background image

GHLF SeRIeS

GHSLF SeRIeS

ANSI/UL & CAN/ULC COMPLIANT

LOW FReQUeNCY VISIBLe AND/OR AUDIBLe SIGNALING APPLIANCe

I. INtRODUCtION

The Gentex models GHLF and GHSLF are high quality low frequency audible and/or visible signaling appliances.  This appliance is intended to provide a low frequency audible or audible/

visible, depending on the model, notification signal for the purpose of life safety and property protection.  The GHSLF is a fixed candela unit; the candela intensities which can be ordered are 

15 Cd, 110Cd and 177Cd.  The GHSLF strobe is listed in compliance with ANSI/UL 1971, Signaling Appliances for the Hearing Impaired.
This appliance is ideal for any occupancy that requires notification appliances per the applicable building or fire code or wherever dependable alarms are required.  As of January 1, 2014 

NFPA 72 requires that audible appliances installed in sleeping areas produce a low frequency alarm signal.  For your information, the National Fire Protection Association's (NFPA) Standard 72,

2013 Edition, Chapter 18, Section 18.4.5 Sleeping Area Requirements, states the following:

18.4.5.3 Effective January 1, 2014, audible appliances provided for the sleeping areas to awaken occupants shall produce a low frequency alarm signal that complies with the following:

1) The alarm signal shall be a square wave or provide equivalent awakening ability

2) The wave shall have a fundamental frequency of 520Hz ± 10 percent

II. LOCAtION

This appliance is intended for use in fire alarm systems and is to be installed in accordance with this manual, the recommendation of the local authorities having jurisdiction, and other NFPA

documents that provide standards on notification appliances for protective signaling systems.  The GHLF and GHSLF are intended for indoor installations only; these appliances are 

no

t listed

for 

outdoor

or drip proof applications.  

Wall mounted strobe appliances shall have their entire lens at heights above the finished floor of not less than 80 in. (2m) and not greater than 96 in. (2.4m)**.  Spacing shall be in accordance

with Table A.  If a room configuration is not square, the room size that will entirely encompass the room or subdivide the room into multiple squares shall be used.  Wall mounted horn only 

appliances shall have their tops above the finished floors at heights of not less than 90 in. (2.30m) and below the finished ceilings at heights of not less than 6 in. (152mm).  Different mounting

heights shall be permitted by the AHJ provided the sound pressure level requirements of NFPA 72 are met.

III. MOUNtING, ROUGH-IN BOX AND RUN WIRING

This unit is designed for mounting to most single gang boxes, 4" square outlet boxes, 2-gang masonry boxes or non-metallic 2-gang switch boxes.  Conduit entrance to boxes should be 

selected to insure sufficient wiring clearance.

1. Run a minimum 18 gauge insulated 2 or more conductor cable.

2. Mount a box for each remote signaling appliance.  Screw bracket onto box. Insert signal into bracket and slide to the right firmly into the terminal block receptacle. Insert mounting screw as 

shown and tighten. Cover assembly with the plastic housing.

NOTICE:

WIRING SHOULD BE CONNECTED TO MOUNTING BRACKET PRIOR TO MOUNTING SIGNAL.  INCOMING POSITIVE POWER LEAD MUST BE BROKEN AND EACH LEAD IS

TO BE INSERTED INTO EACH OF THE TOP TWO TERMINALS. A BARRIER IS PROVIDED TO PREVENT BOTH LEADS FROM BEING PLACED UNDER THE SAME TERMINAL.

IV. AUDIBLe SIGNALING APPLIANCe OUtPUt

w

The three pulse temporal pattern (temporal 3) is to be used for evacuation use only.

w

The standard fire alarm evacuation signal is a three-pulse temporal pattern.  The pattern consists of the following in this order: 

(1) An “on” phase lasting 0.5 second ± 10 percent 

(2) An “off” phase lasting 0.5 second ± 10 percent for three successive “on” periods 

(3) An “off” phase lasting 1.5 seconds  ± 10 percent 

Total cycle lasts for 4 seconds ± 10 percent

w

The sound output for the temporal 3 tone is rated lower since the time the horn is off is averaged into the sound output rating.  Units have been tested to 0°C, 49°C and 93% humidity.  

w

The four pulse temporal pattern (temporal 4) is to be used for carbon monoxide alarm signal use only. 

w

The standard carbon monoxide alarm is a four pulse temporal pattern.  The audible carbon monoxide alarm signal shall comply with the following:  

(1) Signals shall be a single tone pattern consisting of four cycles of 100 milliseconds ± 10 percent “on” and 100 milliseconds of ± 10 percent “off,” followed by 5 seconds ± 

10 percent “off.” 

(2) After the initial 4 minutes of alarm, the 5-second “off” time shall be permitted to be changed to 60 seconds ± 10 percent.  

w

The four pulse temporal pattern (Temporal 4) can only be obtained on this product when used in conjunction with the Gentex GTSM synchronization module or GTSM synchronization 

protocol.

550-0687

Page 1

ADDItIONAL CAN/ULC LISteD PRODUCt INFORMAtION IS FOUND ON PAGe 4

Horn Decibel Levels: 

Reverberant Room

24VDC Nominal Horn 

Current Ratings (mA)

Horn Current Ratings (UL Max)

2

Over Input Voltage Range of 16-33V (mA)

Horn Mode

Minimum SPL 

at 10Ft. Per

ANSI/UL 464

(NORMAL)

Minimum SPL 

at 10Ft. Per

ANSI/UL 464

(LOUD)

24VDC 

Operating 

Current 

(NORMAL)

24VDC 

Operating 

Current 

(LOUD)

24VFWR 

Operating 

Current 

(NORMAL)

24VFWR 

Operating 

Current 

(LOUD)

Regulated

24VDC Max.

Operating

Current 

(NORMAL)

Regulated 

24VDC Max.

Operating 

Current 

(LOUD)

Regulated 

24VFWR Max.

Operating 

Current 

(NORMAL) 

Regulated 

24VFWR Max.

Operating 

Current 

(LOUD) 

Temporal 3 520 Hz

77.8 dBA

79.8 dBA

72.1 mA

120.1 mA

104.6 mA

158.4 mA

99.4 mA

155.8 mA

152.1 mA

213.5 mA

Temporal 4 520 Hz

1

81.5 dBA

83.4 dBA

75.9 mA

116.0 mA

108.1 mA

182.0 mA

100.1 mA

157.2 mA

163.1 mA

235.2 mA

GHLF PRODUCT INFORMATION

1

Temporal 4 520 Hz measured per ANSI/UL 2075

Recommended

GHLF Horn Decibel Levels and Current Ratings

Содержание GHSLF Series

Страница 1: ...ficient wiring clearance 1 Run a minimum 18 gauge insulated 2 or more conductor cable 2 Mount a box for each remote signaling appliance Screw bracket onto box Insert signal into bracket and slide to the right firmly into the terminal block receptacle Insert mounting screw as shown and tighten Cover assembly with the plastic housing NOTICE WIRING SHOULD BE CONNECTED TO MOUNTING BRACKET PRIOR TO MOU...

Страница 2: ...t One Light per Room Four Lights per Room One Light per Wall 6 10 x 6 10 20 x 20 15 NA 8 53 x 8 53 28 x 28 30 NA 9 14 x 9 14 30 x 30 34 NA 12 2 x 12 2 40 x 40 60 15 13 7 x 13 7 45 x 45 75 19 15 2 x 15 2 50 x 50 94 30 16 5 x 16 5 54 x 54 110 30 16 8 x 16 8 55 x 55 115 30 18 3 x 18 3 60 x 60 135 30 19 2 x 19 2 63 x 63 150 37 20 7 x 20 7 68 x 68 177 43 21 3 x 21 3 70 x 70 184 60 24 4 x 24 4 80 x 80 2...

Страница 3: ...from bracket 3 Replace unit that was removed to restore wiring supervision and to eliminate system trouble alert 4 Carefully pack the defective unit the manufacturer cannot be responsible for consequential damage due to shipping or mis handling Include a return address and complete details as to the nature of the difficulties being experienced and date of installation 5 Return to Gentex Corporatio...

Страница 4: ...o consumable parts such as batteries cosmetic damage including but not limited to scratches or dents defects caused by normal wear and tear or otherwise due to the normal aging of the appliance or if any serial number has been removed or defaced from the appliance TO THE EXTENT PERMITTED BY LAW THIS WARRANTY AND THE REMEDIES SET FORTH HEREIN ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES REMEDI...

Страница 5: ...ncher dans la prise du réceptacle Mettre la vis de montage comme illustré puis la serrer Recouvrir l ensemble du boîtier de plastique AVIS LES FILS DOIVENT ÊTRE BRANCHÉS AU SUPPORT AVANT D Y POSER L APPAREIL DE SIGNALISATION LE FIL D ALIMENTATION POSITIF DOIT ÊTRE SCINDÉ EN DEUX CHAQUE PARTIE ÉTANT INSÉRÉE DANS LES DEUX BORNES SUPÉRIEURES UN SÉPARATEUR EST EN PLACE POUR ÉVITER QUE LES DEUX FILS SO...

Страница 6: ... 75 19 15 2 x 15 2 50 x 50 94 30 16 5 x 16 5 54 x 54 110 30 16 8 x 16 8 55 x 55 115 30 18 3 x 18 3 60 x 60 135 30 19 2 x 19 2 63 x 63 150 37 20 7 x 20 7 68 x 68 177 43 21 3 x 21 3 70 x 70 184 60 24 4 x 24 4 80 x 80 240 60 27 4 x 27 4 90 x 90 304 95 30 5 x 30 5 100 x 100 375 95 33 5 x 33 5 110 x 110 455 135 36 6 x 36 6 120 x 120 540 135 39 6 x 39 6 130 x 130 635 185 exigences d intensité efficace p...

Страница 7: ...placer l appareil enlevé pour rétablir la fonction de supervision du câblage et supprimer le signal de dérangement 4 Emballer avec soin l appareil défectueux le fabricant n est pas tenu responsable des dommages indirects attribuables à l expédition ou aux erreurs de manutention Indiquer votre adresse et décrire en détail la nature du problème et la date d installation 5 Retourner à Gentex Corporat...

Страница 8: ...ormal de l appareil si le numéro de série de l appareil a été supprimé ou altéré DANS LES LIMITES AUTORISÉES PAR LA LOI LA PRÉSENTE GARANTIE ET LES RECOURS QUI Y SONT DÉFINIS SONT EXCLUSIFS ET REMPLACENT TOUTE AUTRE GARANTIE RECOURS ET CONDITION QU ELLES SOIENT ORALES ÉCRITES LÉGALES EXPRESSES OU IMPLICITES GENTEX DÉCLINE TOUTE GARANTIE LÉGALE ET IMPLICITE Y COMPRIS MAIS NON DE FAÇON LIMI TATIVE T...

Отзывы: