550-0687
Page 2
V. WIRING
Wiring for synchronized strobes and horns.
Using this method you may:
w
Use the Gentex GTSM synchronization protocol to provide synchronization of temporal 3 and temporal 4 tones and mute the horn, if required.
NOTICE:
w
THIS APPLIANCE IS NOT RECOMMENDED FOR USE ON CODED OR PULSING SIGNALING CIRCUITS. HOWEVER, USE OF THE GTSM CONTROL MODULE IS PERMITTED TO
SYNCHRONIZE THE HORN.
w
THE FOUR PULSE TEMPORAL PATTERN (TEMPORAL 4) CAN ONLY BE OBTAINED ON THIS PRODUCT WHEN USED IN CONJUNCTION WITH THE GENTEX GTSM
SYNCHRONIZATION MODULE OR GTSM SYNCHRONIZATION PROTOCOL.
w
SEE GTSM CONTROL MODULE MANUAL (550-0632, MANUAL ISSUE DATE (02-01-15) FOR SYNCHRONIZATION MODULE WIRING DIAGRAMS. GTSM MANUAL CAN BE OBTAINED
AT HTTP://WWW.GENTEX.COM/FIRE/PRODUCTS OR CALL GENTEX CORPORATION AT 1-800-436-8391.
Conventional Method:
You may connect the horn directly from a source of rated power without the use of a control module. However, the horns will NOT be synchronized.
CAUtION:
For the GHLF and GHSLF, only the S+ and S- terminals are to be used for
connection to FACP. The H+ and H- terminals are to be used for dBA selection using
provided jumper.
DO NOt APPLY VOLtAGe tO H+ AND H- teRMINALS.
Horn Decibel Levels:
Reverberant Room
Horn Mode
Minimum SPL
at 10Ft. Per ANSI/UL
464 (NORMAL)
Minimum SPL
at 10Ft. Per ANSI/UL
464 (LOUD)
Temporal 3 520 Hz
76.3 dBA
78.8 dBA
Temporal 4 520 Hz
1
80.6 dBA
82.0 dBA
GHSLF PRODUCT INFORMATION
1
Temporal 4 520 Hz measured per ANSI/UL 2075
2
Recommended
GHSLF Horn Decibel Levels and Horn/Strobe Current Ratings
Table A
Room Spacing for Wall-Mounted Visible Appliances per NFPA 72, 2016 Edition
Maximum Room Size
Minimum Required Light Output ( Effective Intensity, Cd)
Meters
Feet
One Light
per Room
Four Lights per Room
(One Light per Wall)
6.10 x 6.10
20 x 20
15
NA
8.53 x 8.53
28 x 28
30
NA
9.14 x 9.14
30 x 30
34
NA
12.2 x 12.2
40 x 40
60
15
13.7 x 13.7
45 x 45
75
19
15.2 x 15.2
50 x 50
94
30
16.5 x 16.5
54 x 54
110
30
16.8 x 16.8
55 x 55
115
30
18.3 x 18.3
60 x 60
135
30
19.2 x 19.2
63 x 63
150
37
20.7 x 20.7
68 x 68
177
43
21.3 x 21.3
70 x 70
184
60
24.4 x 24.4
80 x 80
240
60
27.4 x 27.4
90 x 90
304
95
30.5 x 30.5
100 x 100
375
95
33.5 x 33.5
110 x 110
455
135
36.6 x 36.6
120 x 120
540
135
39.6 x 39.6
130 x 130
635
185
**effective Intensity Requirements for Sleeping Areas
Visible Notification Appliance
Distance from Ceiling to Top of Lens
Intensity
greater than or equal to 24"
110cd
less than 24"
177cd
CAUtION:
Strobe light must be
installed within 16 feet
of the pillow when
used in a sleeping
area.
24VDC Nominal Horn/Strobe
Current Ratings (mA)
Horn/Strobe Current Ratings (UL Max)
2
Over Input Voltage Range of 16-33V (mA)
Candela
Horn Mode
24VDC
Operating
Current
(NORMAL)
24VDC
Operating
Current
(LOUD)
24VFWR
Operating
Current
(NORMAL)
24VFWR
Operating
Current
(LOUD)
Regulated 24VDC
Max. Operating
Current
(NORMAL)
Regulated 24VDC
Max. Operating
Current
(LOUD)
Regulated
24VFWR Max.
Operating
Current (NORMAL)
Regulated
24VFWR Max.
Operating
Current (LOUD)
15
Temporal 3 520 Hz
112.0 mA
144.0 mA
163.0 mA
198.0 mA
124.0 mA
182.0 mA
201.0 mA
252.0 mA
Temporal 4 520 Hz
158.0 mA
175.0 mA
210.0 mA
269.0 mA
195.0 mA
291.0 mA
273.0 mA
339.0 mA
110
Temporal 3 520 Hz
193.0 mA
223.0 mA
259.0 mA
295.0 mA
280.0 mA
326.0 mA
348.0 mA
427.0 mA
Temporal 4 520 Hz
241.0 mA
291.0 mA
325.0 mA
383.0 mA
384.0 mA
474.0 mA
470.0 mA
555.0 mA
177
Temporal 3 520 Hz
268.0 mA
293.0 mA
325.0 mA
329.0 mA
365.0 mA
393.0 mA
465.0 mA
478.0 mA
Temporal 4 520 Hz
337.0 mA
391.0 mA
428.0 mA
477.0 mA
427.0 mA
525.0 mA
639.0 mA
759.0 mA
NA = Not allowable
N/A =24 VDC nominal operating current data not available