C60
Connector 2
Connector 4
Connector 2
Control
function 1
Control
function 2 + 3
Control
function
Connectors
2
4
1 (NC)
+
-
2 (NO)
-
+
3 (DA)
+
+
+ = available / - = not available
(for connectors 2 / 4 see pictures above)
11.4 Connecting the
control medium
Important:
Connect the control medium lines
tension-free and without any bends
or knots!
Use appropriate connectors
according to the application.
Thread size of the control medium
connectors: G1/8
Control function
Connectors
1 Normally closed (NC) 2: Control medium (open)
2 Normally open (NO)
4: Control medium (close)
3 Double acting (DA)
2: Control medium (open)
4: Control medium (close)
For connectors 2 / 4 see pictures above
11.5 Setting the stroke limiter
The stroke limiter is used to reduce the
opening stroke by setting a preselected flow
rate.
For all actuator sizes the stroke is 1 mm /
turn.
Tools needed:
Actuator size 1: Socket wrench size 8
Actuator size 2: Socket wrench size 9
Actuator size 3: Socket wrench size 10
Delivery condition of the stroke limiter:
The stroke limiter is fully open i.e. the stroke
limiter is inactive.
Procedure
1. Remove transparent cap: Either push a
2.5 mm screw driver into ready-made
grooves under the transparent cap
and carefully pry the transparent cap
upwards
or pull it up manually.
39 / 48