TROUBLESHOOTING GUIDE

No Lights/LEDs are Lit.

1.   Check for the proper battery supply at terminal block J10 pins 1 and 2.

•   J10 pin 1 should be +  Battery (12 or 24 volts).
•   J10 pin 2 should be – Battery.
•    Refer to the “ power supply requirements”  section at the beginning of the manual for 

cable specifications.

The “ Communication OK”  LED is flash-
ing at the rate: second ON/one second 
OFF.

1.   Does the RS485 communications cable meet specifications. Refer to the “ Communication 

with generator control system”  section at the beginning of this manual.

2.   Check that the RS485 connections are connected properly.

•   RS485+  connected to J10 pin 5.
•   RS485– connected to J10 pin 6.
•    Is the Shield/screen connected correctly. 

The shield/screen should be connected at the 

Generator end only.

3.   Check for proper installation of the RS485 cable between the Annunciator and the genera-

tor’s control panel. Is this cable sharing a conduit or running next to any high voltage or 
high current electrical lines?

4.   Use the Generator Controller GenLink communication diagnostics to check if data is being 

sent or received via the Tx and Rx check boxes. Go to the pull-down menu for diagnostics 
and select “ Com Ports” . Select the port the Annunciator is connected to (normally port 
0) and look to see if the check boxes change state. If not, data is not being transmitted/
received, check the cabling. If data is being received, check the baud rate settings of all 
connected equipment.

 

The “ Communication OK”  LED is flash-
ing at the rate:  0.5 seconds ON/two 
seconds OFF.

1.   Does the RS485 communications cable meet specifications? Refer to the “ Communication 

with generator control system”  section at the beginning of this manual.

2.   Is the cable shield connected correctly? 

The shield/screen should be connected at the 

Generator end only.

3.   Check for proper installation of the RS485 cable between the Annunciator and the genera-

tor’s control panel. Is this cable sharing a conduit or running next to any high voltage or 
high current electrical lines?

4.   Use Generator Controller GenLink communication diagnostics to check if data is being sent 

or received via the Tx and Rx check boxes. Go to the pull-down menu for diagnostics and 
select “ Com Ports” . Select the port the Annunciator is connected to (normally port 0) and 
look to see if the check boxes change state. If not, data is not being transmitted/received, 
check the cabling. If data is being received, check the baud rate settings of all connected 
equipment.

The "Green Status LED" (internal to the 
unit) is flashing at a 0.5 second ON/5 
second OFF rate.

1.  The RS485 Communications is not functioning. See items 1-4 above.

 

 

9

Remote Annunciator

Содержание 0G5719

Страница 1: ...21 light Remote Annunciator Owner s M anual...

Страница 2: ...Interface GUI available using a computer via the RS232 connector on the annunciator printed circuit board see Figure 2 Relays J1 J8 provides a set of normally open contacts All relays are energized c...

Страница 3: ...he same wire grouping as any high voltage or high current conductors 2 The generator control panel Baud Rate should be selected to be compatible with other components that are connected to the RS485 c...

Страница 4: ...ciator to provide strain relief for the connecting cables and wires Figure 3 RELAY ANNUNCIATION J1 J8 The user can select up to eight of the following 18 generator parameters to annunciate via the rel...

Страница 5: ...Figures 6 and 7 DIP Parameter Relay 1 1 RPM Sensor Loss 1 1 3 Overspeed 2 1 5 High Water Temp Low Water Level 3 1 10 Pre Low Fuel 4 Figure 6 S1 Figure 7 S2 Example 2 If subsequently DIP1 3 is removed...

Страница 6: ...ht to turn ON This shows whether the load is power by the utility For an engine controller that is part of an MPS system line power is not used PARAMETER BATTERY CHARGER AC FAILURE This light LED annu...

Страница 7: ...nication between the Remote Annunciator Panel and the Generator control system It typically requires less than a minute for the Annunciator to determine the correct baud rate and connect to the RS485...

Страница 8: ...his method allows for the connection of more than one Annunciator In Master mode the Annunciator is the Modbus master and will request data from the PM GC or PM SC The PM GC or PM SC must be set as a...

Страница 9: ...setting the Annunciator functions A GenLink serial cable P N 0F7707 should be used to connect a laptop computer s RS232 serial port to the Annunciator DB9 connector The GenLink cable is a Null Modem...

Страница 10: ...he following communication restrictions apply for multiple units on a common RS485 line A maximum of 15 1000 ohm RS485 Loads i e 57 6K Annunciator G panel H panels etc can be connected to the RS485 bu...

Страница 11: ...to normally port 0 and look to see if the check boxes change state If not data is not being transmitted received check the cabling If data is being received check the baud rate settings of all connec...