Generac Power Systems 0G5719 Скачать руководство пользователя страница 3

 

 

1

Remote Annunciator

DETAILED SPECIFICATIONS

ENVIRONMENTAL SPECIFICATIONS

 

‹

Operating Temperature 

-25°C (-13°F) to + 60°C (140°F)

Humidity 0 to 95% Non Condensing

POWER SUPPLY REQUIREMENTS

 

‹

Power Supply Source 

 Generator Battery to comply with 
NFPA

Power Supply Voltage 

 + 12 or + 24VDC (Annunciator 
operating range is 6V to 30VDC

Power Usage 

 6 Watts (typical when all the relays 
and keypad are energized)

Power Supply Cable 

 2 wire - Voltage drop across each 
conductor must be less that 1V.

 COMMUNICATION WITH GENERATOR 

 

‹

CONTROL SYSTEM

Communication Link 

2 wire RS485 fully isolated.

Communication Cable 

 2 wire RS485 —  twisted pair with 
overall shield/screen (i.e. Belden 
3105A).

Maximum Cable Length 

4,000 feet

Baud rate  Auto-detect at 57.6K, 38.4K, 9600 or 4800 (no parity, 

2 stop bits).

NOTE:

1.   The RS485 cable should not be run in the same conduit, or in 

the same wire grouping as any high voltage or high current 
conductors.

2.   The generator control panel Baud Rate should be selected to 

be compatible with other components that are connected to 
the RS485 communication line.

 RELAY OUTPUTS (J1-J8) - 0G5719 & 0G5720 ONLY

 

‹

Contact per Channel 

 One Normally Open contact. 
Energized when annunciator is 
powered and no faults are present.

Maximum contact rating 

30VDC/1A

ALARM RELAY OUTPUT (J9)

 

‹

Contact Type 

 SPDT (N.O. & N.C. contacts) 
Energized when annunciator is 
powered and no faults are present.

Maximum contact rating 

30VDC/1A

TRANSPORTATION AND STORAGE

 

‹

Temperature 

-30°C (-22°F) to + 80°C (176°F)

Humidity 0 to 95% Non Condensing

1

3

JMP1

J10

JUMPER BETWEEN 1 & 2 = RS485 TERMINATING RESISTOR IN CIRCUIT
JUMPER BETWEEN 2 & 3 = TERMINATING RESISTOR OUT OF CIRCUIT
JUMPER MISSING = TERMINATING RESISTOR OUT OF CIRCUIT

S1

1

RS232 DB9 CONNECTOR
USED WITH THE 
GRAPHICAL USERINTERFACE (GUI)

1

S2

FACTORY USE ONLY

1

1

S3

S4

J1

J8

J9

J2

J3

J4

J5

J6

J7

GREEN STATUS LED

Figure 2 —  Location of DIP Switches, RS232 Connector & JMP1

Содержание 0G5719

Страница 1: ...21 light Remote Annunciator Owner s M anual...

Страница 2: ...Interface GUI available using a computer via the RS232 connector on the annunciator printed circuit board see Figure 2 Relays J1 J8 provides a set of normally open contacts All relays are energized c...

Страница 3: ...he same wire grouping as any high voltage or high current conductors 2 The generator control panel Baud Rate should be selected to be compatible with other components that are connected to the RS485 c...

Страница 4: ...ciator to provide strain relief for the connecting cables and wires Figure 3 RELAY ANNUNCIATION J1 J8 The user can select up to eight of the following 18 generator parameters to annunciate via the rel...

Страница 5: ...Figures 6 and 7 DIP Parameter Relay 1 1 RPM Sensor Loss 1 1 3 Overspeed 2 1 5 High Water Temp Low Water Level 3 1 10 Pre Low Fuel 4 Figure 6 S1 Figure 7 S2 Example 2 If subsequently DIP1 3 is removed...

Страница 6: ...ht to turn ON This shows whether the load is power by the utility For an engine controller that is part of an MPS system line power is not used PARAMETER BATTERY CHARGER AC FAILURE This light LED annu...

Страница 7: ...nication between the Remote Annunciator Panel and the Generator control system It typically requires less than a minute for the Annunciator to determine the correct baud rate and connect to the RS485...

Страница 8: ...his method allows for the connection of more than one Annunciator In Master mode the Annunciator is the Modbus master and will request data from the PM GC or PM SC The PM GC or PM SC must be set as a...

Страница 9: ...setting the Annunciator functions A GenLink serial cable P N 0F7707 should be used to connect a laptop computer s RS232 serial port to the Annunciator DB9 connector The GenLink cable is a Null Modem...

Страница 10: ...he following communication restrictions apply for multiple units on a common RS485 line A maximum of 15 1000 ohm RS485 Loads i e 57 6K Annunciator G panel H panels etc can be connected to the RS485 bu...

Страница 11: ...to normally port 0 and look to see if the check boxes change state If not data is not being transmitted received check the cabling If data is being received check the baud rate settings of all connec...

Страница 12: ...Part No 0G6960 Revision C 09 14 09 Printed in U S A...

Отзывы: