44-00-0297
SHERLOCK
102/202 REV. 4.1 05-02-15
25
HELPFUL HINTS AND STARTUP GUIDE
When the monitor is first turned on, it will count down from 90 seconds in order to warm up the sensors. Allow the sensors to
run for at least two hours after the initial start up to read accurately.
The Control must be put into ALL ACCESS MODE to make changes in the
SYSTEM CONFIG MENU
. The Control must be
put into IN CHANGE MODE to make changes in other menus.
TEST RELAY MENU
is useful to check out the proper wiring connection between the audio and visual alarming devices and
the relay outputs.
For the initial start up, begin with the
ACCESS MENU
, set the Control to ALL ACCESS MODE
.
enable sensors in
SYSTEM
CONFIG MENU,
modify setpoints in
SETPOINT MENU
and then set the clock in
SET CLOCK MENU
. When the sensor
reading is stable (2 hours), calibrate the sensors in the
CALIBRATION MENU
.
The monitor has an internal buzzer in addition to a optional strobe light that can be mounted on the monitor. The buzzer can
be silenced during an alarm condition by pushing any buttons on the Control. However the strobe light if installed will remain
active as long as alarm level 1 is activated.
The K2 and K4 alarm relay can be silenced using the Alarm Silent Button on the front panel. During an alarm condition, press-
ing this button will silence these relays (returned to non-alarm state). Keep this in mind when wiring the relays. If you do not
want that output to be silenced, do not wire that output to the K2 or K4 relay (i.e. Do not wire the exhaust fans to the K2 or K4
relay.). If the SYSTEM is in CHANGE MODE, pressing the Alarm Silent Button again within ten seconds will clear the alarm.
The alarm can also be cleared in ALARM MENU.
The K3/K4 relay for level 2 alarm has a programmable alarm clear delay. If the alarm condition automatically cleared for level 2
alarm. The delay timer starts counting down. The relays will be de-activated after the count down. It can be programmed from 2
to 240 minutes.
The K1/K2 can be programmed to energize in an alarm condition (N.O.) or de-energize in an alarm condition (N.C.). If N.C.
mode is selected, power loss to the control will activate the alarm contact.
Each alarm level has its own latching feature. Therefore if the user would like for alarm levels 1 to reset itself but have alarm
level 2 be manually reset, they can program it this way.
All the menus and sub-menus wrap around.
The alarm delays are measured in minutes.
An alarm cannot be silenced while in a menu or a submenu.
The time in the control is military time: i.e. 11:00 a.m. = 11:00 and 11:00 p.m. = 23:00.
The display backlight will always be on.
HELPFUL HINTS
Содержание SHERLOCK 102
Страница 3: ...44 00 0297 SHERLOCK102 202 REV 4 1 05 02 15 4 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 11: ...44 00 0297 SHERLOCK102 202 REV 4 1 05 02 15 12 IR SENSOR ...
Страница 49: ...44 00 0297 SHERLOCK102 202 REV 4 1 05 02 15 50 PAGE FOR FIELD WIRING SHERLOCK SYSTEM ...
Страница 51: ...44 00 0297 SHERLOCK102 202 REV 4 1 05 02 15 52 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 53: ......