NOTE:

12.   Pre-alarm conditions MUST be reset at the generator set 

control panel.

SPARE KEYPAD SWITCH

 

‹

When DIP Switch S3, Position 4, is in the ON position, it allows the 
SPARE Keypad Switch to control Relay 8. When this DIP switch is 
in the ON position, pushing the SPARE keypad Switch will energize 
Relay 8 and turn on the spare light/LED on the keypad. Pushing 
the SPARE keypad Switch again will de-energize Relay 8 and turn 
off the spare light/LED.

NOTE:

13.   The Remote Start capability using the Spare Keypad Switch 

and Relay 8 is only available when Remote Annunciator 
version P/N 0G5719 is used.

OTHER FUNCTIONS

 GRAPHICAL USER INTERFACE (GUI) OR DIP 

 

‹

SWITCHES ENABLED - DIP SWITCH S3-1

When Position 1 is in the ON position the Graphical User Interface 
(GUI) must be used to set the relay fault conditions. When Position 
1 is in the OFF position the DIP switches on the Annunciator con-
trol board must be used to set the relay fault conditions.

MASTER/SLAVE MODE - DIP SWITCH S3-3

 

‹

Position 3 is used to configure the Annunciator as either a Slave 
(OFF position) or as a Master (ON position). In Slave mode, it is 
a Modbus slave and must be connected to a master port on the 
PM-GC or PM-SC. This method allows for the connection of more 
than one Annunciator. In Master mode, the Annunciator is the 
Modbus master and will request data from the PM-GC or PM-SC. 
The PM-GC or PM-SC must be set as a slave port when the 
Annunciator is configured as the Master (Figures 10 and 11).

Figure 10 —  Annunciator’s connected to an

H-panel or G-panel Engine Controller

PM-GC

(Master)

Annunciator

(Slave)

Annunciator

(Slave)

Figure 11 —  Annunciator’s connected to a System 

Controller (SC) and Multiple G-panels

PM-SC

(Master)

Annunciator

(Slave)

Annunciator

(Slave)

G-panel

(Slave)

G-panel

(Slave)

SPARE KEYPAD SWITCH - DIP SWITCH S3-4

 

‹

Position 4, when it is in the ON position, it allows the SPARE 
Keypad Switch to control Relay 8. When this DIP switch is in 
the ON position, pushing the SPARE keypad Switch will energize 
Relay 8 and turn on the spare LED on the keypad. Pushing the 
SPARE keypad Switch again will de-energize Relay 8 and turn off 
the SPARE LED. This feature can be used to implement a Remote 
Start function. This Remote Start feature is only available with the 
Remote Annunciator version (0G5719) that has both the Relays 
and the Keypad.

BAUD RATE SELECTION (DIP SWITCH S4)

 

‹

DIP Switch S4 can be used to set the Communications Baud Rate 
to a pre-determined value (see table).

S4-1

S4-2

Baud Rate

OFF

OFF

Auto-Baud Rate detect (max rate is 57600)

OFF

ON

38400

ON

OFF

9600

ON

ON

4800

 6 

Remote Annunciator

Содержание 0G5719

Страница 1: ...21 light Remote Annunciator Owner s M anual...

Страница 2: ...Interface GUI available using a computer via the RS232 connector on the annunciator printed circuit board see Figure 2 Relays J1 J8 provides a set of normally open contacts All relays are energized c...

Страница 3: ...he same wire grouping as any high voltage or high current conductors 2 The generator control panel Baud Rate should be selected to be compatible with other components that are connected to the RS485 c...

Страница 4: ...ciator to provide strain relief for the connecting cables and wires Figure 3 RELAY ANNUNCIATION J1 J8 The user can select up to eight of the following 18 generator parameters to annunciate via the rel...

Страница 5: ...Figures 6 and 7 DIP Parameter Relay 1 1 RPM Sensor Loss 1 1 3 Overspeed 2 1 5 High Water Temp Low Water Level 3 1 10 Pre Low Fuel 4 Figure 6 S1 Figure 7 S2 Example 2 If subsequently DIP1 3 is removed...

Страница 6: ...ht to turn ON This shows whether the load is power by the utility For an engine controller that is part of an MPS system line power is not used PARAMETER BATTERY CHARGER AC FAILURE This light LED annu...

Страница 7: ...nication between the Remote Annunciator Panel and the Generator control system It typically requires less than a minute for the Annunciator to determine the correct baud rate and connect to the RS485...

Страница 8: ...his method allows for the connection of more than one Annunciator In Master mode the Annunciator is the Modbus master and will request data from the PM GC or PM SC The PM GC or PM SC must be set as a...

Страница 9: ...setting the Annunciator functions A GenLink serial cable P N 0F7707 should be used to connect a laptop computer s RS232 serial port to the Annunciator DB9 connector The GenLink cable is a Null Modem...

Страница 10: ...he following communication restrictions apply for multiple units on a common RS485 line A maximum of 15 1000 ohm RS485 Loads i e 57 6K Annunciator G panel H panels etc can be connected to the RS485 bu...

Страница 11: ...to normally port 0 and look to see if the check boxes change state If not data is not being transmitted received check the cabling If data is being received check the baud rate settings of all connec...

Страница 12: ...Part No 0G6960 Revision C 09 14 09 Printed in U S A...

Отзывы: