Section 2: General Information and Setup
Owner’s/Installation Manual for SMM
5
Table 2-2. Lockout Switch Settings
Lockout
Switch
Position
Mode
Function
ON
GENERATOR
Power is NOT available on module output (contactor output). Contactor is OPEN.
ON
UTILITY
Power is available on module output (contactor output). Contactor is CLOSED.
OFF
GENERATOR
Module operates with standard load shed logic. Contactor is OPEN or CLOSED per logic.
OFF
UTILITY
Power is available on module output (contactor output). Contactor is CLOSED.
Table 2-3. LED States
State
LED State
Mode
Note
Shed
1 second flash
(1 On – 1 Off)
Generator
Module detected an overload and shed its load. This state only
occurs in generator mode, or during a first time utility power up for
five minutes of initial operation.
Lockout
(30 minutes)
3 second flash
(3 On – 3 Off)
Generator
Module detected an overload while trying to recover from a shed
situation. It identified the offending load and disabled operation for 30
minutes to allow other loads to operate. This state only occurs in
generator mode.
Lockout
Switch Active
6 second flash
(6 On – 6 Off)
Generator
Module output is disabled and there is no power to the appliance
while in generator mode. Lockout switch must be ON. See Table 2.
Lockout
Switch Active
ON
Utility
Lockout Switch operates in generator mode only. It has no function in
utility mode. LED is solid, indicating contactor is CLOSED and load is
connected. Lockout switch must be ON. See Table 2.
Normal
ON
Generator or Utility
Indicates contactor is CLOSED and appliance has power. This is the
default in utility mode. It is the normal operating state in generator
mode when an overload is not detected.
Test
1 second flash
Generator or Utility
Test button triggers a typical shed condition and overrides all other
states except generator lockout switch ACTIVE state.