44-00-0297
SHERLOCK
102/202 REV. 4.1 05-02-15
39
TEST MENU
This menu is provided to facilitate wiring checks for each
output. When entering into this menu. the relays retain their
operating states. The relays can be turned ON (Energized) or
OFF (De-Energized) by the user. The N.O. or N.C. settings on
alarm relays have no effect on the test. When exiting from this
menu, the preset states for all settings prior to entering this menu
will be resumed. Refer to the input/output diagram on page 20.
TEST RELAY K1
This feature is used to test each dry contact relay. One at a time.
Press
SELECT
button to toggle between "ON" and "OFF".
Down arrow to move to the next screen.
Follow the same procedure for
LVL1 SIL-ALM, LVL2
ALARM, LVL2 SIL-ALM,
and also optional zone
isolation
relays
ZONE A ALM, ZONE A SIL,
and
ZONE B ALM,
ZONE B SIL,
if installed.
TEST HORN/STROBE AND STROBE LIGHT INPUT
HORN/STROBE
and
STROBE LIGHT
can be used to direct
connect a 12 VDC Strobe or Horn/Strobe so as not to use any
relays. This screen can be used to test the wiring for each.
Press
SELECT
button to toggle between
"ON"
and
"OFF"
to
activate the alarm device connected to
HORN/STROBE
. Do
the same for
STROBE LIGHT
.
TEST 4-20 MILLIAMP OUTPUT
This feature tests the optional 4-20mA This output located on
the input/output board.
Press the
SELECT
button. The reading for the
Sensor A
PPM
level will begin to blink. Press the
UP
or
DOWN
arrow. The
blinking number will go up or down between 0 ppm and 1500
ppm. Press the
SELECT
button to save this entry and to read the
current output. Do the same for
Sensor B
if applicable.
RESTART
This function is only necessary if for some reason the control
will not operate properly. Doing restart will not clear any previ-
ous settings already input. This is equivalent to powering down
and powering back up.
Press the
SELECT
button. The "NO" ("YES") will begin to
blink indicating that the controller is in the Change mode. Press
UP/DOWN arrow buttons to change to "YES" ("NO"), press
SELECT
button to save this entry.
The control will then ask for a confirmation. Press the
SELECT
button. The "NO" ("YES") will begin to blink indicating that
the controller is in the Change mode. Press UP/DOWN arrow
buttons to change to "YES" ("NO"), press
SELECT
button to
save this entry.
RE-START
will automatically begin.
Exit this menu and return to DEFAULT SCREEN. All relay
outputs will return to their operating states prior to entering test
menu.
SELECT/
CHANGE
SELECT/
CHANGE
<TEST MENU>
SELECT/
CHANGE
EXIT
<T> TOGGLE RELAY
LVL1 ALARM:
<T> TOGGLE RELAY
LVL1 ALARM: OFF
<T> TOGGLE RELAY
LVL1 ALARM: ON
REPEAT FOR UP TO 8 RELAYS
SELECT/
CHANGE
<TESTING>TOGGLE
AUX1 STROBE : ON
<TESTING>TOGGLE
HORN/STROBE: OFF
SELECT/
CHANGE
<TST>TEST 4-20MA
WHEN SNR A= XX
<TST>TEST 4-20MA
WHEN SNR A= XX
<TST> RE-START
CONFIRM: NO
<TST> RE-START
THIS CONTROL : NO
SELECT/
CHANGE
SELECT/
CHANGE
SELECT/
CHANGE
<TST> RE-START
THIS CONTROL : YES
<TST> RE-START
CONFIRM: YES
SELECT/
CHANGE
<TST> RE-START
IN 2 SECONDS ...
Содержание SHERLOCK 102
Страница 3: ...44 00 0297 SHERLOCK102 202 REV 4 1 05 02 15 4 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 11: ...44 00 0297 SHERLOCK102 202 REV 4 1 05 02 15 12 IR SENSOR ...
Страница 49: ...44 00 0297 SHERLOCK102 202 REV 4 1 05 02 15 50 PAGE FOR FIELD WIRING SHERLOCK SYSTEM ...
Страница 51: ...44 00 0297 SHERLOCK102 202 REV 4 1 05 02 15 52 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 53: ......