Generac Power Systems RTS automatic Скачать руководство пользователя страница 6

 4 

Install the transfer switch as close as possible to the electrical 

loads that are to be connected to it. Mount the switch vertically to 

a rigid supporting structure. To prevent switch distortion, level all 

mounting points. If necessary, use washers behind mounting holes 

to level the unit.

2.3    CONNECTING POWER SOURCE 

AND LOAD LINES



Make sure to turn OFF both the UTILITY 

(NORMAL) and GENERATOR (STANDBY) 

power supplies before trying to connect power 

source and load lines to the transfer switch. 

Supply voltages are extremely high and dan-

gerous. Contact with such high voltage power 

supply lines causes extremely hazardous, pos-

sibly lethal, electrical shock.

Wiring diagrams and electrical schematics are provided in this 

manual.

NOTE:

All installations must comply with national, state and local 

codes. It is the responsibility of the installer to perform an 

installation that will pass the final electrical inspection.

The utility supply connection is made at the UTILITY SERVICE DIS-

CONNECT circuit breaker terminals. The generator and customer 

load connections are made at the transfer switch mechanism, 

inside the switch enclosure.
Conductor sizes must be adequate to handle the maximum cur-

rent to which they will be subjected, based on the 75°C column of 

tables, charts, etc. used to size conductors. The installation must 

comply fully with all applicable codes, standards and regulations.
All power cables must enter the enclosure through the knockouts 

provided. If not using the knockouts, conduit entry into the enclo-

sure must be at or below knockouts to maintain the Type 3R rating. 

Conduits should be arranged to provide separation between the 

Utility and Generator supply conductors inside the enclosure.
Before connecting wiring cables to terminals, remove any surface 

oxides from the cable ends with a wire brush. If ALUMINUM con-

ductors are used, apply corrosion inhibitor to conductors. Tighten 

terminal lugs to the torque values on "Utility Service Disconnect 

Circuit Breaker", and on the decal located on the inside of the door. 

After tightening terminal lugs, carefully wipe away any excess cor-

rosion inhibitor.

 

 

Use a torque wrench to tighten the conductors, 

being sure not to overtighten, or damage to 

the switch base could occur. If not tightened 

enough, a loose connection would result, 

causing excess heat which could damage the 

switch base.

Connect power source load conductors to clearly marked transfer 

mechanism terminal lugs as follows
1.  Connect UTILITY (NORMAL) power source cables to UTILITY 

SERVICE DISCONNECT circuit breaker.

2.  Connect the GENERATOR (STANDBY) source power cables to 

switch terminals E1, E2.

3.  Connect customer LOAD leads to switch terminals T1, T2.
Conductors must be properly supported, of approved insulative 

qualities, protected by approved conduit, and of the correct wire 

gauge size in accordance with applicable codes.
Be sure to maintain proper electrical clearance between live metal 

parts and grounded metal. Allow at least 1/2 inch for 100-400 

amp circuits.

2.4  

CONNECTING START CIRCUIT

WIRES

Control system interconnections (Electrical Data section) consist 

of UTILITY 1 (N1), UTILITY 2 (N2) and LOAD (T1), and leads 23, 0 

and 194. Recommended wire gauge sizes for this wiring depends 

on the length of the wire, as recommended in the following chart:

MAXIMUM WIRE LENGTH

RECOMMENDED WIRE

SIZE

460 feet (140m)

No. 18 AWG.

461 to 730 feet (223m)

No. 16 AWG.

731 to 1,160 feet (354m)

No. 14 AWG.

1,161 to 1,850 feet (565m)

No. 12 AWG.

2.5  

CONNECTING LOAD SHED 

MODULE (LSM) CONNECTION

The LSM can control an air conditioner (24 Vac) directly or a sepa-

rate contactor (120 Vac) which can control any load connected to 

it. See Figure 2.1.

2.5.1   SEQUENCE OF OPERATION

The 4 green status LEDs will indicate when a load priority level is 

enabled.
•  All loads are enabled when the transfer signal is off. (ATS in 

Utility position).

•  If the transfer signal is pulled low (Active)

• All loads are enabled until an overload is detected
• When an overload is detected all loads are disabled
• After 5 minutes priority 1 loads are enabled.
• After another 30 seconds priority 2 loads are enabled
• After another 30 seconds priority 3 loads are enabled
• After another 30 seconds priority 4 loads are enabled 

If an overload is detected within 30 seconds of a level being 

enabled, all loads are disabled again and the sequence repeats. 

However, the level that caused the overload and all levels higher 

will not be enabled again for 30 minutes.

Installation

Содержание RTS automatic

Страница 1: ...This manual should remain with the unit Technical Manual RTS Automatic Transfer Switch...

Страница 2: ...ORMAL UTILITY power source by means of an approved transfer switch Failure to properly isolate the NORMAL and STANDBY power sources from each other may result in injury or death to electric utility wo...

Страница 3: ...ove the Negative Neg or battery cable Safety Rules Inside Front Cover General Information 2 1 1 Introduction 2 1 2 Unpacking 2 1 3 Equipment Description 2 1 3 1 Transfer Switch Mechanism 2 1 3 2 Utili...

Страница 4: ...o be switched Solderless screw type terminal lugs are standard Switch Wire Conductor Tightening Rating Range Torque 100A 14 1 0 AWG 50 in lbs 200A 6 250 MCM 275 in lbs This transfer switch is suitable...

Страница 5: ...FER SWITCH ENCLOSURE ThestandardswitchenclosureisaNationalElectricalManufacturer s Association NEMA and UL 3R type UL and NEMA 3R type enclo sures primarily provide a degree of protection against fall...

Страница 6: ...bitor Use a torque wrench to tighten the conductors being sure not to overtighten or damage to the switch base could occur If not tightened enough a loose connection would result causing excess heat w...

Страница 7: ...coil voltage The LSM supplies a fused 5A 120 Vac to energize the coils of the relay contactors L1 L2 L3 and L4 1 Mount the contactor module and connect the load to the main contacts 2 Connect the con...

Страница 8: ...position of the switch by observing the position of manual operation handle in Figure 3 1 If the handle is UP the contacts are closed in the NORMAL UTILITY position no further action is required If t...

Страница 9: ...s main circuit breaker CB1 to its OFF or OPEN position 9 Set the AUTO OFF MANUAL switch to the OFF position to shut down the generator NOTE Do NOT proceed until generator AC output voltage and fre qu...

Страница 10: ...erator run at no load for several minutes Then shut down by setting the AUTO OFF MANUAL switch to its OFF position 8 Move the transfer switch s main contacts back to their UTIL ITY position For exampl...

Страница 11: ...9 9 Notes...

Страница 12: ...10 Notes...

Страница 13: ...11 100A SE non SE 150 200A non SE Installation Drawing No 0G6832 A Installation Diagrams...

Страница 14: ...Installation Diagrams 150 200A SE Installation Drawing No 0H4905 A 12...

Страница 15: ...13 13 Installation Drawing No 0J0814 B Installation Diagrams...

Страница 16: ...14 14 Electrical Data Interconnection Drawing No 0H8676 C...

Страница 17: ...15 15 Interconnection Drawing No 0H7454 C Electrical Data...

Страница 18: ...16 Electrical Data Schematic Drawing No 0H7254 B...

Страница 19: ...17 Schematic Drawing No 0H7254 B Electrical Data...

Страница 20: ...18 Exploded Views Parts Lists 100A Assembly Drawing No 0H7264 H...

Страница 21: ...0E3484 1 DECAL MANUAL OPERATING HANDLE 25 0F9969 1 DECAL UTILITY DISCONNECT 26 0G4220 1 DECAL NEUTRAL CONNECTION 27 067210A 1 DECAL GROUNDING LUG 28 0G0900 1 DECAL UL LIST HSB ITEM PART NO QTY DESCRI...

Страница 22: ...20 Exploded Views Parts Lists 150A Assembly Drawing No 0J2006 D Parts List on page 22...

Страница 23: ...21 150A Assembly Drawing No 0J2006 D Exploded Views Parts Lists Parts List on page 22...

Страница 24: ...2 0H7917 1 DECAL TERMINAL STRIP 33 0H1480 1 DECAL TEST SEQUENCE 34 0G3274 1 DECAL LIVE CIRCUIT ENG FRN SPN ITEM PART NO QTY DESCRIPTION 35 0G3259 1 DECAL TERMINAL SHOCK HZD BI 36 0G0900 1 DECAL UL LIS...

Страница 25: ...23 Parts List on page 25 200A Assembly Drawing No 0H7265 F Exploded Views Parts Lists...

Страница 26: ...24 Parts List on page 25 Exploded Views Parts Lists 200A Assembly Drawing No 0H7265 F...

Страница 27: ...DECAL NEUTRAL CONNECTION 31 0D3587 1 DECAL FUSE REPLACEMENT 32 0H7917 1 DECAL TERMINAL STRIP 33 0H1480 1 DECAL TEST SEQUENCE 34 0G3274 1 DECAL LIVE CIRCUIT ENG FRN SPN ITEM PART NO QTY DESCRIPTION 35...

Страница 28: ...Part No 0J2119 Revision B 01 06 12 Printed in U S A...

Страница 29: ......

Страница 30: ...U T IL IT Y D IS C O N N E C T 2 6 0 G 4 2 2 0 1 D E C A L N E U T R A LC O N N E C T IO N 2 7 0 6 7 2 1 0 A 1 D E C A L G R O U N D IN G L U G 2 8 0 G 0 9 0 0 1 D E C A L U LL IS TH S B 2 9 0 D 3 5...

Страница 31: ......

Страница 32: ...3587 1 DECAL FUSE REPLACEMENT 32 0H7917 1 DECAL TERMINAL STRIP 33 0H1480 1 DECAL TEST SEQUENCE 34 0G3274 1 DECAL LIVE CIRCUIT ENG FRN SPN 35 0G3259 1 DECAL TERMINAL SHOCK HZD BI 36 0G0900 1 DECAL UL L...

Страница 33: ......

Страница 34: ......

Страница 35: ......

Страница 36: ...3587 1 DECAL FUSE REPLACEMENT 32 0H7917 1 DECAL TERMINAL STRIP 33 0H1480 1 DECAL TEST SEQUENCE 34 0G3274 1 DECAL LIVE CIRCUIT ENG FRN SPN 35 0G3259 1 DECAL TERMINAL SHOCK HZD BI 36 0G0900 1 DECAL UL L...

Страница 37: ......

Страница 38: ......

Страница 39: ......

Страница 40: ......

Страница 41: ......

Страница 42: ......

Страница 43: ......

Страница 44: ......

Страница 45: ......

Страница 46: ......

Страница 47: ......

Страница 48: ......

Страница 49: ......

Отзывы: