29
Model TA502A
4.4.8 Card Test Options
After the Fault/Inhibit option has been selected, the user will select the ramp time (
1
,
3
or
10
seconds) and whether or not the alarm outputs will activate during a Card
Test. The display will indicate
ct
for about five seconds (Figure 32).
Figure 32: Entering Card Test Options
Following
ct
, the ramp-up time (
1
,
3
or
10
) during the card test (Figure 33) will be
displayed.
3
as the factory default for this selection.
Figure 33: Card Test Ramp Time, 1 / 3 / 10
Next, the display will indicate the alarm output option during a Card Test as either
Ac
,
active or
nA
, not active (Figure 34).
Not Active
is the factory default for this
selection.