Remote Annunciator

Figure 4 —  DIP Switch S1 Settings

Figure 5 —  DIP Switch S2 Settings

NOTE:

6.   If a unit is wired up and then subsequently an additional 

DIP switch position is selected or deselected, all the relay 
outputs are re-assigned sequentially and therefore the 
annunciator terminals may require re-wiring.

PARAMETER SELECTION EXAMPLES

 

‹

Example 1

DIP S1-1, 3, 5, 10 are initially selected, these are assigned to 
relays 1, 2, 3, 4 (Figures 6 and 7).

DIP

Parameter

Relay

1, 1

RPM Sensor Loss

1

1, 3

Overspeed

2

1, 5

High Water Temp/Low Water Level

3

1, 10

Pre-Low Fuel

4

Figure 6 —  S1

Figure 7 —  S2

Example 2

If subsequently DIP1-3 is removed, and DIP2-5 is added, then 
relays will be re-assigned (Figures 8 and 9).

DIP

Parameter

Relay

1, 1

RPM Sensor Loss

1

1, 5

High Water Temp/Low Water Level

2

1, 10

Pre-Low Fuel

3

2, 5

Generator Power

4

Figure 8 —  S1

Figure 9 —  S2

PARAMETERS S1.1 - S1.10 & S2.1 - S2.3

 

‹

When a remote annunciator (0G5719) or Remote Relay Panel 
(0G5720) is used in a Modular Power System (MPS), an alarm on 
any one of the generators causes the associated relay to activate.

Содержание 0G5719

Страница 1: ...21 light Remote Annunciator Owner s M anual...

Страница 2: ...Interface GUI available using a computer via the RS232 connector on the annunciator printed circuit board see Figure 2 Relays J1 J8 provides a set of normally open contacts All relays are energized c...

Страница 3: ...he same wire grouping as any high voltage or high current conductors 2 The generator control panel Baud Rate should be selected to be compatible with other components that are connected to the RS485 c...

Страница 4: ...ciator to provide strain relief for the connecting cables and wires Figure 3 RELAY ANNUNCIATION J1 J8 The user can select up to eight of the following 18 generator parameters to annunciate via the rel...

Страница 5: ...Figures 6 and 7 DIP Parameter Relay 1 1 RPM Sensor Loss 1 1 3 Overspeed 2 1 5 High Water Temp Low Water Level 3 1 10 Pre Low Fuel 4 Figure 6 S1 Figure 7 S2 Example 2 If subsequently DIP1 3 is removed...

Страница 6: ...ht to turn ON This shows whether the load is power by the utility For an engine controller that is part of an MPS system line power is not used PARAMETER BATTERY CHARGER AC FAILURE This light LED annu...

Страница 7: ...nication between the Remote Annunciator Panel and the Generator control system It typically requires less than a minute for the Annunciator to determine the correct baud rate and connect to the RS485...

Страница 8: ...his method allows for the connection of more than one Annunciator In Master mode the Annunciator is the Modbus master and will request data from the PM GC or PM SC The PM GC or PM SC must be set as a...

Страница 9: ...setting the Annunciator functions A GenLink serial cable P N 0F7707 should be used to connect a laptop computer s RS232 serial port to the Annunciator DB9 connector The GenLink cable is a Null Modem...

Страница 10: ...he following communication restrictions apply for multiple units on a common RS485 line A maximum of 15 1000 ohm RS485 Loads i e 57 6K Annunciator G panel H panels etc can be connected to the RS485 bu...

Страница 11: ...to normally port 0 and look to see if the check boxes change state If not data is not being transmitted received check the cabling If data is being received check the baud rate settings of all connec...

Страница 12: ...Part No 0G6960 Revision C 09 14 09 Printed in U S A...

Отзывы: