26
In the serial port parameter area, the following contents are read/write
bit status (read function code is 0x03, write function code is 0x06)
8000
48001
RS485
from
immediately
Initial value: 1. Parameter
range: 1 to 254
8001
48002
RS485 baud
rate
Initial value 0:38 400
0:38 400/1:48 00/2:9 when
good, 5200, 600/600/200/4:57
and optional
8002
48003
RS485
protocol
Initial value: 0:modbus RTU
Zero: the modbus RTU; 1:
Automatic reporting
8003
48004
RS485 data
format
Initial value:
0:8-E-1.Parameter range:
0:8-E-1;
8 - O - 1;"- N -
1;Then - E - 1; 4:7-O-1
(meaning: data bit - parity -
stop bit)
8004
48005
RS485
duplex
mode
Initial value: H-L.
Zero: H
- L;1:L-H
8005
48006
RS485
continuous
transmission
interval
Scope: 0 ~ 9999
8006-8099.
48007-48100.
The reserved
In the network port parameter area, the following contents are read/write
bit status (read function code is 0x03, write function code is 0x06)
8100
48101
Network port
communication
mode
Zero: the modbus
TCP/IP;1: Automatic
reporting
8101
48102
Network port high
and low bytes
0: h-L 1: L-h, initial value:
0
8102
48103
Network
port
Sending interval
Scope: 0 ~ 9999
8103
48104
IP
address
segment 1 of the
network port
IP address.
Initial value:
192.168.101.246
This
parameter
ranges
from
0.0.0.0
to
255.255.255.255
8104
48105
IP
address
segment 2 of the
network port
8105
48106
IP
address
Содержание GMT-H1