background image

550-0687

Page 2

V. WIRING

Wiring for synchronized strobes and horns.

Using this method you may:

w

Use the Gentex GTSM synchronization protocol to provide synchronization of temporal 3 and temporal 4 tones and mute the horn, if required.

NOTICE: 

w

THIS APPLIANCE IS NOT RECOMMENDED FOR USE ON CODED OR PULSING SIGNALING CIRCUITS. HOWEVER, USE OF THE GTSM CONTROL MODULE IS  PERMITTED TO 

SYNCHRONIZE THE HORN.

w

THE FOUR PULSE TEMPORAL PATTERN (TEMPORAL 4) CAN ONLY BE OBTAINED ON THIS PRODUCT WHEN USED IN CONJUNCTION WITH THE GENTEX GTSM 

SYNCHRONIZATION MODULE OR GTSM SYNCHRONIZATION PROTOCOL.

w

SEE GTSM CONTROL MODULE MANUAL (550-0632, MANUAL ISSUE DATE (02-01-15) FOR SYNCHRONIZATION MODULE WIRING DIAGRAMS.  GTSM MANUAL CAN BE OBTAINED 

AT HTTP://WWW.GENTEX.COM/FIRE/PRODUCTS OR CALL GENTEX CORPORATION AT 1-800-436-8391.

Conventional Method:

You may connect the horn directly from a source of rated power without the use of a control module.  However, the horns will NOT be synchronized.  

CAUtION:

For the GHLF and GHSLF, only the S+ and S- terminals are to be used for

connection to FACP.  The H+ and H- terminals are to be used for dBA selection using

provided  jumper.  

DO NOt APPLY VOLtAGe tO H+ AND H- teRMINALS.

Horn Decibel Levels: 

Reverberant Room

Horn Mode

Minimum SPL 

at 10Ft. Per ANSI/UL

464 (NORMAL)

Minimum SPL 

at 10Ft. Per ANSI/UL

464 (LOUD)

Temporal 3 520 Hz

76.3 dBA

78.8 dBA

Temporal 4 520 Hz

1

80.6 dBA

82.0 dBA

GHSLF PRODUCT INFORMATION

1

Temporal 4 520 Hz measured per ANSI/UL 2075

Recommended

GHSLF Horn Decibel Levels and Horn/Strobe Current Ratings

Table A

Room Spacing for Wall-Mounted Visible Appliances per NFPA 72, 2016 Edition

Maximum Room Size

Minimum Required Light Output ( Effective Intensity, Cd)

Meters

Feet

One Light 

per Room 

Four Lights per Room 

(One Light per Wall)

6.10 x 6.10

20 x 20

15

NA

8.53 x 8.53

28 x 28

30

NA

9.14 x 9.14

30 x 30

34

NA

12.2 x 12.2

40 x 40

60

15

13.7 x 13.7

45 x 45

75

19

15.2 x 15.2

50 x 50

94

30

16.5 x 16.5

54 x 54

110

30

16.8 x 16.8

55 x 55

115

30

18.3 x 18.3

60 x 60

135

30

19.2 x 19.2

63 x 63

150

37

20.7 x 20.7

68 x 68

177

43

21.3 x 21.3

70 x 70

184

60

24.4 x 24.4

80 x 80

240

60

27.4 x 27.4

90 x 90

304

95

30.5 x 30.5

100 x 100

375

95

33.5 x 33.5

110 x 110

455

135

36.6 x 36.6

120 x 120

540

135

39.6 x 39.6

130 x 130

635

185

**effective Intensity Requirements for Sleeping Areas

Visible Notification Appliance

Distance from Ceiling to Top of Lens  

Intensity

greater than or equal to 24"

110cd

less than 24"

177cd

CAUtION: 

Strobe light must be

installed within 16 feet

of the pillow when

used in a sleeping

area.

24VDC Nominal Horn/Strobe  

Current Ratings (mA)

Horn/Strobe Current Ratings (UL Max)

2

Over Input Voltage Range of 16-33V (mA)

Candela

Horn Mode

24VDC 

Operating 

Current 

(NORMAL)

24VDC 

Operating 

Current 

(LOUD)

24VFWR

Operating 

Current 

(NORMAL)

24VFWR

Operating 

Current 

(LOUD)

Regulated 24VDC

Max. Operating

Current 

(NORMAL)

Regulated 24VDC

Max. Operating 

Current 

(LOUD)

Regulated

24VFWR Max.

Operating 

Current (NORMAL) 

Regulated 

24VFWR Max.

Operating 

Current (LOUD) 

15

Temporal 3 520 Hz

112.0 mA

144.0 mA

163.0 mA

198.0 mA

124.0 mA

182.0 mA

201.0 mA

252.0 mA

Temporal 4 520 Hz

158.0 mA

175.0 mA

210.0 mA

269.0 mA

195.0 mA

291.0 mA

273.0 mA

339.0 mA

110

Temporal 3 520 Hz

193.0 mA

223.0 mA

259.0 mA

295.0 mA

280.0 mA

326.0 mA

348.0 mA

427.0 mA

Temporal 4 520 Hz

241.0 mA

291.0 mA

325.0 mA

383.0 mA

384.0 mA

474.0 mA

470.0 mA

555.0 mA

177

Temporal 3 520 Hz

268.0 mA

293.0 mA

325.0 mA

329.0 mA

365.0 mA

393.0 mA

465.0 mA

478.0 mA

Temporal 4 520 Hz

337.0 mA

391.0 mA

428.0 mA

477.0 mA

427.0 mA

525.0 mA

639.0 mA

759.0 mA

NA = Not allowable

N/A =24 VDC nominal operating current data not available

Содержание GHSLF Series

Страница 1: ...ficient wiring clearance 1 Run a minimum 18 gauge insulated 2 or more conductor cable 2 Mount a box for each remote signaling appliance Screw bracket onto box Insert signal into bracket and slide to the right firmly into the terminal block receptacle Insert mounting screw as shown and tighten Cover assembly with the plastic housing NOTICE WIRING SHOULD BE CONNECTED TO MOUNTING BRACKET PRIOR TO MOU...

Страница 2: ...t One Light per Room Four Lights per Room One Light per Wall 6 10 x 6 10 20 x 20 15 NA 8 53 x 8 53 28 x 28 30 NA 9 14 x 9 14 30 x 30 34 NA 12 2 x 12 2 40 x 40 60 15 13 7 x 13 7 45 x 45 75 19 15 2 x 15 2 50 x 50 94 30 16 5 x 16 5 54 x 54 110 30 16 8 x 16 8 55 x 55 115 30 18 3 x 18 3 60 x 60 135 30 19 2 x 19 2 63 x 63 150 37 20 7 x 20 7 68 x 68 177 43 21 3 x 21 3 70 x 70 184 60 24 4 x 24 4 80 x 80 2...

Страница 3: ...from bracket 3 Replace unit that was removed to restore wiring supervision and to eliminate system trouble alert 4 Carefully pack the defective unit the manufacturer cannot be responsible for consequential damage due to shipping or mis handling Include a return address and complete details as to the nature of the difficulties being experienced and date of installation 5 Return to Gentex Corporatio...

Страница 4: ...o consumable parts such as batteries cosmetic damage including but not limited to scratches or dents defects caused by normal wear and tear or otherwise due to the normal aging of the appliance or if any serial number has been removed or defaced from the appliance TO THE EXTENT PERMITTED BY LAW THIS WARRANTY AND THE REMEDIES SET FORTH HEREIN ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES REMEDI...

Страница 5: ...ncher dans la prise du réceptacle Mettre la vis de montage comme illustré puis la serrer Recouvrir l ensemble du boîtier de plastique AVIS LES FILS DOIVENT ÊTRE BRANCHÉS AU SUPPORT AVANT D Y POSER L APPAREIL DE SIGNALISATION LE FIL D ALIMENTATION POSITIF DOIT ÊTRE SCINDÉ EN DEUX CHAQUE PARTIE ÉTANT INSÉRÉE DANS LES DEUX BORNES SUPÉRIEURES UN SÉPARATEUR EST EN PLACE POUR ÉVITER QUE LES DEUX FILS SO...

Страница 6: ... 75 19 15 2 x 15 2 50 x 50 94 30 16 5 x 16 5 54 x 54 110 30 16 8 x 16 8 55 x 55 115 30 18 3 x 18 3 60 x 60 135 30 19 2 x 19 2 63 x 63 150 37 20 7 x 20 7 68 x 68 177 43 21 3 x 21 3 70 x 70 184 60 24 4 x 24 4 80 x 80 240 60 27 4 x 27 4 90 x 90 304 95 30 5 x 30 5 100 x 100 375 95 33 5 x 33 5 110 x 110 455 135 36 6 x 36 6 120 x 120 540 135 39 6 x 39 6 130 x 130 635 185 exigences d intensité efficace p...

Страница 7: ...placer l appareil enlevé pour rétablir la fonction de supervision du câblage et supprimer le signal de dérangement 4 Emballer avec soin l appareil défectueux le fabricant n est pas tenu responsable des dommages indirects attribuables à l expédition ou aux erreurs de manutention Indiquer votre adresse et décrire en détail la nature du problème et la date d installation 5 Retourner à Gentex Corporat...

Страница 8: ...ormal de l appareil si le numéro de série de l appareil a été supprimé ou altéré DANS LES LIMITES AUTORISÉES PAR LA LOI LA PRÉSENTE GARANTIE ET LES RECOURS QUI Y SONT DÉFINIS SONT EXCLUSIFS ET REMPLACENT TOUTE AUTRE GARANTIE RECOURS ET CONDITION QU ELLES SOIENT ORALES ÉCRITES LÉGALES EXPRESSES OU IMPLICITES GENTEX DÉCLINE TOUTE GARANTIE LÉGALE ET IMPLICITE Y COMPRIS MAIS NON DE FAÇON LIMI TATIVE T...

Отзывы: