Model TA502A
4.3 Setup Mode Selection Table
OPTION DESCRIPTION
ENTER
SELECTION
Password
Enter the Password, if the Password is enabled
Inhibit Mode
Enter the Inhibit Mode, if Desired
Operating
Mode
Selection for use with Standard 4-20mA field devices
(IR400, IR5500) “
Std
”, “
Obs
” Observer Series, “
Sur
”
Surveyor, Model TS400 “
400
”, Model TS420 “
420
”
Set Display
Range
Display will indicate “
Sr
” then select the Sensor Range
0-1.0, 0-2.0, 0-5.0, 0-10.0… Up to 0-100 (In increments
of 5 units, 0-200, 0-500.
Display
Multiplier
Display will indicate “
dis
” then select the Display
Multiplier X 1, x 10, or x 100.
A2 Alarm
Set the Energized (En) / De-Energized (dE) Option
Set the Latching (LA) / Non-Latching (nL) Option
Set the High alarm set point
A1 Alarm
Set the Energized (En) / De-Energized (dE) Option
Set the Latching (LA) / Non-Latching (nL) Option
Set the Low alarm set point
Fault/Inhibit
Set the fault to Activate (Ac) or not (nA) during Inhibit
Mode
Card Test
The Display will indicate “
ct
” for 5 seconds
Password
Options
Set the Password to be Disabled (Pd) or Enabled (PE)
If the Password option to be changed from Disabled to
Enabled:
Set the password digits
Left__________
Right__________
Setup
Check Mode
After all of the options have been selected, the TA502A
will enter the Setup Check Mode.
Table 13: Setup Mode Selection Table