Air Handler
13
The heating mode temperature rise is dependent upon the system airflow, the supply voltage,
and the heater kit size (KW) selected. Use Tables 8-10
to determine the temperature rise(ºF).
N/ATable 8
CFM
HEATER KIT NOMINAL KW
5
10
15
20
600
28
56
N/A
N/A
800
21
42
N/A
N/A
1000
17
34
50
N/A
1200
14
28
42
56
1400
12
24
36
48
1600
10
21
31
42
1800
9
19
28
37
230/1/60 Supply Voltage-Temperature Rise Table ºF
Table 9
CFM
HEATER KIT NOMINAL KW
5
10
15
20
600
27
52
N/A
N/A
800
20
40
N/A
N/A
1000
16
32
48
N/A
1200
13
27
40
53
1400
11
23
34
46
1600
10
20
30
40
1800
9
18
27
36
220/1/60 Supply Voltage-Temperature Rise Table ºF
Table 10
CFM
HEATER KIT NOMINAL KW
5
10
15
20
600
25
50
N/A
N/A
800
19
38
N/A
N/A
1000
15
30
46
N/A
1200
13
25
38
56
1400
11
22
33
48
1600
9
19
28
42
1800
8
17
25
37
208/1/60 Supply Voltage-Temperature Rise Table ºF.
Note:
For installations not indicated above the following formula is to be used:
TR= (kW*3412)*(Voltage Correction)*1.08/CFM
Where: TR=Temperature Rise
KW=Heater Kit Actual kW
3412=Btu per kW
Voltage Correction= 0.96(230 Supply Volts)
0.92(220 Supply Volts)
0.87(208 Supply Volts)
1.08=Constant CFM=Measured Airflow