Generac Power Systems 0G5719 Скачать руководство пользователя страница 7

      These alarms will be latched/not latched by the annunciator 
according to the above table. They can be acknowledged at the 
annunciator using the ‘Reset' switch— the active lamps will then 
stop flashing and remain in the ON state until the alarm signal 
clears from the generator control panel. The "Reset" switch will 
also turn off and re-arm the horn.

NOTE:

10.   These lights can only be fully reset when the alarm state 

is no longer active and “Reset” has been pressed at both 
the generator control panel and the remote annunciator. 
Alternatively, at any time the horn can be turned OFF and 
re-armed with the "Re-Arm Horn" switch.

11.   When this annunciator is used in a Modular Power System 

(MPS), a warning on any one of the generators will cause 
the above lights to light, and alarm to sound (if the warning 
is audible).

SPARE INDICATOR

The spare indicator light/LED can be activated from the PM-GC or 
PM-SC by using the Integrated Logic Controller (ILC) feature in the 
G-panel or H-panel. Also see the section in this manual describing 
the operation and set-up of the spare keypad switch.

Annunciator Light

Light Color

Audible Alarm

System Ready

Green

Yes

Communication OK

Green

Yes

Line Power

Green

No

Spare

Green

No

SYSTEM STATUS INDICATORS

These lights/LEDs are for Status indication only— the normal 
condition is ON.

SYSTEM READY

 

‹

The System Ready is defined as ALL “ in service”  generators are 
ready to start, run, and supply power. Any generators manually 
declared as “ out of service”  will not affect this LED.
Upon a loss of System Ready, the annunciator will respond as 
follows:
1.  The System Ready LED will begin to flash.
2.  The alarm will sound.
The “ Re-arm Horn”  switch can be used to turn off and re-arm 
the horn, or the alarm can be fully acknowledged using the reset 
switch at which time the System Ready LED will turn off and 
remain off until the System Ready status is returned.

COMMUNICATION OK

 

‹

This LED will be ON as long as there is proper communication 
between the Remote Annunciator Panel and the Generator control 
system. It typically requires less than a minute for the Annunciator 
to determine the correct baud rate and connect to the RS485 
bus.
When communication failure occurs, the Annunciator will flash the 
communication LED, and sound the horn. The rate of flashing will 
be indicative of the cause of error.
1.  No reply from the generator control system, Frequency =  one 

second ON/one second OFF

2.  Consecutive data errors, Frequency =  0.5 second ON/two 

seconds OFF.

This alarm condition can be acknowledged at the Annunciator 
using the “ reset”  switch - the horn will be turned off and re-armed, 
and the communication OK light will continue to flash until proper 
communication returns.

GREEN STATUS LED (INTERNAL TO UNIT)

 

‹

If the green LED is flashing at a one second on and one sec-

•  

ond off rate, the unit is operational and is configured from the 
Windows Graphical User Interface.

If the green LED is flashing at a one second off and five seconds 

•  

on rate, the unit is operational and is configured from the DIP 
switches.

If the green LED is flashing at a half second on and five seconds 

•  

off rate, the unit is operational but there are no RS485 com-
munications.

If the unit is powered for 30 seconds and the Green Status LED 

•  

does not turn on at all during this time, the circuit board is not 
functional.

SYSTEM KEYPAD SWITCHES

TEST SWITCH

 

‹

While the test switch is pressed, all lights/LEDs will light and the 
horn will sound. When released the lights/LEDs will return to their 
original status. During this test, communication to the generator 
control system will be suspended.

RE-ARM HORN SWITCH

 

‹

The re-arm horn switch will silence the alarm horn and re-arm it 
for new alarm occurrences.

RESET SWITCH

 

‹

The reset switch is used to acknowledge any active alarms. It will 
re-set any flashing light/LED’s to a ON (steady) condition (or OFF 
for normally on lights). If the alarm no longer exists and it has also 
been latched OFF at the generator control panel (pre-alarm indica-
tors only) the active light will go OFF. It will also silence the horn 
and re-arm it for new occurrences.

 

 

5

Remote Annunciator

Содержание 0G5719

Страница 1: ...21 light Remote Annunciator Owner s M anual...

Страница 2: ...Interface GUI available using a computer via the RS232 connector on the annunciator printed circuit board see Figure 2 Relays J1 J8 provides a set of normally open contacts All relays are energized c...

Страница 3: ...he same wire grouping as any high voltage or high current conductors 2 The generator control panel Baud Rate should be selected to be compatible with other components that are connected to the RS485 c...

Страница 4: ...ciator to provide strain relief for the connecting cables and wires Figure 3 RELAY ANNUNCIATION J1 J8 The user can select up to eight of the following 18 generator parameters to annunciate via the rel...

Страница 5: ...Figures 6 and 7 DIP Parameter Relay 1 1 RPM Sensor Loss 1 1 3 Overspeed 2 1 5 High Water Temp Low Water Level 3 1 10 Pre Low Fuel 4 Figure 6 S1 Figure 7 S2 Example 2 If subsequently DIP1 3 is removed...

Страница 6: ...ht to turn ON This shows whether the load is power by the utility For an engine controller that is part of an MPS system line power is not used PARAMETER BATTERY CHARGER AC FAILURE This light LED annu...

Страница 7: ...nication between the Remote Annunciator Panel and the Generator control system It typically requires less than a minute for the Annunciator to determine the correct baud rate and connect to the RS485...

Страница 8: ...his method allows for the connection of more than one Annunciator In Master mode the Annunciator is the Modbus master and will request data from the PM GC or PM SC The PM GC or PM SC must be set as a...

Страница 9: ...setting the Annunciator functions A GenLink serial cable P N 0F7707 should be used to connect a laptop computer s RS232 serial port to the Annunciator DB9 connector The GenLink cable is a Null Modem...

Страница 10: ...he following communication restrictions apply for multiple units on a common RS485 line A maximum of 15 1000 ohm RS485 Loads i e 57 6K Annunciator G panel H panels etc can be connected to the RS485 bu...

Страница 11: ...to normally port 0 and look to see if the check boxes change state If not data is not being transmitted received check the cabling If data is being received check the baud rate settings of all connec...

Страница 12: ...Part No 0G6960 Revision C 09 14 09 Printed in U S A...

Отзывы: