HS24-177, S24-177, EH-24, HS-24 & S-24 SERIES

ANSI/UL & CAN/ULC COMPLIANT

HS-24-WP, HSLP-24-WP, S-24-WP & SLP-24-WP SERIES

CHS-24A, CS-24WA, CHS-24B, CS-24WB, CHS-24G, 

CS-24WG, CHS-24R & CS-24WR SERIES

CHS-24A-WP, CHSLP-24A-WP, CS-24WA-WP, CSLP-24WA-WP  

CHS-24B-WP, CHSLP-24B-WP, CS-24WB-WP, CSLP-24WB-WP

CHS-24G-WP, CHSLP-24G-WP, CS-24WG-WP, CSLP-24WG-WP

CHS-24R-WP, CHSLP-24R-WP, CS-24WR-WP & CSLP-24WR-WP SERIES

ANSI/UL & CAN/ULC COMPLIANT

VISIBLE AND/OR AUDIBLE 

SIGNALING APPLIANCES

I. INTRODUCTION

The Potter Electric models HS24-177, S24-177, EH-24, HS-24, S-24, HS-24-WP, HSLP-24-WP, S-24-WP, SLP-24-WP, CHS-24A, CS-24WA, CHS-24B, CS-24WB, CHS-24G, CS-24WG, 

CHS-24R, CS-24WR, CHS-24A-WP, CHSLP-24A-WP, CS-24WA-WP, CSLP-24WA-WP, CHS-24B-WP, CHSLP-24B-WP, CS-24WB-WP, CSLP-24WB-WP, CHS-24G-WP, CHSLP-24G-WP, 

CS-24WG-WP, CSLP-24WG-WP, CHS-24R-WP, CHSLP-24R-WP, CS-24WR-WP, CSLP-24WR-WP are high quality audible and/or visible signaling appliances.  The high intensity strobe utilizes

a Xenon flash tube that generates a high-intensity flash visible from all angles.  This appliance is intended to provide a visible, audible or audible/visible, depending on the model, notification 

signal for the purpose of life safety and property protection.  The HS-24, S-24, CHS-24A, CS-24WA, CHS-24B, CS-24WB, CHS-24G, CS-24WG, CHS-24R, CS-24WR are provided with a slider

switch which allows for candela selection at the installation site; the candela intensities which can be selected are 15Cd, 30Cd, 60Cd, 75Cd, or 110Cd.  The HS24-177 and S24-177 are fixed

candela units; the candela intensity which can be ordered is 177Cd.  The HS-24-WP, HSLP-24-WP, S-24-WP, SLP-24-WP, CHS-24A-WP, CHSLP-24A-WP, CS-24WA-WP, CSLP-24WA-WP,

CHS-24B-WP, CHSLP-24B-WP, CS-24WB-WP, CSLP-24WB-WP, CHS-24G-WP, CHSLP-24G-WP, CS-24WG-WP, CSLP-24WG-WP, CHS-24R-WP, CHSLP-24R-WP, CS-24WR-WP, 

CSLP-24WR-WP are fixed candela units, available in a 75 candela intensity only.  This appliance is ideal for any occupancy that requires notification appliances per the applicable building or fire

code or wherever dependable alarms are required.  
The HS24-177, S24-177, HS-24, S-24 strobe is listed in compliance with ANSI/UL 1971, Signaling Appliances for the Hearing Impaired.  The HS-24-WP, HSLP-24-WP, S-24-WP, SLP-24-WP,

CHS-24A, CS-24WA, CHS-24B, CS-24WB, CHS-24G, CS-24WG, CHS-24R, CS-24WR, CHS-24A-WP, CHSLP-24A-WP, CS-24WA-WP, CSLP-24WA-WP, CHS-24B-WP, CHSLP-24B-WP, 

CS-24WB-WP, CSLP-24WB-WP, CHS-24G-WP, CHSLP-24G-WP, CS-24WG-WP, CSLP-24WG-WP, CHS-24R-WP, CHSLP-24R-WP, CS-24WR-WP, CSLP-24WR-WP strobe is listed in 

compliance with ANSI/UL 1638, Visual Signaling Appliances - Private Mode Emergency and General Signaling.  Additionally, colored lens models CHS-24A, CS-24WA, CHS-24B, CS-24WB,

CHS-24G, CS-24WG, CHS-24R, CS-24WR comply with the polar dispersion requirements of ANSI/UL 1971.

II. LOCATION

This appliance is intended for use in Fire Alarm Systems and is to be installed in accordance with this manual, the recommendation of the local authorities having jurisdiction, and other NFPA

documents that provide standards on notification appliances for protective signaling systems.  The HS24-177, S24-177, EH-24, HS-24, S-24, CHS-24A, CS-24WA, CHS-24B, CS-24WB, 

CHS-24G, CS-24WG, CHS-24R, CS-24WR are intended for indoor installations only; this appliance is 

no

t listed for 

outdoor

or drip proof applications.  The HS-24-WP, HSLP-24-WP, S-24-WP,

SLP-24-WP, CHS-24A-WP, CHSLP-24A-WP, CS-24WA-WP, CSLP-24WA-WP, CHS-24B-WP, CHSLP-24B-WP, CS-24WB-WP, CSLP-24WB-WP, CHS-24G-WP, CHSLP-24G-WP, CS-24WG-WP, 

CSLP-24WG-WP, CHS-24R-WP, CHSLP-24R-WP, CS-24WR-WP, CSLP-24WR-WP are intended for indoor or outdoor installations; this appliance is rated for outdoor or drip proof applications

when used in conjunction with the WPBB or WPLPBB Enclosure.
Wall mounted strobe and horn/strobe appliances shall have their entire lens at heights above the finished floor of not less than 80 in. (2m) and not greater than 96 in. (2.4m)**.  Spacing shall be

in accordance with Table A.  If a room configuration is not square, the room size that will entirely encompass the room or subdivide the room into multiple squares shall be used.  Wall mounted

horn only appliances shall have their tops above the finished floors at heights of not less than 90 in. (2.30m) and below the finished ceilings at heights of not less than 6 in. (152mm).  Different

mounting heights shall be permitted by the AHJ provided the sound pressure level requirements of NFPA 72 are met.

III. MOUNTING, ROUGH-IN BOX AND RUN WIRING

This unit is designed for mounting to most single gang boxes, 4" square outlet boxes, 2-gang masonry boxes or non-metallic 2-gang switch boxes.  Conduit entrance to boxes should be 

selected to insure sufficient wiring clearance.

1. Run a minimum 18 gauge insulated 2 or more conductor cable.

2. Mount a box for each remote signaling appliance.  Screw bracket onto box. Insert signal into bracket and slide to the right firmly into the terminal block 

receptacle.  Place housing over mounted assembly and screw together with single screw at the bottom of the signal.  Cover screw with plastic tab.

NOTICE:

WIRING SHOULD BE CONNECTED TO MOUNTING BRACKET PRIOR TO MOUNTING SIGNAL.  INCOMING POSITIVE POWER LEAD MUST BE BROKEN AND EACH LEAD IS

TO BE INSERTED INTO EACH OF THE TOP TWO TERMINALS. IF TWO POWER RUNS ARE MADE TO THE SIGNAL, ONE FOR THE STROBE AND ONE FOR THE HORN, ONLY ONE OF

THE RUNS MUST HAVE ITS POSITIVE LEAD BROKEN AND PLACED UNDER THE TWO SEPARATE TOP TERMINALS. A BARRIER IS PROVIDED TO PREVENT BOTH LEADS FROM

BEING PLACED UNDER THE SAME TERMINAL.

NA = Not allowable

Table A

Room Spacing for Wall-Mounted Visible Appliances per NFPA 72, 2013 Edition

Maximum Room Size

Minimum Required Light Output ( Effective Intensity, Cd)

Meters

Feet

One Light 

per Room 

Four Lights per Room 

(One Light per Wall)

6.10 x 6.10

20 x 20

15

NA

8.53 x 8.53

28 x 28

30

NA

9.14 x 9.14

30 x 30

34

NA

12.2 x 12.2

40 x 40

60

15

13.7 x 13.7

45 x 45

75

19

15.2 x 15.2

50 x 50

94

30

16.5 x 16.5

54 x 54

110

30

16.8 x 16.8

55 x 55

115

30

18.3 x 18.3

60 x 60

135

30

19.2 x 19.2

63 x 63

150

37

20.7 x 20.7

68 x 68

177

43

21.3 x 21.3

70 x 70

184

60

24.4 x 24.4

80 x 80

240

60

27.4 x 27.4

90 x 90

304

95

30.5 x 30.5

100 x 100

375

95

33.5 x 33.5

110 x 110

455

135

36.6 x 36.6

120 x 120

540

135

39.6 x 39.6

130 x 130

635

185

550-0593

Page 1

HS24-177, S24-177, HS-24 AND S-24  PRODUCT INFORMATION

**Effective Intensity Requirements for Sleeping Areas

Visible Notification Appliance

Distance from Ceiling to Top of Lens  

Intensity

greater than or equal to 24"

110cd

less than 24"

177cd

CAUTION: 

Strobe light must be

installed within 16 feet

of the pillow when used

in a sleeping area.

ADDITIONAL CAN/ULC LISTED PRODUCT INFORMATION IS FOUND ON PAGES 5 AND 6

firealarmresources.com

Содержание CHS-24A Series

Страница 1: ...door or drip proof applications The HS 24 WP HSLP 24 WP S 24 WP SLP 24 WP CHS 24A WP CHSLP 24A WP CS 24WA WP CSLP 24WA WP CHS 24B WP CHSLP 24B WP CS 24WB WP CSLP 24WB WP CHS 24G WP CHSLP 24G WP CS 24W...

Страница 2: ...L 3 TONE IS RATED LOWER SINCE THE TIME THE HORN IS OFF IS AVERAGED INTO THE SOUND OUT PUT RATING WHILE THE HORN IS PRODUCING A TONE IN THE TEMPORAL 3 MODE ITS SOUND PRESSURE IS THE SAME AS THE CONTINU...

Страница 3: ...rns and strobe lights will NOT be synchronized Place switches 1 and 2 in the ON position on the HS24 177 HS 24 HS 24 WP HSLP 24 WP CHS 24A CHS 24B CHS 24G CHS 24R CHS 24A WP CHSLP 24A WP CHS 24B WP CH...

Страница 4: ...ONTROL PANEL OPERATING INSTRUCTIONS FOR PROPER OPERATION OF THE PANEL AND FIRE DETECTION SYSTEM SIGNALING APPLIANCE LIMITATION Your horn and horn strobe meet or exceed the current audibility requireme...

Страница 5: ...RATINGS PRODUCT INFORMATION HORN HORN STROBE NOTICE w THE NATIONAL BUILDING CODE AND CAN ULC S525 REQUIRES THAT ALL HORNS USED FOR BUILDING EVACUATION PRODUCE TEMPORAL CODED SIGNALS w THE SOUND OUTPU...

Страница 6: ...L NOT IN ANY CASE EXCEED THE PURCHASE PRICE PAID BY YOU FOR THE APPLIANCE PLEASE NOTE THAT SOME STATES COUNTRIES AND PROVINCES DO NOT ALLOW THE EXCLUSION OR LIMITATION OF INCIDENTAL OR CONSEQUENTIAL D...

Страница 7: ...et des avertisseurs ou stroboscopes muraux doit tre plac e au dessus du plancher fini une hauteur situ e entre 80 po 2 m et 96 po 2 4 m L espacement doit tre conforme ce qui est indiqu au Tableau A L...

Страница 8: ...B CS 24WB CHS 24G CS 24WG CHS 24R et CS 24WR Candela Tension stabilis e maximum de 24 V RDA Courant de fonctionnement mA Tension stabilis e maximum de 24 V RDA Courant de fonctionnement mA 1 15 105 16...

Страница 9: ...position ON pour alimenter les signaux sonores et visuels partir d une seule paire de fils d alimentation Pour alimenter l avertisseur et le stroboscope au moyen de sources d alimentation ind pendante...

Страница 10: ...EMENT APPROPRI DU PANNEAU ET DU SYST ME DE D TECTION D INCENDIE LIMITES DE L APPAREIL DE SIGNALISATION L avertisseur et l avertisseur ou stroboscope sont conformes ou surpassent les exigences d audibi...

Страница 11: ...IS w LE CODE NATIONAL DU B TIMENT ET LA NORME CAN ULC S525 EXIGENT QUE TOUS LES AVERTISSEURS DESTIN S L VACUATION DU B TIMENT DIFFUSENT DES SIGNAUX TEMPORELS CODIFI S w LA PUISSANCE SONORE NOMINALE DU...

Страница 12: ...S OU EXCLUSIONS CI DESSUS POURRAIENT NE PAS S APPLIQUER DANS VOTRE CAS Si un d faut de fabrication ou de mat riau entra ne la d faillance de votre appareil pendant la p riode de garantie vous devez le...

Отзывы: