Instructions
Rev A
Procedure
14 Software
Update
Part No. 1258800
PCON Software Update
1
Open the platform control box and set the
fasteners aside.
2
Connect the computer DB9 cable to the PCON
PCB.
3
At the TCON, turn the key switch to platform
controls and pull out the red Emergency Stop
buttons at both control boxes.
4
Open WebGPI™ and click on the
Connect
icon.
Note: The current application software file will be
shown at the top of the screen. (example:
S0676201 for older software)
Note: If
Check power and serial connection
is
displayed, confirm power is on at the TCON and
check the connection between the computer and
PCON.
Note: If
Attempting to establish connection
is
displayed, check your serial port COM settings.
The COM port settings can vary between
computers.
5
Click on the
Download
icon.