FUNCTIONAL TESTS AND

ADJUSTMENTS

Following transfer switch installation and interconnection, 

inspect the entire installation carefully. A competent, qualified 

electrician should inspect it. The installation should comply 

strictly with all applicable codes, standards, and regulations. 

When absolutely certain the installation is proper and correct, 

complete a functional test of the system.

 

 

Perform functional tests in the exact order 

presented in this manual, or damage could be 

done to the switch.

IMPORTANT:

 Before proceeding with functional tests, read and 

make sure all instructions and information in this section are 

understood. Also read the information and instructions of labels 

and decals affixed to the switch. Note any options or accessories 

that might be installed and review their operation.

3.2   MANUAL OPERATION

 

 

Do NOT manually transfer under load. 

Disconnect transfer switch from all power 

sources by approved means, such as the main 

circuit breaker(s).

A manual HANDLE is shipped with the transfer switch. Manual 

operation must be checked BEFORE the transfer switch is operated 

electrically. To check manual operation, proceed as follows:
1.  Turn the generator’s AUTO/OFF/MANUAL switch to OFF.
2.  Turn OFF both UTILITY (service disconnect circuit breaker) 

and GENERATOR (generator main line circuit breaker) power 

supplies to the transfer switch.

3.  Note position of transfer mechanism main contacts by 

observing the moveable contact carrier arm. This can be 

viewed through the long narrow slot in the inside cover of the 

ATS. The top of the moveable contact carrier arm is yellow to 

be easily identified.

• Manual operation handle in the UP position - LOAD terminals 

(T1, T2) are connected to UTILITY terminals (N1, N2).

• Manual operation handle in the DOWN position - LOAD termi-

nals (T1, T2) are connected to EMERGENCY terminals (E1, 

E2).

 

 

Do not use excessive force when operating the 

transfer switch manually or damage could be 

done to the manual handle.

3.2.1   CLOSE TO UTILITY SOURCE SIDE

Before proceeding, verify the position of the switch by observing 

the position of manual operation handle in Figure 3.1. If the handle 

is UP, the contacts are closed in the NORMAL (UTILITY) position, 

no further action is required. If the handle is DOWN, proceed with 

Step 1.
Step 1:  With the handle inserted into the moveable contact carrier 

arm, move handle UP. Be sure to hold on to the handle as 

it will move quickly after the center of travel.

Step 2:  Remove manual operating handle from moveable contact 

carrier arm. Return handle to storage bracket.

3.2.2   CLOSE TO GENERATOR SOURCE SIDE

Before proceeding, verify the position of the switch by observ-

ing the position of the manual operation handle in Figure 3.1. If 

the handle is DOWN, the contacts are closed in the GENERATOR 

(STANDBY) position. No further action is required. If the handle is 

UP, proceed with Step 1.
Step 1:  With the handle inserted into the moveable contact carrier 

arm, move the handle DOWN. Be sure to hold on to the 

handle as it will move quickly after the center of travel.

Step 2:  Remove manual operating handle from moveable contact 

carrier arm. Return handle to storage bracket.

3.2.3   RETURN TO UTILITY SOURCE SIDE

Step 1:  Manually actuate switch to return manual operating handle 

to the UP position.

Step 2:  Remove manual operating handle from moveable contact 

carrier arm. Return handle to storage bracket.

3.3 VOLTAGE 

CHECKS

1.  Turn ON the UTILITY power supply to the transfer switch using 

the UTILITY SERVICE DISCONNECT circuit breaker.



PROCEED WITH CAUTION. THE TRANSFER 

SWITCH IS NOW ELECTRICALLY HOT. 

CONTACT WITH LIVE TERMINALS RESULTS 

IN EXTREMELY HAZARDOUS AND POSSIBLY 

FATAL ELECTRICAL SHOCK.

2.   With an accurate AC voltmeter, check for correct voltage. 

Measure across ATS terminal lugs N1 and N2. Also check N1 

to NEUTRAL and N2 to NEUTRAL.

3.  When certain that UTILITY supply voltage is correct and compat-

ible with transfer switch ratings, turn OFF the UTILITY supply to 

the transfer switch.

4.   On the generator panel, set the AUTO/OFF/ MANUAL switch to 

MANUAL position. The generator should crank and start.

5.   Let the generator stabilize and warm up at no-load for at least 

five minutes.

6.   Set the generator's main circuit breaker (CB1) to its ON or 

CLOSED position.

Operation

Содержание RTS automatic

Страница 1: ...This manual should remain with the unit Technical Manual RTS Automatic Transfer Switch...

Страница 2: ...ORMAL UTILITY power source by means of an approved transfer switch Failure to properly isolate the NORMAL and STANDBY power sources from each other may result in injury or death to electric utility wo...

Страница 3: ...ove the Negative Neg or battery cable Safety Rules Inside Front Cover General Information 2 1 1 Introduction 2 1 2 Unpacking 2 1 3 Equipment Description 2 1 3 1 Transfer Switch Mechanism 2 1 3 2 Utili...

Страница 4: ...o be switched Solderless screw type terminal lugs are standard Switch Wire Conductor Tightening Rating Range Torque 100A 14 1 0 AWG 50 in lbs 200A 6 250 MCM 275 in lbs This transfer switch is suitable...

Страница 5: ...FER SWITCH ENCLOSURE ThestandardswitchenclosureisaNationalElectricalManufacturer s Association NEMA and UL 3R type UL and NEMA 3R type enclo sures primarily provide a degree of protection against fall...

Страница 6: ...bitor Use a torque wrench to tighten the conductors being sure not to overtighten or damage to the switch base could occur If not tightened enough a loose connection would result causing excess heat w...

Страница 7: ...coil voltage The LSM supplies a fused 5A 120 Vac to energize the coils of the relay contactors L1 L2 L3 and L4 1 Mount the contactor module and connect the load to the main contacts 2 Connect the con...

Страница 8: ...position of the switch by observing the position of manual operation handle in Figure 3 1 If the handle is UP the contacts are closed in the NORMAL UTILITY position no further action is required If t...

Страница 9: ...s main circuit breaker CB1 to its OFF or OPEN position 9 Set the AUTO OFF MANUAL switch to the OFF position to shut down the generator NOTE Do NOT proceed until generator AC output voltage and fre qu...

Страница 10: ...erator run at no load for several minutes Then shut down by setting the AUTO OFF MANUAL switch to its OFF position 8 Move the transfer switch s main contacts back to their UTIL ITY position For exampl...

Страница 11: ...9 9 Notes...

Страница 12: ...10 Notes...

Страница 13: ...11 100A SE non SE 150 200A non SE Installation Drawing No 0G6832 A Installation Diagrams...

Страница 14: ...Installation Diagrams 150 200A SE Installation Drawing No 0H4905 A 12...

Страница 15: ...13 13 Installation Drawing No 0J0814 B Installation Diagrams...

Страница 16: ...14 14 Electrical Data Interconnection Drawing No 0H8676 C...

Страница 17: ...15 15 Interconnection Drawing No 0H7454 C Electrical Data...

Страница 18: ...16 Electrical Data Schematic Drawing No 0H7254 B...

Страница 19: ...17 Schematic Drawing No 0H7254 B Electrical Data...

Страница 20: ...18 Exploded Views Parts Lists 100A Assembly Drawing No 0H7264 H...

Страница 21: ...0E3484 1 DECAL MANUAL OPERATING HANDLE 25 0F9969 1 DECAL UTILITY DISCONNECT 26 0G4220 1 DECAL NEUTRAL CONNECTION 27 067210A 1 DECAL GROUNDING LUG 28 0G0900 1 DECAL UL LIST HSB ITEM PART NO QTY DESCRI...

Страница 22: ...20 Exploded Views Parts Lists 150A Assembly Drawing No 0J2006 D Parts List on page 22...

Страница 23: ...21 150A Assembly Drawing No 0J2006 D Exploded Views Parts Lists Parts List on page 22...

Страница 24: ...2 0H7917 1 DECAL TERMINAL STRIP 33 0H1480 1 DECAL TEST SEQUENCE 34 0G3274 1 DECAL LIVE CIRCUIT ENG FRN SPN ITEM PART NO QTY DESCRIPTION 35 0G3259 1 DECAL TERMINAL SHOCK HZD BI 36 0G0900 1 DECAL UL LIS...

Страница 25: ...23 Parts List on page 25 200A Assembly Drawing No 0H7265 F Exploded Views Parts Lists...

Страница 26: ...24 Parts List on page 25 Exploded Views Parts Lists 200A Assembly Drawing No 0H7265 F...

Страница 27: ...DECAL NEUTRAL CONNECTION 31 0D3587 1 DECAL FUSE REPLACEMENT 32 0H7917 1 DECAL TERMINAL STRIP 33 0H1480 1 DECAL TEST SEQUENCE 34 0G3274 1 DECAL LIVE CIRCUIT ENG FRN SPN ITEM PART NO QTY DESCRIPTION 35...

Страница 28: ...Part No 0J2119 Revision B 01 06 12 Printed in U S A...

Страница 29: ......

Страница 30: ...U T IL IT Y D IS C O N N E C T 2 6 0 G 4 2 2 0 1 D E C A L N E U T R A LC O N N E C T IO N 2 7 0 6 7 2 1 0 A 1 D E C A L G R O U N D IN G L U G 2 8 0 G 0 9 0 0 1 D E C A L U LL IS TH S B 2 9 0 D 3 5...

Страница 31: ......

Страница 32: ...3587 1 DECAL FUSE REPLACEMENT 32 0H7917 1 DECAL TERMINAL STRIP 33 0H1480 1 DECAL TEST SEQUENCE 34 0G3274 1 DECAL LIVE CIRCUIT ENG FRN SPN 35 0G3259 1 DECAL TERMINAL SHOCK HZD BI 36 0G0900 1 DECAL UL L...

Страница 33: ......

Страница 34: ......

Страница 35: ......

Страница 36: ...3587 1 DECAL FUSE REPLACEMENT 32 0H7917 1 DECAL TERMINAL STRIP 33 0H1480 1 DECAL TEST SEQUENCE 34 0G3274 1 DECAL LIVE CIRCUIT ENG FRN SPN 35 0G3259 1 DECAL TERMINAL SHOCK HZD BI 36 0G0900 1 DECAL UL L...

Страница 37: ......

Страница 38: ......

Страница 39: ......

Страница 40: ......

Страница 41: ......

Страница 42: ......

Страница 43: ......

Страница 44: ......

Страница 45: ......

Страница 46: ......

Страница 47: ......

Страница 48: ......

Страница 49: ......

Отзывы: