X
GEM-P816 Installation Instructions
L
NAPCO Security Systems
WI994C 3/04
!
Page 34
Enable Local Alarm on First Zone “AND” Trip
See Zone ANDing (Do not program in UL installations.)
Exit/Entry Delay; Exit/Entry 1; Exit/Entry 2; Entry Relay
Delays permit exit and entry through the Entry/Exit Zone(s) after the system is armed without setting off an immediate alarm. Entry
delay allows the user time to enter and disarm the panel. Exit delay allows the user to leave the premises after the panel has been
armed. Unless the keypad has been configured otherwise, the sounder will come on and will pulse during the last 10 seconds of entry
delay to remind the user to disarm.
Two individually-programmable entry-delay times are provided to accommodate different entry zones. If two or more Exit/Entry Zones
are entered in succession, the delay programmed for the last Exit/Entry Zone entered will take precedence over all others. Exit-Delay
time and Entry-Delay time may each be programmed for up to 255 seconds (4 minutes). See Time Selection.
An external relay may be programmed to trip upon entry (see Programming Manual: Relay Event ID Codes, Area Entry Relays), and
remain on for a programmed duration.
Note:
In UL installations, maximum exit delay is 60 seconds; maximum entry delay is 45 seconds. In UL Mercantile installations,
maximum entry delay is 60 seconds.
Entry delay may be canceled by pressing the
F
button prior to arming, however it will be restored automatically upon disarming.
Exit/Entry Follower
A zone programmed as an Exit/Entry Follower will ignore detection during the exit delay, and only during entry delay if the Exit/Entry
Zone is entered first. Thus, detection devices (passive infrared detectors, for example) along the path between the keypad and the exit/
entry door will not signal an alarm during exit/entry delay under normal conditions. However, if a device in the Exit/Entry Follower Zone
detects a violation when the exit/entry door has not first been entered, there will be no entry delay and the Exit/Entry Follower Zone will
go into an instant alarm. If the panel is armed with the entry delays canceled (Instant protection), any violation on the Exit/Entry Zone or
the Exit/Entry Follower Zone will cause an immediate alarm.
Exit Time Restart
This option allows for the following scenario prior to the end of the Exit Time: a violation of an entry/exit zone, a restore, and a second viola-
tion of an entry/exit zone
restarts the Exit Time
. The panel does not allow the Exit Time to be restarted more than once. The default setting
for this option is
enabled
. Restart is event logged. (SIA CP-01: 4.2.2.3).
Exit Urgency Annunciation
When armed Away, exit is audible, and time is 60 seconds (default). Enabled with "Enable CP-01 Limits" in the EZ Program Menu.
(SIA CP-01: 4.2.2.2).
Expansion Module Zones; EZM Type; EZM Tamper
See Tamper
Zones 9–16 are expansion zones added to the basic system using expansion zone modules (EZMs). Any combination of GEM-EZM8
(8 zones) and/or the 4-zone EZM modules integral to each GEM-RP1CAe2 keypad may be used. Refer to the instructions
accompanying each module for wiring information.
Regardless of how the modules are arranged, the expansion zones are divided into consecutively-numbered groups of four. Each 8-
zone module comprises two groups. Each group is assigned a number.
EZ Arming (Easy Arming); Easy Arming Closing Report
Permits quick arming by simply pressing the
U
button. Each keypad may be individually programmed for Easy Arming (see Keypad
Features). Disarming still requires entry of a valid user code. Do not program Easy Arming in UL installations. If closings are reported,
Easy Arming will report as User 35.
Fire; Keypad Fire
Any zone may be programmed for Fire. Connect normally-open devices across a Fire Zone. (The EOL2.2K end-of-line resistor must be
installed.) A short across the zone will cause a fire alarm, which will be indicated at the keypad by a “
FIRE ALARM
” LCD display and
pulsing sounder. An open circuit on the Fire Zone will identify a trouble and cause flashing “
SYSTEM TROUBLE/E41-00 SERVICE
” LCD
display and pulsing sounder after a 10-second delay. The sounder may be silenced by pressing the
C
button. The LED will go off
within 30 seconds after reset if the alarm or trouble is cleared. For Smoke-Detector Reset, see Alarm Outputs. Fire or Keypad Fire can
be made to trip an alarm or report to Central Station. If Keypad Fire is programmed, pressing both the
7
and
G
buttons at
the same time will sound a fire panic alarm and display “
FIRE ALARM
” at the keypad. The Keypad Fire function is supplementary to the
hardwired zones.
Note:
This feature shall not be considered a substitute for listed manual initiating devices. A fire condition that has
not been restored will cause the zone number and description to scroll. To reset (acknowledge) the condition, enter a valid code, then
press the
U
button.
Fire Verification (Not for use in California.)
An alarm on any Fire Zone programmed for “Fire Verification” and connected to the fire power terminal will cause all fire zones to be
powered down for 12 seconds. (All devices must be wired with + power on Terminal 25.) After this time, power is restored and a 4-
second power-up time is started. Thereafter, the zone will be active again. This represents a total processing delay of 16 seconds from
the time the alarm is first detected. If an alarm condition still exists at this time or reoccurs within 2 minutes, an alarm will be initiated,
otherwise the zone will return to its original state.
NOTE:
A zone programmed for “Fire Verification” must be programmed as a “Fire
Zone” as well.
Glossar
y