Installation

Automatic Transfer Switch Owner’s Manual

13

Auxiliary Contacts

See 

Figure 3-4

. Auxiliary contacts on the transfer switch

are available to operate customer accessories, remote
advisory lights, or remote annunciator devices. A suitable
power source must be connected to the common termi-
nal (D). Auxiliary contact (A) is optional. 

Figure 3-4. Auxiliary Contacts

Auxiliary contact (B) operation is shown in the following
chart:

NOTE: Auxiliary Contacts are rated 10 amps at 125 or
250 volts AC. 

Fault Current Label

See 

Figure 3-5

. A Fault Current Identification Label is

provided in the bag containing the unit Owner’s Manual
and transfer switch manual operating handle. The 2017
NEC requires that the short-circuit current rating of the
transfer equipment, based on the type of overcurrent pro-
tective device protecting the transfer equipment, be field
marked on the exterior of the transfer equipment. For
NEC compliance, verify the required short-circuit current
rating of the transfer switch before installation. The com-
pleted label provides the local AHJ (Authority Having
Jurisdiction) with the information he or she may require
during inspection.
Apply the label to the exterior of the transfer switch enclo-
sure. Use a pen to fill in the required information, and
then cover the label with the clear protective decal.

Figure 3-5. Fault Current Label

A

Auxiliary Contact (Actuated)

B

Auxiliary Contact (Non-Actuated)

C

Single Contact (Utility Position)

D

Common Terminal

E

Normally Open Terminal

F

Normally Closed Terminal

Switch Position

Utility

Standby

Common to Normally Open

Open

Closed

Common to Normally Closed

 Closed

 Open

(000134a)

CAUTION

Equipment damage. Exceeding rated voltage and 
current will damage the auxiliary contacts. Verify 
that voltage and current are within specification 
before energizing this equipment.

000140

A

B

C

D

E

F

004496

Содержание RXSW400A3CUL

Страница 1: ...AC COM 1 888 GENERAC 888 436 3722 Para espa ol visita http www generac com service support product support lookup Pour le fran ais visiter http www generac com service support product support lookup S...

Страница 2: ...ii Automatic Transfer Switch Owner s Manual 000393a WARNING CANCER AND REPRODUCTIVE HARM www P65Warnings ca gov...

Страница 3: ...ner Load 11 Auxiliary Contacts 13 Fault Current Label 13 Section 4 Operation Functional Tests and Adjustments 15 Manual Operation 15 Close to Normal Source Side 16 Close to Standby Source Side 16 Retu...

Страница 4: ...iv Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Страница 5: ...unsafe Throughout this publication and on tags and decals affixed to the unit DANGER WARNING CAUTION and NOTE blocks are used to alert personnel to special instructions about a particular operation th...

Страница 6: ...ng and connections to unit Failure to follow proper installation requirements could result in death serious injury and equipment or property damage 000120 CAUTION Equipment damage Verify all conductor...

Страница 7: ...000213 DANGER Electrocution Only authorized personnel should access transfer switch interior Transfer switch doors should be kept closed and locked Failure to do so will result in death or serious in...

Страница 8: ...Introduction and Safety 4 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Страница 9: ...UL listed transfer switch has locking provisions for the utility entry cabinet In addition it has a lockout tagout provision for the service entrance circuit breaker Transfer Switch Mechanism See Figu...

Страница 10: ...s affixed to the equipment The following publications outline the safe use of transfer switches Canadian Electrical Code CE CSA C22 1 NFPA 70E Standard for Electrical Safety In The Workplace UL CUL 10...

Страница 11: ...top priorities then use additional SMMs as the remaining priorities A SMM can share a priority with an A C priority on the SACM provided the generator is sized to handle the combined surge load from b...

Страница 12: ...General Information 8 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Страница 13: ...to it Mount the switch vertically to a rigid supporting structure To pre vent switch distortion level all mounting points If neces sary use washers behind mounting holes to level the unit Open Enclosu...

Страница 14: ...ent to which they will be subjected based on the 75 C column of tables charts etc used to size con ductors The installation must comply fully with all appli cable codes standards and regulations Knock...

Страница 15: ...tor within the equipment cable or conduit See NEC 300 3 C 1 Connecting SACM See Figure 3 3 The SACM can control an air conditioner 24 VAC directly Control of Air Conditioner Load 1 Route the thermosta...

Страница 16: ...t 2 D Air Conditioner 2 E Thermostat 3 F Air Conditioner 3 G Thermostat 4 H Air Conditioner 4 T1 fused Battery Charge N1 fused Utility Sense N2 fused Utility Sense 0 Ground 194 12 VDC 23 Transfer Cont...

Страница 17: ...transfer equipment be field marked on the exterior of the transfer equipment For NEC compliance verify the required short circuit current rating of the transfer switch before installation The com ple...

Страница 18: ...Installation 14 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Страница 19: ...Operation See Figure 4 1 A manual handle A is shipped with the transfer switch Manual operation must be checked BEFORE the transfer switch is operated electrically Proceed as follows to check manual o...

Страница 20: ...MM manufac turer s literature for additional information Utility Voltage Checks 1 Turn ON the UTILITY power supply to the transfer switch with whatever means provided such as the UTILITY main line cir...

Страница 21: ...transfer switch 5 Set transfer switch utility service disconnect circuit breaker to ON CLOSED 6 Set generator main circuit breaker to ON 7 Select AUTO on generator panel The system is now ready for au...

Страница 22: ...e test pushbutton will work when the ATS is in the utility or the generator position Figure 4 2 Test Pushbutton and Fuse Removal Installation Tool 1 Turn on the utility supply to the ATS 2 Verify mana...

Страница 23: ...nual 19 Section 5 Drawings and Diagrams Installation Drawing No 0K2438 A 400A Service Entrance Rated PP PP PP PP PP PP PP 3 2 86720 5 6833 2 7 21 PP 127 25 5 5 7 1 6 21 8 76 0867 17 5 2 1 5 20321 176...

Страница 24: ...rams 20 Automatic Transfer Switch Owner s Manual Interconnection Drawing No 10000041110 Part 1 of 2 Liquid Cooled Generator GROUP G INTERCONNECTION DIAGRAM ID 400A CUL SACM DRAWING 10000041110 REVISIO...

Страница 25: ...ings and Diagrams Automatic Transfer Switch Owner s Manual 21 No 10000041110 Part 2 of 2 Air Cooled Generator GROUP G INTERCONNECTION DIAGRAM ID 400A CUL SACM DRAWING 10000041110 REVISION A DATE 07 18...

Страница 26: ...s 22 Automatic Transfer Switch Owner s Manual Schematic and Wiring Diagram No 10000041100 Part 1 of 2 Schematic Diagram SCHEMATIC DIAGRAM SERVICE ENTRANCE W SMART AC MODULE DRAWING 10000041100 REVISIO...

Страница 27: ...awings and Diagrams Automatic Transfer Switch Owner s Manual 23 No 10000041100 Part 2 of 2 Wiring Diagram WIRING DIAGRAM SERVICE ENTRANCE W SMART AC MODULE DRAWING 10000041100 REVISION A DATE 07 31 20...

Страница 28: ...Drawings and Diagrams 24 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Страница 29: ...Drawings and Diagrams Automatic Transfer Switch Owner s Manual 25 This page intentionally left blank...

Страница 30: ...Drawings and Diagrams 26 Automatic Transfer Switch Owner s Manual This page intentionally left blank...

Страница 31: ......

Страница 32: ...ights reserved Specifications are subject to change without notice No reproduction allowed in any form without prior written consent from Generac Power Systems Inc Generac Power Systems Inc S45 W29290...

Отзывы: