 L LS S Optima 310 Heat Pump and Domestic Hot Water...

Страница 2: ...ry default scheme 10 2 Function 2 1 Controller Optima 310 11 2 2 Extra capacity 11 2 3 Operation safety 11 2 4 Warnings 11 3 Maintaining 3 1 Connecting to computer 12 3 2 Servicing 12 3 3 Water circui...

Страница 3: ...when the display shows 1 T1 Supply air T2 Room T3 Fresh air T4 Exhaust air T5 Before coil cooling coil T6 Coil cooling T7 D water top T8 D water bottom T9 Solar collector R1 Compressor R3 Air heating...

Страница 4: ...tank while the heat pump continues heating up the lower part to the operating temperature adjusted in menu point 5 8 R8 function This relay may be used as follows If the set point is 0 a circulation p...

Страница 5: ...w suppl It is recommended that the supply air volume is adjusted to 20 lower than the set value in menu point 22 14 Filter change The control system contains an integral timer which counts the time fo...

Страница 6: ...the relevant number of minutes 31 36 When the marker is pointing to menus between 18 and 23 the display heading changes to show actual changing point according to the following format Changepoint Wee...

Страница 7: ...ly from the outside 38 Default values Please notice Before resetting the values please ensure that the actual set points are noted in the scheme page 43 Here is an option for re adjusting the set poin...

Страница 8: ...8 Optima 310 53 Danish Select language 54 English Select language 55 German Select language 56 Polish Select language Danish 54 English 55 German 56 Polish Set point Operations menu Exit OK 5...

Страница 9: ...esday Hours Minutes Le vel Red T2 1 2 3 4 5 6 7 8 9 10 Thursday Hours Minutes Le vel Red T2 1 2 3 4 5 6 7 8 9 10 Friday Hours Minutes Le vel Red T2 1 2 3 4 5 6 7 8 9 10 Saturday Hours Minutes Le vel R...

Страница 10: ...Arrow Up or Arrow Down This will change the clock hour by 1 hour in the desired direction Contrast adjustment Contrast of the display can be changed by pressing the Info button while the program info...

Страница 11: ...il has reached a temperature of app 5 C Then the magnetic valve closes again and the supply air fan and electric heating coil restart operation 2 2 Extra capacity Electric element If the hot water nee...

Страница 12: ...n unbalance and thereby a higher noise level and abrasion of the fans Supply and extract valves Clean the valves by wiping with a dry cloth Make sure the valve does not rotate causing a change in the...

Страница 13: ...t to check that the anode is intact at all times This should be done by inspecting the anode every 2 years and replacing it if it is corroded and measures only 6 10 mm in diameter To inspect the anode...

Страница 14: ...e heating element dismantled The reset button can now be pressed Please notice Be careful not to damage or tear the cables to the control 4 3 Heat pump will not operate Unit has stopped Please control...

Страница 15: ...15 Optima 310...

Страница 16: ...erslev Tel 45 73 53 27 00 Fax 45 73 53 27 07 E Mail salg genvex dk Germany Novelan GmbH D 95359 Kasendorf Tel 49 0 92 28 99 60 7 0 Fax 49 0 92 28 99 60 7 189 E Mail info novelan de Great Britain Total...

Отзывы: