1-800-345-8207
6
Section 2 - System Overview
The Nitrogen Generator operates using membrane technology. The smaller oxygen and water vapor molecules can pass
through (permeate) the membrane quickly. The larger nitrogen molecules are less likely to diffuse through the separator
tubes; therefore, they continue downstream to the separator outlet. The permeated molecules are discharged to the atmos-
phere through a vent in the separator casing.
The Nitrogen Generator is specifically designed to provide clean, dry, high purity nitrogen for use in fire protection sprin-
kler systems. The generator is a fully assembled package ready to be connected to a new or existing fire sprinkler system
using a factory pre-engineered air compressor. These turn-key systems include all air filtration equipment required to keep
the generator operating at peak efficiency.
Figure 1: NGP-1000D M2/M3 System Diagram
Product Designation
Outlet Pipe Connections, NPS
Sprinkler System Capacity
Bypass Capacity (Gallon)
NPG-1000D-M2
1/2
3880
925
NPG-1000D-M3
1/2
6500
925
OPTIONAL ANALYZER
QUICK CONNECT
NITROGEN
SOLENOID
VALVE
VALVE
CHECK
VALVE
CHECK
SEPARATOR
OUT TO
DRAIN
TIMED DRAIN
SOLENOID
VALVE
FILTER
COALESCING
FILTER
5 MICRON
(GREEN HANDLE)
NITROGEN TEST PORT VALVE
INLET
OUTLET
VALVE
(YELLOW HANDLE)
BYPASS VALVE
VENT
NITROGEN
AIR
ORIFICE
ANALYZER
NITROGEN
CHECK
(BLUE HANDLE)
NITROGEN “OUTLET”
(BLUE HANDLE)
“INLET”
NITROGEN
GAUGE
PRESSURE
NITROGEN TANK
PG
CONTROL
FLOW
OUTLET
PERMEATE
MEMBRANE
NITROGEN
GAUGE
PRESSURE
MEMBRANE
PG
FILTER
COALESCING
Содержание NGP-1000D-M2
Страница 2: ...2 1 800 345 8207 ...
Страница 7: ...1 800 345 8207 7 Figure 2 Typical NGP 1000D M2 M3 External View ...
Страница 31: ...1 800 345 8207 31 Section 18 Wiring Diagrams ...