 8 

3.4  

GENERATOR TESTS UNDER 

LOAD

1.  Set the generator's main circuit breaker to its OFF or OPEN 

position.

2.  Set the UTILITY SERVICE DISCONNECT circuit breaker to the 

OFF position.

3.  Manually actuate the transfer switch main contacts to 

their GENERATOR (STANDBY) position. Refer to "Manual 

Operation".

4.  To start the generator, set the AUTO/OFF/ MANUAL switch to 

MANUAL. When engine starts, let it stabilize for a few min-

utes.

5.  Turn the generator's main circuit breaker to its ON or CLOSED 

position. The generator now powers all LOAD circuits. Check 

generator operation under load as follows:

• Turn ON electrical loads to the full rated wattage/amperage 

capacity of the generator. DO NOT OVERLOAD.

• With maximum rated load applied, check voltage and fre-

quency across transfer switch terminals E1 and E2. Voltage 

should be greater than 230VAC and frequency should be 

greater than 59 Hertz.

•  Let the generator run under rated load for at least 30 minutes. 

With unit running, listen for unusual noises, vibration, over-

heating, etc., that might indicate a problem.

6.  When checkout under load is complete, turn the generator's 

main circuit breaker to its OFF or OPEN position.

7.  Let the generator run at no-load for several minutes. Then, 

shut down by setting the AUTO/OFF/MANUAL switch to its 

OFF position.

8.  Move the transfer switch's main contacts back to their UTIL-

ITY position. For example, LOAD connected to UTILITY power 

supply. Refer to "Manual Operation". Handle and operating 

lever of transfer switch should be in the UP position.

9.  Turn on the utility power supply to transfer switch, using the 

UTILITY SERVICE DISCONNECT circuit breaker. The utility 

power source now powers the loads.

10.  Set the generator's AUTO/OFF/MANUAL switch to its AUTO 

position.

3.5  

TESTING LOAD SHED MODULE 

(LSM)

A Test pushbutton is provided on the bottom of the LSM to test the 

operation of the tested functions. The Test button will work when 

the ATS is in the Utility or the Generator position. 
1.  Turn the Utility supply on to the ATS.
2.  Press the TEST pushbutton on the LSM.
3.  Verify that all of the connected loads to be “shed” become 

disabled. The method of verification will depend on the type 

of load.

4.  After 5 minutes verify the priority 1 loads are enabled. Status 

LED L1 and Air 1 is ON.

5.  After another 30 seconds, verify the priority 2 loads are 

enabled. Status LED L2 and Air 2 is ON.

6.  After another 30 seconds, verify the priority 3 loads are 

enabled. Status LED L3 is ON.

7.  After another 30 seconds, verify the priority 4 loads are 

enabled. Status LED L4 is ON.

Operation

Содержание RTS automatic

Страница 1: ...This manual should remain with the unit Technical Manual RTS Automatic Transfer Switch...

Страница 2: ...ORMAL UTILITY power source by means of an approved transfer switch Failure to properly isolate the NORMAL and STANDBY power sources from each other may result in injury or death to electric utility wo...

Страница 3: ...ove the Negative Neg or battery cable Safety Rules Inside Front Cover General Information 2 1 1 Introduction 2 1 2 Unpacking 2 1 3 Equipment Description 2 1 3 1 Transfer Switch Mechanism 2 1 3 2 Utili...

Страница 4: ...o be switched Solderless screw type terminal lugs are standard Switch Wire Conductor Tightening Rating Range Torque 100A 14 1 0 AWG 50 in lbs 200A 6 250 MCM 275 in lbs This transfer switch is suitable...

Страница 5: ...FER SWITCH ENCLOSURE ThestandardswitchenclosureisaNationalElectricalManufacturer s Association NEMA and UL 3R type UL and NEMA 3R type enclo sures primarily provide a degree of protection against fall...

Страница 6: ...bitor Use a torque wrench to tighten the conductors being sure not to overtighten or damage to the switch base could occur If not tightened enough a loose connection would result causing excess heat w...

Страница 7: ...coil voltage The LSM supplies a fused 5A 120 Vac to energize the coils of the relay contactors L1 L2 L3 and L4 1 Mount the contactor module and connect the load to the main contacts 2 Connect the con...

Страница 8: ...position of the switch by observing the position of manual operation handle in Figure 3 1 If the handle is UP the contacts are closed in the NORMAL UTILITY position no further action is required If t...

Страница 9: ...s main circuit breaker CB1 to its OFF or OPEN position 9 Set the AUTO OFF MANUAL switch to the OFF position to shut down the generator NOTE Do NOT proceed until generator AC output voltage and fre qu...

Страница 10: ...erator run at no load for several minutes Then shut down by setting the AUTO OFF MANUAL switch to its OFF position 8 Move the transfer switch s main contacts back to their UTIL ITY position For exampl...

Страница 11: ...9 9 Notes...

Страница 12: ...10 Notes...

Страница 13: ...11 100A SE non SE 150 200A non SE Installation Drawing No 0G6832 A Installation Diagrams...

Страница 14: ...Installation Diagrams 150 200A SE Installation Drawing No 0H4905 A 12...

Страница 15: ...13 13 Installation Drawing No 0J0814 B Installation Diagrams...

Страница 16: ...14 14 Electrical Data Interconnection Drawing No 0H8676 C...

Страница 17: ...15 15 Interconnection Drawing No 0H7454 C Electrical Data...

Страница 18: ...16 Electrical Data Schematic Drawing No 0H7254 B...

Страница 19: ...17 Schematic Drawing No 0H7254 B Electrical Data...

Страница 20: ...18 Exploded Views Parts Lists 100A Assembly Drawing No 0H7264 H...

Страница 21: ...0E3484 1 DECAL MANUAL OPERATING HANDLE 25 0F9969 1 DECAL UTILITY DISCONNECT 26 0G4220 1 DECAL NEUTRAL CONNECTION 27 067210A 1 DECAL GROUNDING LUG 28 0G0900 1 DECAL UL LIST HSB ITEM PART NO QTY DESCRI...

Страница 22: ...20 Exploded Views Parts Lists 150A Assembly Drawing No 0J2006 D Parts List on page 22...

Страница 23: ...21 150A Assembly Drawing No 0J2006 D Exploded Views Parts Lists Parts List on page 22...

Страница 24: ...2 0H7917 1 DECAL TERMINAL STRIP 33 0H1480 1 DECAL TEST SEQUENCE 34 0G3274 1 DECAL LIVE CIRCUIT ENG FRN SPN ITEM PART NO QTY DESCRIPTION 35 0G3259 1 DECAL TERMINAL SHOCK HZD BI 36 0G0900 1 DECAL UL LIS...

Страница 25: ...23 Parts List on page 25 200A Assembly Drawing No 0H7265 F Exploded Views Parts Lists...

Страница 26: ...24 Parts List on page 25 Exploded Views Parts Lists 200A Assembly Drawing No 0H7265 F...

Страница 27: ...DECAL NEUTRAL CONNECTION 31 0D3587 1 DECAL FUSE REPLACEMENT 32 0H7917 1 DECAL TERMINAL STRIP 33 0H1480 1 DECAL TEST SEQUENCE 34 0G3274 1 DECAL LIVE CIRCUIT ENG FRN SPN ITEM PART NO QTY DESCRIPTION 35...

Страница 28: ...Part No 0J2119 Revision B 01 06 12 Printed in U S A...

Страница 29: ......

Страница 30: ...U T IL IT Y D IS C O N N E C T 2 6 0 G 4 2 2 0 1 D E C A L N E U T R A LC O N N E C T IO N 2 7 0 6 7 2 1 0 A 1 D E C A L G R O U N D IN G L U G 2 8 0 G 0 9 0 0 1 D E C A L U LL IS TH S B 2 9 0 D 3 5...

Страница 31: ......

Страница 32: ...3587 1 DECAL FUSE REPLACEMENT 32 0H7917 1 DECAL TERMINAL STRIP 33 0H1480 1 DECAL TEST SEQUENCE 34 0G3274 1 DECAL LIVE CIRCUIT ENG FRN SPN 35 0G3259 1 DECAL TERMINAL SHOCK HZD BI 36 0G0900 1 DECAL UL L...

Страница 33: ......

Страница 34: ......

Страница 35: ......

Страница 36: ...3587 1 DECAL FUSE REPLACEMENT 32 0H7917 1 DECAL TERMINAL STRIP 33 0H1480 1 DECAL TEST SEQUENCE 34 0G3274 1 DECAL LIVE CIRCUIT ENG FRN SPN 35 0G3259 1 DECAL TERMINAL SHOCK HZD BI 36 0G0900 1 DECAL UL L...

Страница 37: ......

Страница 38: ......

Страница 39: ......

Страница 40: ......

Страница 41: ......

Страница 42: ......

Страница 43: ......

Страница 44: ......

Страница 45: ......

Страница 46: ......

Страница 47: ......

Страница 48: ......

Страница 49: ......

Отзывы: