background image

Instructions

 

Rev A

 

Procedure 

 
 
 

 

 

16 Software 

Update

 

Part No. 1258800 

 

 

10

 

Click on the 

Download

 button. 

 

11

 

When the 

Kernel

 file is at 100%, cycle the 

power off, then back on at the red Emergency 
Stop Button at the PCON. 

 

12

 

Click on the 

Exit

 button, then the 

Application

 

icon. 

 

13

 

Select 

Set All Defaults

. Select 

Ok

 

14

 

When prompted, select 

Level 2,

 enter 

SG81355 

for the password and select 

Accept

15

 

Cycle the power off, then back on at the red 
Emergency Stop Button at the TCON. 

16

 

Select 

RSJ1AO Function Check

17

 

Enter the following settings: 

Sensor voltage 

range %, 60

Timeout, 10

Lower Deadband, 

75

Min Movement Value, 22

18

 

When prompted, select 

Level 2,

 enter 

SG81355 

for the password and select 

Accept

19

 

Push in the red Emergency Stop Button and 
disconnect the DB9 cable from the PCON 
PCB.  

20

 

Close the platform control box and securely 
tighten the retaining fasteners. 

21

 

Calibrate the machine. Refer to the 
appropriate Service Manual for you 
machine.

 

Instructions 

Part No. 1258800 

Rev A 

Software Update 

 

Содержание Z-135/70

Страница 1: ...Installation Instructions Software Update Z 135 70 ZX 135 70 Part No 1258800 Rev A...

Страница 2: ...lt is expected after performing a series of steps Indicates than an incorrect result has occurred after performing a series of steps Note These installation instructions only apply to the Genie models...

Страница 3: ...ion 3 00 or higher continue to the Application Software Installation Machines not equipped with platform overload protection continue to the Application Software Installation Before proceeding verify...

Страница 4: ...t one of the following telephone numbers United States 800 536 1800 Canada 425 881 1800 Europe UK 0044 1476 584 333 France 0033 237 260 986 Germany 0049 4221 491 821 Iberica 0034 935 725 090 Italy 003...

Страница 5: ...placed before proceeding with the software upgrade Calibration Information After the installation of the Application Software is complete the machine will have to go through a complete calibration pro...

Страница 6: ...the Choose Destination screen record the default destination folder and select Next 6 On the Setup Type screen select Typical then select Next Note After pressing Next you will see a series of file n...

Страница 7: ...art number 107647 between the gray connector and the SCON 4 Connect the laptop DB9 cable to the Tee Harness 5 At the TCON turn the key switch to ground controls and pull out the red Emergency Stop but...

Страница 8: ...eters 9 Select Tilt Sensors Params Read and record the Tilt Angle Matrix Gains parameters 10 Click on the Disconnect icon 11 Click on the Connect icon 12 Click on the Download icon 13 Select File type...

Страница 9: ...download button Cycle the power off then back on at the red Emergency Stop Button at the TCON 17 Click on the Download button 18 When the Kernel file is at 100 cycle the power off then back on at the...

Страница 10: ...rs that were recorded in step 9 Note The numbers must be entered accurately The SCON can not be calibrated in the field If the numbers are not accurate the machine will not operate or level properly 2...

Страница 11: ...y switch to ground controls and pull out the red Emergency Stop button 4 Open WebGPI and click on the Connect icon Note The current application software file will be shown at the top of the screen exa...

Страница 12: ...827306 HEX 7 Select S0827306 HEX and then click on Open 8 Click on the Download button Note This download can take 10 to 30 minutes depending on the speed of your serial connection If your computer ti...

Страница 13: ...on at the TCON 11 Click on the Application icon 12 Select Set All Defaults Select Ok 13 When prompted select Level 2 enter SG81355 for the password and select Accept 14 Push in the red Emergency Stop...

Страница 14: ...t both control boxes 4 Open WebGPI and click on the Connect icon Note The current application software file will be shown at the top of the screen example S0676201 for older software Note If Check pow...

Страница 15: ...5 6 Select File Type Kernel 7 Click on the Search button and locate application software S0828306 HEX 8 Select S0828306 HEX and then click on Open 9 Click on the Force download button Cycle the power...

Страница 16: ...he power off then back on at the red Emergency Stop Button at the TCON 16 Select RSJ1AO Function Check 17 Enter the following settings Sensor voltage range 60 Timeout 10 Lower Deadband 75 Min Movement...

Отзывы: