HS-24-WP, HSLP-24-WP, S-24-WP, SLP-24-WP, CHS-24A-WP, CHSLP-24A-WP, CS-24WA-WP, CSLP-24WA-WP, CHS-24B-WP, 

CHSLP-24B-WP, CS-24WB-WP, CSLP-24WB-WP, CHS-24G-WP, CHSLP-24G-WP, CS-24WG-WP, CSLP-24WG-WP, 

CHS-24R-WP, CHSLP-24R-WP, CS-24WR-WP AND CSLP-24WR-WP PRODUCT INFORMATION

Models

Color Lens

CHS-24A-WP, CHSLP-24A-WP, 

CS-24WA-WP, CSLP-24WA-WP

Amber

CHS-24B-WP, CHSLP-24B-WP, 

CS-24WB-WP, CSLP-24WB-WP

Blue

CHS-24G-WP, CHSLP-24G-WP, 

CS-24WG-WP, CSLP-24WG-WP

Green

CHS-24R-WP, CHSLP-24R-WP, 

CS-24WR-WP, CSLP-24WR-WP

Red

NOTICE:

DC VOLTAGE RANGE LIMITS: 16-33V.  FWR VOLTAGE RANGE LIMITS: 16-33V.  THIS PRODUCT WAS ONLY TESTED TO

THE STATED VOLTAGE RANGE(S); DO NOT APPLY 80% AND 110% OF THIS RANGE FOR SYSTEM OPERATION.

24VDC CLEAR & AMBER Lens Outdoor 

Strobe Current Ratings

Use with HS-24-WP, HSLP-24-WP, S-24-WP,

SLP-24-WP, CHS-24A-WP, CHSLP-24A-WP, 

CS-24WA-WP, and CSLP-24WA-WP Products

Candela

Regulated 24VDC 

Max. Operating 

Current (mA)

Regulated 24VFWR

Max. Operating 

Current (mA)

75

170

263

24VDC BLUE, GREEN & RED Lens Outdoor 

Strobe Current Ratings

Use with CHS-24B-WP, CHSLP-24B-WP, 

CS-24WB-WP, CSLP-24WB-WP, CHS-24G-WP, 

CHSLP-24G-WP, CS-24WG-WP, CSLP-24WG-WP, 

CHS-24R-WP, CHSLP-24R-WP, CS-24WR-WP 

and CSLP-24WR-WP Products

Candela

Regulated 24VDC 

Max. Operating 

Current (mA)

Regulated 24VFWR

Max. Operating 

Current (mA)

75

164

278

AMBER Lens Indoor Strobe Current Ratings

Use with CHS-24A and CS-24WA Products

Candela

Regulated 24VDC 

Max. Operating 

Current (mA)

Regulated 24VFWR

Max. Operating 

Current (mA)

15

47

82

30

64

112

60

113

178

75

145

213

110

178

259

CHS-24A, CS-24WA, CHS-24B, CS-24WB, CHS-24G, CS-24WG, CHS-24R AND CS-24WR PRODUCT INFORMATION

BLUE, GREEN & RED Lens Indoor 

Strobe Current Ratings

Use with CHS-24B, CS-24WB, CHS-24G, 

CS-24WG, CHS-24R and CS-24WR Products

Candela

Regulated 24VDC 

Max. Operating 

Current (mA)

Regulated 24VFWR

Max. Operating 

Current (mA)

15

105

164

30

130

196

60

203

325

75

243

355

110

310

491

Models

Color Lens

CHS-24A, CS-24WA

Amber

CHS-24B, CS-24WB

Blue

CHS-24G, CS-24WG

Green

CHS-24R, CS-24WR

Red

NOTICE

: DC VOLTAGE RANGE LIMITS: 16-33V.  FWR VOLTAGE RANGE LIMITS: 16-33V.  THIS PRODUCT WAS ONLY TESTED TO

THE STATED VOLTAGE RANGE(S); DO NOT APPLY 80% AND 110% OF THIS RANGE FOR SYSTEM OPERATION.

HORN DECIBEL AND CURRENT RATINGS PRODUCT INFORMATION

NOTICE:

w

THE THREE PULSE TEMPORAL PATTERN IS TO BE USED FOR EVACUATION USE ONLY.

w

THE SOUND OUTPUT FOR THE TEMPORAL 3 TONE IS RATED LOWER SINCE THE TIME THE HORN IS OFF IS AVERAGED INTO THE SOUND OUT PUT RATING.  WHILE THE HORN IS PRODUCING A TONE 

IN THE TEMPORAL 3 MODE ITS SOUND PRESSURE IS THE SAME AS THE CONTINUOUS MODE.  UNITS HAVE BEEN TESTED TO 0°C, 49°C AND 93% HUMIDITY.   

* Operating the horn in this mode at this voltage will result in not meeting the minimum ANSI/UL 464 sound level required for public mode fire protection service.  

These settings are acceptable only for private mode fire alarm signaling use.  Use the high dBA setting for public mode applications (the chime tone is always private mode).

550-0593

Page 2

Strobe light cannot be seen when objects such as doors, furniture or walls block strobe light.

NOTICE: 

w

THE VISUAL SIGNAL MUST BE IN THE DIRECT VIEWING AREA OF THE OCCUPANT IN ORDER TO BE SEEN.

w

VISUAL SIGNALS FOR THE HEARING IMPAIRED ARE ONLY ONE METHOD OF ALERTING THE HEARING IMPAIRED.  VISUAL SIGNALS MAY NOT BE THE PREFERRED METHOD 

FOR NOTIFYING ALL HEARING IMPAIRED INDIVIDUALS.

w

THE STROBE LIGHT MUST BE SEEN BY THE SLEEPING PERSON.  IF THE PERSON HAS HEAD TURNED OR OTHERWISE UNABLE TO BE ALERTED BY VISUAL, THE STROBE 

WILL NOT BE EFFECTIVE.

24VDC CLEAR Lens Indoor Strobe Current Ratings

HS24-177 and 

S24-177 Series

Available Candela

S-24 and HS-24

Series Available

Candela

Strobe

Candela

Regulated 24VDC

Max. Operating 

Current(mA)

Regulated 24VFWR 

Max. Operating 

Current (mA)

24VDC 

Nominal Operating

Current (mA) 

w

15

42

77

30

w

30

58

102

42

w

60

97

161

66

w

75

116

225

80

w

110

161

256

103

w

177

213

341

N/A

NOTICE:

DC VOLTAGE RANGE LIMITS: 16-33V.  FWR

VOLTAGE RANGE LIMITS: 16-33V.  THIS PRODUCT WAS

ONLY TESTED TO THE STATED VOLTAGE RANGE(S); DO

NOT APPLY 80% AND 110% OF THIS RANGE FOR 

SYSTEM OPERATION.
N/A: 24VDC nominal operating current data not available

Horn Decibel Levels:

Reverberant Room

Horn Current Ratings Over 

Input Voltage Range of 16-33V

24VDC Nominal Horn 

Current Ratings

Horn Mode

Minimum SPL

at 10Ft. Per

ANSI/UL 464

(HIGH)

Minimum SPL

at 10Ft. Per

ANSI/UL 464

(LOW)

Regulated 24VDC

Max. Operating

Current (mA)

HIGH Setting

Regulated 24VFWR

Max. Operating

Current (mA) 

HIGH Setting

24VDC Operating

Current (mA) 

HIGH Setting

24VFWR Operating

Current (mA)

HIGH Setting

Temp 3 2400Hz

78 dBA

71* dBA

28

48

10.7

26.8

Temp 3 Mechanical

76 dBA

70* dBA

25

44

9.7

24.5

Temp 3 Chime

70* dBA

66* dBA

15

30

8.6

20.6

Continuous 2400Hz

81 dBA

74* dBA

28

48

20.4

43.7

Continuous Mechanical

80 dBA

72* dBA

25

44

17.0

39.3

Continuous Chime

70* dBA

66* dBA

15

30

9.6

23.0

Whoop

82 dBA

69* dBA

56

62

45.4

60.2

firealarmresources.com

Содержание CHS-24A Series

Страница 1: ...door or drip proof applications The HS 24 WP HSLP 24 WP S 24 WP SLP 24 WP CHS 24A WP CHSLP 24A WP CS 24WA WP CSLP 24WA WP CHS 24B WP CHSLP 24B WP CS 24WB WP CSLP 24WB WP CHS 24G WP CHSLP 24G WP CS 24W...

Страница 2: ...L 3 TONE IS RATED LOWER SINCE THE TIME THE HORN IS OFF IS AVERAGED INTO THE SOUND OUT PUT RATING WHILE THE HORN IS PRODUCING A TONE IN THE TEMPORAL 3 MODE ITS SOUND PRESSURE IS THE SAME AS THE CONTINU...

Страница 3: ...rns and strobe lights will NOT be synchronized Place switches 1 and 2 in the ON position on the HS24 177 HS 24 HS 24 WP HSLP 24 WP CHS 24A CHS 24B CHS 24G CHS 24R CHS 24A WP CHSLP 24A WP CHS 24B WP CH...

Страница 4: ...ONTROL PANEL OPERATING INSTRUCTIONS FOR PROPER OPERATION OF THE PANEL AND FIRE DETECTION SYSTEM SIGNALING APPLIANCE LIMITATION Your horn and horn strobe meet or exceed the current audibility requireme...

Страница 5: ...RATINGS PRODUCT INFORMATION HORN HORN STROBE NOTICE w THE NATIONAL BUILDING CODE AND CAN ULC S525 REQUIRES THAT ALL HORNS USED FOR BUILDING EVACUATION PRODUCE TEMPORAL CODED SIGNALS w THE SOUND OUTPU...

Страница 6: ...L NOT IN ANY CASE EXCEED THE PURCHASE PRICE PAID BY YOU FOR THE APPLIANCE PLEASE NOTE THAT SOME STATES COUNTRIES AND PROVINCES DO NOT ALLOW THE EXCLUSION OR LIMITATION OF INCIDENTAL OR CONSEQUENTIAL D...

Страница 7: ...et des avertisseurs ou stroboscopes muraux doit tre plac e au dessus du plancher fini une hauteur situ e entre 80 po 2 m et 96 po 2 4 m L espacement doit tre conforme ce qui est indiqu au Tableau A L...

Страница 8: ...B CS 24WB CHS 24G CS 24WG CHS 24R et CS 24WR Candela Tension stabilis e maximum de 24 V RDA Courant de fonctionnement mA Tension stabilis e maximum de 24 V RDA Courant de fonctionnement mA 1 15 105 16...

Страница 9: ...position ON pour alimenter les signaux sonores et visuels partir d une seule paire de fils d alimentation Pour alimenter l avertisseur et le stroboscope au moyen de sources d alimentation ind pendante...

Страница 10: ...EMENT APPROPRI DU PANNEAU ET DU SYST ME DE D TECTION D INCENDIE LIMITES DE L APPAREIL DE SIGNALISATION L avertisseur et l avertisseur ou stroboscope sont conformes ou surpassent les exigences d audibi...

Страница 11: ...IS w LE CODE NATIONAL DU B TIMENT ET LA NORME CAN ULC S525 EXIGENT QUE TOUS LES AVERTISSEURS DESTIN S L VACUATION DU B TIMENT DIFFUSENT DES SIGNAUX TEMPORELS CODIFI S w LA PUISSANCE SONORE NOMINALE DU...

Страница 12: ...S OU EXCLUSIONS CI DESSUS POURRAIENT NE PAS S APPLIQUER DANS VOTRE CAS Si un d faut de fabrication ou de mat riau entra ne la d faillance de votre appareil pendant la p riode de garantie vous devez le...

Отзывы: