Section 16 - Normal Operating Parameters
The Nitrogen Generator System uses a two tank system design to deliver high purity nitrogen to the fire protection
system.The pressure switch on the air storage tank controls the air compressor by turning it on and off at the desired pressure
set points. Another pressure switch on the nitrogen tank controls the nitrogen solenoid valve on the inside of the cabinet.
Whenever the nitrogen storage tank requires nitrogen, the nitrogen solenoid valve opens allowing air to come from the air
storage tank. Once the nitrogen storage tank reaches the desired set point the nitrogen solenoid closes.
•
Periodic (typically less than 10 times an hour) running of the air compressor is expected.
•
Periodic (typically less than 12 times a day) opening and closing of the nitrogen solenoid is expected.
•
When the nitrogen solenoid valve is closed, the membrane pressure gauge will read “0”.
•
The automatic drain valve automatically releases condensate from the unit.
NOTE:
These are typical durations. Actual times may be slightly longer or shorter. These are typical pressure set points.
Actual pressure can be ±3 PSI.
Operational State
1*3'
5HFRUGHG3DUDPHWHU
$LU&RPSUHVVRU2))3UHVVXUH
105 PSI
$LU&RPSUHVVRU213UHVVXUH
85 PSI
7LPH,QWHUYDOWREXLOGSUHVVXUHIURP36,WR36,LQ
DLUVWRUDJHWDQN
1 Minute
1LWURJHQ6ROHQRLG2))3UHVVXUH1LWURJHQ7DQN3UHVVXUH
75 PSI
1LWURJHQ6ROHQRLG213UHVVXUH1LWURJHQ7DQN3UHVVXUH
60 PSI
7LPH,QWHUYDOWREXLOGSUHVVXUHIURP36,WR36,LQ
DLUWDQNVWRUDJHLQ%\SDVV0RGH
2 minutes
7LPH,QWHUYDOWREXLOGSUHVVXUHIURP36,WR36,LQ
DLUWDQNVWRUDJHLQ1LWURJHQ0RGH
20 minutes
Operational State
1*3'0 1*3'0
5HFRUGHG3DUDPHWHU
$LU&RPSUHVVRU2))3UHVVXUH
105 PSI
105 PSI
$LU&RPSUHVVRU213UHVVXUH
85 PSI
85 PSI
7LPH,QWHUYDOWREXLOGSUHVVXUH
IURP36,WR36,LQDLU
VWRUDJHWDQN
1 minute
1 minute
1LWURJHQ6ROHQRLG2))3UHVVXUH
1LWURJHQ7DQN3UHVVXUH
75 PSI
75 PSI
1LWURJHQ6ROHQRLG213UHVVXUH
1LWURJHQ7DQN3UHVVXUH
60 PSI
60 PSI
7LPH,QWHUYDOWREXLOGSUHVVXUH
IURP36,WR36,LQDLUWDQN
VWRUDJHLQ%\SDVV0RGH
2 minutes
2 minutes
7LPH,QWHUYDOWREXLOGSUHVVXUH
IURP36,WR36,LQDLUWDQN
VWRUDJHLQ1LWURJHQ0RGH
14 minutes
8 minutes