Instructions

 

 Procedure 

 

 

Part No. 1258800

 

Software Update 

 

Procedure 

Note: Perform this procedure on a flat level surface, 
with the boom and jib in the stowed position. 

Software Version 

Note: Before proceeding, verify the version of 
software installed on your machine.

 

1

 

At the TCON, turn the key switch to ground 
controls and pull out the red Emergency Stop 
button. 

2

 

Read and record the scroll message on the 
display (example: VER 2_10 is version 2.10). 

3

 

Push in the red Emergency Stop button. 

Limit Switch Rework 

For machines equipped with platform overload 
protection and software version less than 3.00

 

The platform overload limit switch LSP1OLS must 
be replaced before proceeding with the software 
upgrade. 

Calibration Information 

After the installation of the Application Software is 
complete, the machine will have to go through a 
complete calibration process. Refer to the 
appropriate Service Manual for your machine. 

Loading the Software onto a 
Computer or Laptop 

Note: Loading software onto your computer 
requires that you must have administrative 
rights to download executable files.

 

1

 

Turn on the computer or laptop. 

Note: If the WebGPI Software Update Zip files 
have been downloaded from the Firmware site, 
continue to the Application Software Installation. 

2

 

Insert the thumb drive (Genie part 
number 1258799) into the computer or laptop. 

Note: If the WebGPI Update files are not displayed 
on your computer, go to 

My Computer

 and locate 

the 

Removable Disk

3

 

Select each of the three application files one at 
a time. 

 

Содержание Z-135/70

Страница 1: ...Installation Instructions Software Update Z 135 70 ZX 135 70 Part No 1258800 Rev A...

Страница 2: ...lt is expected after performing a series of steps Indicates than an incorrect result has occurred after performing a series of steps Note These installation instructions only apply to the Genie models...

Страница 3: ...ion 3 00 or higher continue to the Application Software Installation Machines not equipped with platform overload protection continue to the Application Software Installation Before proceeding verify...

Страница 4: ...t one of the following telephone numbers United States 800 536 1800 Canada 425 881 1800 Europe UK 0044 1476 584 333 France 0033 237 260 986 Germany 0049 4221 491 821 Iberica 0034 935 725 090 Italy 003...

Страница 5: ...placed before proceeding with the software upgrade Calibration Information After the installation of the Application Software is complete the machine will have to go through a complete calibration pro...

Страница 6: ...the Choose Destination screen record the default destination folder and select Next 6 On the Setup Type screen select Typical then select Next Note After pressing Next you will see a series of file n...

Страница 7: ...art number 107647 between the gray connector and the SCON 4 Connect the laptop DB9 cable to the Tee Harness 5 At the TCON turn the key switch to ground controls and pull out the red Emergency Stop but...

Страница 8: ...eters 9 Select Tilt Sensors Params Read and record the Tilt Angle Matrix Gains parameters 10 Click on the Disconnect icon 11 Click on the Connect icon 12 Click on the Download icon 13 Select File type...

Страница 9: ...download button Cycle the power off then back on at the red Emergency Stop Button at the TCON 17 Click on the Download button 18 When the Kernel file is at 100 cycle the power off then back on at the...

Страница 10: ...rs that were recorded in step 9 Note The numbers must be entered accurately The SCON can not be calibrated in the field If the numbers are not accurate the machine will not operate or level properly 2...

Страница 11: ...y switch to ground controls and pull out the red Emergency Stop button 4 Open WebGPI and click on the Connect icon Note The current application software file will be shown at the top of the screen exa...

Страница 12: ...827306 HEX 7 Select S0827306 HEX and then click on Open 8 Click on the Download button Note This download can take 10 to 30 minutes depending on the speed of your serial connection If your computer ti...

Страница 13: ...on at the TCON 11 Click on the Application icon 12 Select Set All Defaults Select Ok 13 When prompted select Level 2 enter SG81355 for the password and select Accept 14 Push in the red Emergency Stop...

Страница 14: ...t both control boxes 4 Open WebGPI and click on the Connect icon Note The current application software file will be shown at the top of the screen example S0676201 for older software Note If Check pow...

Страница 15: ...5 6 Select File Type Kernel 7 Click on the Search button and locate application software S0828306 HEX 8 Select S0828306 HEX and then click on Open 9 Click on the Force download button Cycle the power...

Страница 16: ...he power off then back on at the red Emergency Stop Button at the TCON 16 Select RSJ1AO Function Check 17 Enter the following settings Sensor voltage range 60 Timeout 10 Lower Deadband 75 Min Movement...

Отзывы: