Generac Power Systems RTS automatic Скачать руководство пользователя страница 5

 

 

3

•  Priority 3 and 4 have connections for one contactor only.
•  Four LEDs, located on the load shed module, will indicate when 

a load priority level is enabled.

•  Any loads, including central air conditioners, can be controlled 

via a contactor that must be purchased separately. Up to four 

contactors can be controlled by the load shed module. The LSM 

supplies the 120 Vac to energize each contactor coil.  

• Generator overload condition is determined by generator fre-

quency. Loads are shed when the frequency is <58Hz for 3 

seconds or <50Hz for ½ Second  (For 60Hz).

The LSM has a Test button which forces the unit to act as if an 

overload has occurred. This button operates even when the trans-

fer signal is inactive.

Figure 1.2 — Load Shed Module

0 Ground

194 +12V

23 Transfer

T1

NEUTRAL

AIR 1

AIR 2

CONTACTOR

1

CONTACTOR

2

CONTACTOR

3

CONTACTOR

4

Priority 1

Priority 2

Priority 3

Priority 4

0 Ground

194 +12V

23 Transfer

T1

NEUTRAL

AIR 1

AIR 2

CONTACTOR

1

CONTACTOR

2

CONTACTOR

3

CONTACTOR

4

Priority 1

Priority 2

Priority 3

Priority 4

Air Conditioner Connections:
Up to two A/Cs can be
controlled via low voltage
thermostat wires

Status LEDs: Shows
which loads are
currently allowed
to run.

Load Connections: Up to four loads of any type can
be controlled via these connections. (A separate
contactor module is required.)

1.4  

TRANSFER SWITCH DATA 

DECAL

A DATA DECAL is permanently affixed to the transfer switch enclo-

sure. Use this transfer switch only with the specific limits shown 

on the DATA DECAL and on other decals and labels that may be 

affixed to the switch. This will prevent damage to equipment and 

property.
When requesting information or ordering parts for this equipment, 

make sure to include all information from the DATA DECAL.
Record the Model and Serial numbers in the space provided below 

for future reference.

MODEL #
SERIAL #

1.5  

TRANSFER SWITCH 

ENCLOSURE

The standard switch enclosure is a National Electrical Manufacturer’s 

Association (NEMA) and UL 3R type. UL and NEMA 3R type enclo-

sures primarily provide a degree of protection against falling rain 

and sleet; undamaged by the formation of ice on the enclosure.

1.6  

SAFE USE OF TRANSFER 

SWITCH

Before installing, operating or servicing this equipment, read the 

SAFETY RULES (inside front cover) carefully. Comply strictly 

with all SAFETY RULES to prevent accidents and/or damage to 

the equipment. The manufacturer recommends that a copy of the 

SAFETY RULES are posted near the transfer switch. Also, be sure 

to read all instructions and information found on tags, labels and 

decals affixed to the equipment.
Three publications that outline the safe use of transfer switches 

are the following:
•  NFPA 70; National Electrical Code
•  NFPA 70E; Standard for Electrical Safety in the Workplace
• UL 1008, STANDARD FOR SAFETY-AUTOMATIC TRANSFER 

SWITCHES

NOTE:

It is essential to use the latest version of any standard to ensure 

correct and current information.

2.1  

INTRODUCTION TO 

INSTALLATION

This equipment has been wired and tested at the factory. Installing 

the switch includes the following procedures:
•  Mounting the enclosure.
•  Connecting power source leads and load leads.
•  Connecting the generator sensing and transfer relay circuits.
•  Connecting any auxiliary contact (if needed)
•  Connect load shed module loads (as required)
• Testing functions.

2.2 MOUNTING

Mounting dimensions for the transfer switch enclosure are in this 

manual. Enclosures are typically wall-mounted. See “Installation 

Diagram”.

 

 

Handle transfer switches carefully when install-

ing. Do not drop the switch. Protect the switch 

against impact at all times, and against con-

struction grit and metal chips. Never install a 

transfer switch that has been damaged.

This transfer switch is mounted in a UL type 3R enclosure. It can 

be mounted outside or inside and should be based on the layout 

of installation, convenience and proximity to the utility supply and 

load center.

Installation

Содержание RTS automatic

Страница 1: ...This manual should remain with the unit Technical Manual RTS Automatic Transfer Switch...

Страница 2: ...ORMAL UTILITY power source by means of an approved transfer switch Failure to properly isolate the NORMAL and STANDBY power sources from each other may result in injury or death to electric utility wo...

Страница 3: ...ove the Negative Neg or battery cable Safety Rules Inside Front Cover General Information 2 1 1 Introduction 2 1 2 Unpacking 2 1 3 Equipment Description 2 1 3 1 Transfer Switch Mechanism 2 1 3 2 Utili...

Страница 4: ...o be switched Solderless screw type terminal lugs are standard Switch Wire Conductor Tightening Rating Range Torque 100A 14 1 0 AWG 50 in lbs 200A 6 250 MCM 275 in lbs This transfer switch is suitable...

Страница 5: ...FER SWITCH ENCLOSURE ThestandardswitchenclosureisaNationalElectricalManufacturer s Association NEMA and UL 3R type UL and NEMA 3R type enclo sures primarily provide a degree of protection against fall...

Страница 6: ...bitor Use a torque wrench to tighten the conductors being sure not to overtighten or damage to the switch base could occur If not tightened enough a loose connection would result causing excess heat w...

Страница 7: ...coil voltage The LSM supplies a fused 5A 120 Vac to energize the coils of the relay contactors L1 L2 L3 and L4 1 Mount the contactor module and connect the load to the main contacts 2 Connect the con...

Страница 8: ...position of the switch by observing the position of manual operation handle in Figure 3 1 If the handle is UP the contacts are closed in the NORMAL UTILITY position no further action is required If t...

Страница 9: ...s main circuit breaker CB1 to its OFF or OPEN position 9 Set the AUTO OFF MANUAL switch to the OFF position to shut down the generator NOTE Do NOT proceed until generator AC output voltage and fre qu...

Страница 10: ...erator run at no load for several minutes Then shut down by setting the AUTO OFF MANUAL switch to its OFF position 8 Move the transfer switch s main contacts back to their UTIL ITY position For exampl...

Страница 11: ...9 9 Notes...

Страница 12: ...10 Notes...

Страница 13: ...11 100A SE non SE 150 200A non SE Installation Drawing No 0G6832 A Installation Diagrams...

Страница 14: ...Installation Diagrams 150 200A SE Installation Drawing No 0H4905 A 12...

Страница 15: ...13 13 Installation Drawing No 0J0814 B Installation Diagrams...

Страница 16: ...14 14 Electrical Data Interconnection Drawing No 0H8676 C...

Страница 17: ...15 15 Interconnection Drawing No 0H7454 C Electrical Data...

Страница 18: ...16 Electrical Data Schematic Drawing No 0H7254 B...

Страница 19: ...17 Schematic Drawing No 0H7254 B Electrical Data...

Страница 20: ...18 Exploded Views Parts Lists 100A Assembly Drawing No 0H7264 H...

Страница 21: ...0E3484 1 DECAL MANUAL OPERATING HANDLE 25 0F9969 1 DECAL UTILITY DISCONNECT 26 0G4220 1 DECAL NEUTRAL CONNECTION 27 067210A 1 DECAL GROUNDING LUG 28 0G0900 1 DECAL UL LIST HSB ITEM PART NO QTY DESCRI...

Страница 22: ...20 Exploded Views Parts Lists 150A Assembly Drawing No 0J2006 D Parts List on page 22...

Страница 23: ...21 150A Assembly Drawing No 0J2006 D Exploded Views Parts Lists Parts List on page 22...

Страница 24: ...2 0H7917 1 DECAL TERMINAL STRIP 33 0H1480 1 DECAL TEST SEQUENCE 34 0G3274 1 DECAL LIVE CIRCUIT ENG FRN SPN ITEM PART NO QTY DESCRIPTION 35 0G3259 1 DECAL TERMINAL SHOCK HZD BI 36 0G0900 1 DECAL UL LIS...

Страница 25: ...23 Parts List on page 25 200A Assembly Drawing No 0H7265 F Exploded Views Parts Lists...

Страница 26: ...24 Parts List on page 25 Exploded Views Parts Lists 200A Assembly Drawing No 0H7265 F...

Страница 27: ...DECAL NEUTRAL CONNECTION 31 0D3587 1 DECAL FUSE REPLACEMENT 32 0H7917 1 DECAL TERMINAL STRIP 33 0H1480 1 DECAL TEST SEQUENCE 34 0G3274 1 DECAL LIVE CIRCUIT ENG FRN SPN ITEM PART NO QTY DESCRIPTION 35...

Страница 28: ...Part No 0J2119 Revision B 01 06 12 Printed in U S A...

Страница 29: ......

Страница 30: ...U T IL IT Y D IS C O N N E C T 2 6 0 G 4 2 2 0 1 D E C A L N E U T R A LC O N N E C T IO N 2 7 0 6 7 2 1 0 A 1 D E C A L G R O U N D IN G L U G 2 8 0 G 0 9 0 0 1 D E C A L U LL IS TH S B 2 9 0 D 3 5...

Страница 31: ......

Страница 32: ...3587 1 DECAL FUSE REPLACEMENT 32 0H7917 1 DECAL TERMINAL STRIP 33 0H1480 1 DECAL TEST SEQUENCE 34 0G3274 1 DECAL LIVE CIRCUIT ENG FRN SPN 35 0G3259 1 DECAL TERMINAL SHOCK HZD BI 36 0G0900 1 DECAL UL L...

Страница 33: ......

Страница 34: ......

Страница 35: ......

Страница 36: ...3587 1 DECAL FUSE REPLACEMENT 32 0H7917 1 DECAL TERMINAL STRIP 33 0H1480 1 DECAL TEST SEQUENCE 34 0G3274 1 DECAL LIVE CIRCUIT ENG FRN SPN 35 0G3259 1 DECAL TERMINAL SHOCK HZD BI 36 0G0900 1 DECAL UL L...

Страница 37: ......

Страница 38: ......

Страница 39: ......

Страница 40: ......

Страница 41: ......

Страница 42: ......

Страница 43: ......

Страница 44: ......

Страница 45: ......

Страница 46: ......

Страница 47: ......

Страница 48: ......

Страница 49: ......

Отзывы: