Section 3: Installation, Tests and Troubleshooting
Owner’s/Installation Manual for SMM
7
Section 3: Installation, Tests and Troubleshooting
Electrical Specifications
Enclosure Specifications
Remove Contents from Carton
1.
Open carton.
2.
Remove and verify carton contents.
3.
Retain carton for mounting template.
Carton Contents:
•
Smart Management Module (SMM)
•
Priority decal
•
Owner/Installation manual
4.
Contact the place of purchase with the unit model
number for any missing carton contents.
5.
Record date of purchase on front cover of this
manual.
Tools Needed For Installation
•
Power drill and suitable drill bit
•
Phillips and flat head screwdrivers
•
Mounting screws or wall anchors
•
Electrical materials
•
Voltmeter to indicate voltage presence
Mounting Instructions
The recommended installation is near the electrical panel
or appliance/load. The enclosure has a UL type 3R rating
and can be mounted indoors or outdoors. It provides a
degree of protection against rain and sleet and is
undamaged by the formation of ice on the enclosure.
1.
Turn OFF both UTILITY (NORMAL) and
EMERGENCY (STANDBY) power supplies.
2.
Choose mounting location (near electrical panel,
appliance or load to be managed).
3.
Use a flat head screwdriver to remove appropriate
knockouts from module enclosure for wiring. See A
in
NOTE:
If outdoor installation is chosen, bottom
knockouts must be used to meet NEMA 3R rating and
protect against water ingress.
4.
Hold SMM enclosure against mounting surface
with arrows pointing up, and mark or drill four
mounting holes. See B in
for arrows.
5.
Install SMM enclosure to mounting surface using
appropriate mounting screws or wall anchors.
Figure 3-1. Knockouts and UP Arrows
Input Voltage
240 VAC
Current Rating
50A resistive, 40A inductive
Locked Rotor Amp Rating 240A
Motor Rating
3 HP
Contactor Coil Voltage
240 VAC
UL Rating
Type 3R
Temperature
-30 to 50 deg C (-22 to 122 deg F)
Electrocution. Turn utility and emergency
power supplies to OFF before connecting
power source and load lines. Failure to do so
will result in death or serious injury.
(000116)
DANGER
000138
A
A
A
B