IV. WIRING

Wiring for synchronized strobes and horns.

Using this method you may:

w

Use only two wires to synchronize the temporal horn and strobe with the ability to mute the horn (place switches 

1

and 

2

in the ON position on the HS24-177, HS-24, HS-24-WP, HSLP-24-WP, CHS-24A, CHS-24B, CHS-24G, 

CHS-24R, CHS-24A-WP, CHSLP-24A-WP, CHS-24B-WP, CHSLP-24B-WP, CHS-24G-WP, CHSLP-24G-WP, 

CHS-24R-WP, CHSLP-24R-WP).

w

Mute the horn 

only

when the temporal horn option has been selected.

w

Use the Potter Electric AVSM synchronization protocol to provide synchronization and mute the horn, if available.

Wiring for synchronized parallel (unison) horn/strobe operation.

Using this method you may:

w

Use four wires where two wires are used to power and synchronize the strobe and two additional wires are used to 

power and synchronize the horn (place switches 

1

and 

2

in the OFF position on the HS24-177, HS-24, HS-24-WP, HSLP-24-WP, CHS-24A, CHS-24B, CHS-24G, CHS-24R, CHS-24A-WP, 

CHSLP-24A-WP, CHS-24B-WP, CHSLP-24B-WP, CHS-24G-WP, CHSLP-24G-WP, CHS-24R-WP, CHSLP-24R-WP).

w

Choose either continuous horn and allow the FACP to control the horn or choose temporal horn and synchronize the horns with the Potter Electric AVSM synchronization protocol. 

w

Use the Potter Electric AVSM synchronization protocol to provide synchronization and mute the horn, if available.  

NOTICE: 

w

FOR THIS OPTION, SWITCHES 

1

AND 

2

ON THE HS24-177, HS-24, HS-24-WP, HSLP-24-WP, CHS-24A, CHS-24B, CHS-24G, CHS-24R, CHS-24A-WP, CHSLP-24A-WP, CHS-24B-WP, 

CHSLP-24B-WP, CHS-24G-WP, CHSLP-24G-WP, CHS-24R-WP, CHSLP-24R-WP MUST BE IN THE OFF POSITION TO ISOLATE POWER TO THE AUDIBLE AND VISIBLE PORTION OF  

THE CIRCUIT.

w

ALL STROBES ARE DESIGNED TO FLASH AS SPECIFIED WITH CONTINUOUS APPLIED VOLTAGE.  THIS APPLIANCE IS NOT RECOMMENDED FOR USE ON CODED OR PULSING 

SIGNALING CIRCUITS. HOWEVER, USE OF THE AVSM CONTROL MODULE IS PERMITTED TO SYNCHRONIZE THE STROBE AND/OR MUTE THE HORN.

w

REFERENCE AVSM CONTROL MODULE MANUAL (550-0598, DATED 2-1-13) FOR SYNCHRONIZATION MODULE WIRING DIAGRAMS.  AVSM MANUAL CAN BE OBTAINED BY 

CALLING POTTER ELECTRIC SIGNAL COMPANY AT 1-800-325-3936.

Conventional Method:

You may connect both the strobe and the horn directly from a source of rated power without the use of a control module.  However, the horns and strobe lights will NOT be synchronized.  Place

switches 

1

and 

2

in the ON position on the HS24-177, HS-24, HS-24-WP, HSLP-24-WP, CHS-24A, CHS-24B, CHS-24G, CHS-24R, CHS-24A-WP, CHSLP-24A-WP, CHS-24B-WP, 

CHSLP-24B-WP, CHS-24G-WP, CHSLP-24G-WP, CHS-24R-WP, CHSLP-24R-WP to power both the audible and visible from a single pair of power wires. If you wish to power the horn and

strobe from independent sources of power, place switches 

1

and 

2

in the OFF position on the HS24-177, HS-24, HS-24-WP, HSLP-24-WP, CHS-24A, CHS-24B, CHS-24G, CHS-24R, 

CHS-24A-WP, CHSLP-24A-WP, CHS-24B-WP, CHSLP-24B-WP, CHS-24G-WP, CHSLP-24G-WP, CHS-24R-WP, CHSLP-24R-WP and connect power to the appropriate terminals.

CAUTION:

When using only a single power source to 

energize the strobe and horn (switches 1 and 2 in the ON 

position), the in/out wiring must be under the S+ and S- 

terminals only.  Failure to do so may result in damage to your

signal.  For the horn only (EH-24) and strobe only (S24-177,

S-24, S-24-WP, SLP-24-WP, CS-24WA, CS-24WB, CS-24WG,  

CS-24WR, CS-24WA-WP, CSLP-24WA-WP, CS-24WB-WP,

CSLP-24WB-WP, CS-24WG-WP, CSLP-24WG-WP, 

CS-24WR-WP, CSLP-24WR-WP), only the top three terminals

are to be used.  

SWITCH POSITION

TONE

3

4

5

Mechanical Temporal 3

ON

ON

ON

Mechanical - Continuous

OFF

ON

ON

2400Hz - Temporal 3

ON

OFF

ON

2400Hz - Continuous

OFF

OFF

ON

Chime - Temporal 3

ON

ON

OFF

Chime - Continuous

OFF

ON

OFF

Whoop

ON

OFF

OFF

Whoop

OFF

OFF

OFF

NOTICE

w

SWITCH POSITIONS 1 AND 2 IN THE OFF POSITION TO 

SELECT ISOLATED HORN AND STROBE POWER INPUTS

w

SWITCH POSITION 6 ON = HIGH DBA

w

SWITCH POSITION 6 OFF = LOW DBA

CAUTION: 

A jumper card is provided to test for correct

wiring in the supervisory mode only.  DO NOT pass alarm

current through the jumper.

Mounting Bracket:

Allows the installer to pre-wire the system, test for system

supervision, remove the signal head until occupancy,

switch out Potter Electric signals without changing 

mounting brackets and has locking edge connector for

snap-in-place installation.

Instant Voltage Verification:  

It is often necessary to confirm the voltage drop along a

line of devices. The access holes are provided in the back

of the terminal block to allow the voltage to be measured

directly without removing the device. Typically this would

be done at the end of the line to confirm design criteria.

Most measurements will be taken using the S+ and S-

locations although access is provided to other locations. 

NOTICE

: CARE SHOULD BE TAKEN TO NOT SHORT

THE TEST PROBES.

firealarmresources.com

Содержание CHS-24A Series

Страница 1: ...door or drip proof applications The HS 24 WP HSLP 24 WP S 24 WP SLP 24 WP CHS 24A WP CHSLP 24A WP CS 24WA WP CSLP 24WA WP CHS 24B WP CHSLP 24B WP CS 24WB WP CSLP 24WB WP CHS 24G WP CHSLP 24G WP CS 24W...

Страница 2: ...L 3 TONE IS RATED LOWER SINCE THE TIME THE HORN IS OFF IS AVERAGED INTO THE SOUND OUT PUT RATING WHILE THE HORN IS PRODUCING A TONE IN THE TEMPORAL 3 MODE ITS SOUND PRESSURE IS THE SAME AS THE CONTINU...

Страница 3: ...rns and strobe lights will NOT be synchronized Place switches 1 and 2 in the ON position on the HS24 177 HS 24 HS 24 WP HSLP 24 WP CHS 24A CHS 24B CHS 24G CHS 24R CHS 24A WP CHSLP 24A WP CHS 24B WP CH...

Страница 4: ...ONTROL PANEL OPERATING INSTRUCTIONS FOR PROPER OPERATION OF THE PANEL AND FIRE DETECTION SYSTEM SIGNALING APPLIANCE LIMITATION Your horn and horn strobe meet or exceed the current audibility requireme...

Страница 5: ...RATINGS PRODUCT INFORMATION HORN HORN STROBE NOTICE w THE NATIONAL BUILDING CODE AND CAN ULC S525 REQUIRES THAT ALL HORNS USED FOR BUILDING EVACUATION PRODUCE TEMPORAL CODED SIGNALS w THE SOUND OUTPU...

Страница 6: ...L NOT IN ANY CASE EXCEED THE PURCHASE PRICE PAID BY YOU FOR THE APPLIANCE PLEASE NOTE THAT SOME STATES COUNTRIES AND PROVINCES DO NOT ALLOW THE EXCLUSION OR LIMITATION OF INCIDENTAL OR CONSEQUENTIAL D...

Страница 7: ...et des avertisseurs ou stroboscopes muraux doit tre plac e au dessus du plancher fini une hauteur situ e entre 80 po 2 m et 96 po 2 4 m L espacement doit tre conforme ce qui est indiqu au Tableau A L...

Страница 8: ...B CS 24WB CHS 24G CS 24WG CHS 24R et CS 24WR Candela Tension stabilis e maximum de 24 V RDA Courant de fonctionnement mA Tension stabilis e maximum de 24 V RDA Courant de fonctionnement mA 1 15 105 16...

Страница 9: ...position ON pour alimenter les signaux sonores et visuels partir d une seule paire de fils d alimentation Pour alimenter l avertisseur et le stroboscope au moyen de sources d alimentation ind pendante...

Страница 10: ...EMENT APPROPRI DU PANNEAU ET DU SYST ME DE D TECTION D INCENDIE LIMITES DE L APPAREIL DE SIGNALISATION L avertisseur et l avertisseur ou stroboscope sont conformes ou surpassent les exigences d audibi...

Страница 11: ...IS w LE CODE NATIONAL DU B TIMENT ET LA NORME CAN ULC S525 EXIGENT QUE TOUS LES AVERTISSEURS DESTIN S L VACUATION DU B TIMENT DIFFUSENT DES SIGNAUX TEMPORELS CODIFI S w LA PUISSANCE SONORE NOMINALE DU...

Страница 12: ...S OU EXCLUSIONS CI DESSUS POURRAIENT NE PAS S APPLIQUER DANS VOTRE CAS Si un d faut de fabrication ou de mat riau entra ne la d faillance de votre appareil pendant la p riode de garantie vous devez le...

Отзывы: