  2

1.1   INTRODUCTION

This manual has been prepared especially for the purpose of famil-

iarizing personnel with the design, application, installation, opera-

tion and servicing of the applicable equipment. Read the manual 

carefully and comply with all instructions. This will help to prevent 

accidents or damage to equipment that might otherwise be caused 

by carelessness, incorrect application, or improper procedures.
Every effort has been expended to make sure that the contents 

of this manual are both accurate and current. The manufacturer, 

however, reserves the right to change, alter or otherwise improve 

the product at any time without prior notice.

1.2 UNPACKING

Carefully unpack the transfer switch. Inspect closely for any dam-

age that might have occurred during shipment. The purchaser must 

file with the carrier any claims for loss or damage incurred while in 

transit.
Check that all packing material is completely removed from the 

switch prior to installation.

1.3   EQUIPMENT DESCRIPTION

The automatic transfer switch is used for transferring electrical 

load from a UTILITY (NORMAL) power source to an GENERATOR 

(STANDBY) power source. Such a transfer of electrical loads 

occurs automatically when the UTILITY power source has failed or 

is substantially reduced and the GENERATOR source voltage and 

frequency have reached an acceptable level. The transfer switch 

prevents electrical feedback between two different power sources 

(such as the UTILITY and GENERATOR sources) and, for that rea-

son, codes require it in all standby electric system installations.
The transfer switch consists of a transfer mechanism, UTILITY 

SERVICE DISCONNECT circuit breaker, a relay control, fuses, ter-

minal strip, and fuse holder for connection of sensing wires.
This transfer switch is suitable for use as service equipment.

1.3.1   TRANSFER SWITCH MECHANISM

These switches (Figure 1.1) are used with a single-phase system, 

when the single-phase NEUTRAL line is to be connected to a 

Neutral Lug and is not to be switched.
Solderless, screw-type terminal lugs are standard.

Switch

Wire

Conductor Tightening

Rating

Range

Torque

100A

#14-1/0 AWG

50 in-lbs.

200A

#6-250 MCM

275 in-lbs.

This transfer switch is suitable for control of motors, electric dis-

charge lamps, tungsten filament and electric heating equipment 

where the sum of motor full load ampere ratings and the ampere 

ratings of other loads do not exceed the ampere rating of the 

switch and the tungsten load does not exceed 30 percent of the 

switch rating.
This UL listed transfer switch is for use in optional standby sys-

tems only (NEC article 702).

This transfer switch is suitable for use on a circuit capable of 

22,000 rms (200A) and 10,000 (100A) symmetrical amperes, 

240 VAC maximum.

Figure 1.1 — Typical ATS Transfer Mechanism

UTILITY
CLOSING
COIL

GENERATOR
CLOSING
COIL

UTILITY LUGS

GENERATOR
LUGS (E1 & E2)

LOAD LUGS (T1 & T2)

1.3.2   UTILITY SERVICE DISCONNECT CIRCUIT BREAKER

The utility service and generator disconnect circuit breakers for the 

100 amp models are:
•  Type BQ, 2-pole
• 120/240VAC, 100A
• 50/60 Hertz
•  Heating, Air Conditioning and Refrigeration (HACR) rated
•  Wire range:  #1 - #8 AWG.
•  The conductor tightening torque is 50 in-lbs.
The utility service circuit breaker for the 150/200 amp models 

are:
•  Type 225AF, 2-pole
• 120/240VAC, 150A/200A
• 50/60 Hertz
• Wire range:  300 MCM - 6 STR (Line), 250 MCM - 6 STR 

(Load - ATS)

•  The conductor tightening torque is 375 in-lbs. (Line), 275 in-

lbs. (Load - ATS)

1.3.3   LOAD SHED MODULE (LSM)

The Load Shed module is designed to prevent an overload on the 

generator when it is supplying the customer loads (see Figure 

1.2). Up to six loads can be managed by the LSM; 2 air condi-

tioner loads and 4 other loads. The LSM manages the loads by 

“shedding” the connected loads in the event of a drop in generator 

frequency (overload). Loads to be “shed” are grouped in 4 priority 

levels on the LSM.  
•  Priority 1 and 2 has connections for both one air conditioner 

and one contactor.  Both an air conditioner and a contactor 

can be used at the same time if desired. To control an air 

conditioner, no additional equipment is required. Internal relays 

interrupt the thermostat 24VAC control signal to disable the air 

conditioner load.

General Information

Содержание RTS automatic

Страница 1: ...This manual should remain with the unit Technical Manual RTS Automatic Transfer Switch...

Страница 2: ...ORMAL UTILITY power source by means of an approved transfer switch Failure to properly isolate the NORMAL and STANDBY power sources from each other may result in injury or death to electric utility wo...

Страница 3: ...ove the Negative Neg or battery cable Safety Rules Inside Front Cover General Information 2 1 1 Introduction 2 1 2 Unpacking 2 1 3 Equipment Description 2 1 3 1 Transfer Switch Mechanism 2 1 3 2 Utili...

Страница 4: ...o be switched Solderless screw type terminal lugs are standard Switch Wire Conductor Tightening Rating Range Torque 100A 14 1 0 AWG 50 in lbs 200A 6 250 MCM 275 in lbs This transfer switch is suitable...

Страница 5: ...FER SWITCH ENCLOSURE ThestandardswitchenclosureisaNationalElectricalManufacturer s Association NEMA and UL 3R type UL and NEMA 3R type enclo sures primarily provide a degree of protection against fall...

Страница 6: ...bitor Use a torque wrench to tighten the conductors being sure not to overtighten or damage to the switch base could occur If not tightened enough a loose connection would result causing excess heat w...

Страница 7: ...coil voltage The LSM supplies a fused 5A 120 Vac to energize the coils of the relay contactors L1 L2 L3 and L4 1 Mount the contactor module and connect the load to the main contacts 2 Connect the con...

Страница 8: ...position of the switch by observing the position of manual operation handle in Figure 3 1 If the handle is UP the contacts are closed in the NORMAL UTILITY position no further action is required If t...

Страница 9: ...s main circuit breaker CB1 to its OFF or OPEN position 9 Set the AUTO OFF MANUAL switch to the OFF position to shut down the generator NOTE Do NOT proceed until generator AC output voltage and fre qu...

Страница 10: ...erator run at no load for several minutes Then shut down by setting the AUTO OFF MANUAL switch to its OFF position 8 Move the transfer switch s main contacts back to their UTIL ITY position For exampl...

Страница 11: ...9 9 Notes...

Страница 12: ...10 Notes...

Страница 13: ...11 100A SE non SE 150 200A non SE Installation Drawing No 0G6832 A Installation Diagrams...

Страница 14: ...Installation Diagrams 150 200A SE Installation Drawing No 0H4905 A 12...

Страница 15: ...13 13 Installation Drawing No 0J0814 B Installation Diagrams...

Страница 16: ...14 14 Electrical Data Interconnection Drawing No 0H8676 C...

Страница 17: ...15 15 Interconnection Drawing No 0H7454 C Electrical Data...

Страница 18: ...16 Electrical Data Schematic Drawing No 0H7254 B...

Страница 19: ...17 Schematic Drawing No 0H7254 B Electrical Data...

Страница 20: ...18 Exploded Views Parts Lists 100A Assembly Drawing No 0H7264 H...

Страница 21: ...0E3484 1 DECAL MANUAL OPERATING HANDLE 25 0F9969 1 DECAL UTILITY DISCONNECT 26 0G4220 1 DECAL NEUTRAL CONNECTION 27 067210A 1 DECAL GROUNDING LUG 28 0G0900 1 DECAL UL LIST HSB ITEM PART NO QTY DESCRI...

Страница 22: ...20 Exploded Views Parts Lists 150A Assembly Drawing No 0J2006 D Parts List on page 22...

Страница 23: ...21 150A Assembly Drawing No 0J2006 D Exploded Views Parts Lists Parts List on page 22...

Страница 24: ...2 0H7917 1 DECAL TERMINAL STRIP 33 0H1480 1 DECAL TEST SEQUENCE 34 0G3274 1 DECAL LIVE CIRCUIT ENG FRN SPN ITEM PART NO QTY DESCRIPTION 35 0G3259 1 DECAL TERMINAL SHOCK HZD BI 36 0G0900 1 DECAL UL LIS...

Страница 25: ...23 Parts List on page 25 200A Assembly Drawing No 0H7265 F Exploded Views Parts Lists...

Страница 26: ...24 Parts List on page 25 Exploded Views Parts Lists 200A Assembly Drawing No 0H7265 F...

Страница 27: ...DECAL NEUTRAL CONNECTION 31 0D3587 1 DECAL FUSE REPLACEMENT 32 0H7917 1 DECAL TERMINAL STRIP 33 0H1480 1 DECAL TEST SEQUENCE 34 0G3274 1 DECAL LIVE CIRCUIT ENG FRN SPN ITEM PART NO QTY DESCRIPTION 35...

Страница 28: ...Part No 0J2119 Revision B 01 06 12 Printed in U S A...

Страница 29: ......

Страница 30: ...U T IL IT Y D IS C O N N E C T 2 6 0 G 4 2 2 0 1 D E C A L N E U T R A LC O N N E C T IO N 2 7 0 6 7 2 1 0 A 1 D E C A L G R O U N D IN G L U G 2 8 0 G 0 9 0 0 1 D E C A L U LL IS TH S B 2 9 0 D 3 5...

Страница 31: ......

Страница 32: ...3587 1 DECAL FUSE REPLACEMENT 32 0H7917 1 DECAL TERMINAL STRIP 33 0H1480 1 DECAL TEST SEQUENCE 34 0G3274 1 DECAL LIVE CIRCUIT ENG FRN SPN 35 0G3259 1 DECAL TERMINAL SHOCK HZD BI 36 0G0900 1 DECAL UL L...

Страница 33: ......

Страница 34: ......

Страница 35: ......

Страница 36: ...3587 1 DECAL FUSE REPLACEMENT 32 0H7917 1 DECAL TERMINAL STRIP 33 0H1480 1 DECAL TEST SEQUENCE 34 0G3274 1 DECAL LIVE CIRCUIT ENG FRN SPN 35 0G3259 1 DECAL TERMINAL SHOCK HZD BI 36 0G0900 1 DECAL UL L...

Страница 37: ......

Страница 38: ......

Страница 39: ......

Страница 40: ......

Страница 41: ......

Страница 42: ......

Страница 43: ......

Страница 44: ......

Страница 45: ......

Страница 46: ......

Страница 47: ......

Страница 48: ......

Страница 49: ......

Отзывы: