General Information
Automatic Transfer Switch Owner’s Manual
7
Four LEDs, located on the SACM (B), illuminate when a
load is connected and powered.
The SACM has a test button (C) that is used to simulate
an overload condition. This button operates even when
the transfer signal is inactive. The generator control wir-
ing is connected to terminals (D).
Smart Management Module (SMM)
See
. Any loads, including central air condi-
tioners, can be managed using an optional Smart Man-
agement Module (SMM). The system can accommodate
up to eight individual SMMs.
Figure 2-4. Smart Management Module (SMM)
NOTE:
SMMs are self-contained and have individual
built-in controllers.
Application Considerations
Generator overload condition is determined by generator
frequency. Loads are shed when frequency is less than
58 Hz for three seconds or less than 50 Hz for ½ second
(for 60 Hz systems).
The SACM can be used in conjunction with individual
SMMs to manage a combined total of eight loads.
•
Use Priorities A/C 1-4 on the SACM as the top priori-
ties, then up to four SMMs as Priorities 5-8.
•
Use only select A/C priorities on the SACM as the top
priorities, then use additional SMMs as the remaining
priorities.
•
A SMM can share a priority with an A/C priority on
the SACM provided the generator is sized to handle
the combined surge load from both appliances. Shar-
ing priorities can allow up to 12 loads to be managed
in a properly sized system.
In any combination of modules, the recovery times after a
loss of utility power or shutdown due to overload are
shown in
.
Refer to the SMM Owner’s/Installation Manual for
detailed characteristics and specifications of that product.
Table 2-1. Customer Wiring Connections
Terminal Numbering
Decal
Wire Numbers
BLUE NO. 3 *
T1 - Fused 120-240 VAC for battery charger
YELLOW
NO. 1 & NO. 2
N1 & N2 - Fused 240 VAC - Sensing for
utility dropout and pickup
BLACK NO.1 **
0 - DC (-) Common ground wire
RED NO. 2
194 - DC (+) 12 VDC for transfer controls
WHITE NO. 3
23 - Transfer control signal wire
* Must be connected to keep battery charged whether unit is
running or not.
** Required if generator is paired with Generac Smart Power
management transfer switch.
000106
Priority Settings
Priority
Recovery Time
SACM
SMM
1
5 minutes
Yes
Yes
2
5 minutes 15 seconds
Yes
Yes
3
5 minutes 30 seconds
Yes
Yes
4
5 minutes 45 seconds
Yes
Yes
5
6 minutes
NA
Yes
6
6 minutes 15 seconds
NA
Yes
7
6 minutes 30 seconds
NA
Yes
8
6 minutes 45 seconds
NA
Yes
Содержание RXSW400A3CUL
Страница 4: ...iv Automatic Transfer Switch Owner s Manual This page intentionally left blank...
Страница 8: ...Introduction and Safety 4 Automatic Transfer Switch Owner s Manual This page intentionally left blank...
Страница 12: ...General Information 8 Automatic Transfer Switch Owner s Manual This page intentionally left blank...
Страница 18: ...Installation 14 Automatic Transfer Switch Owner s Manual This page intentionally left blank...
Страница 28: ...Drawings and Diagrams 24 Automatic Transfer Switch Owner s Manual This page intentionally left blank...
Страница 29: ...Drawings and Diagrams Automatic Transfer Switch Owner s Manual 25 This page intentionally left blank...
Страница 30: ...Drawings and Diagrams 26 Automatic Transfer Switch Owner s Manual This page intentionally left blank...
Страница 31: ......