C60
Installation - Butt weld spigots:
DANGER
Vapor fumes from PFA welding can
cause health related issues!
®
Risk of damage to respiratory tracts,
caustic burns / poisoning!
G
Weld PFA components in a well-
ventilated area.
G
Only use approved welding equipment.
G
Wear protective gear.
G
Breathing masks are recommended.
G
Welding may only be carried out by
quali
fi
ed trained personnel.
Important:
Poor or careless welding
procedures and processes will void
warranty and cause damage to the
product. The results of poor welding
procedures are valve leakage and
deformation.
Adhere to good welding practices!
Installation - Flare and space saver
connections:
1. Also refer to GEMÜ FlareStar
®
brochure
and GEMÜ
fl
are and assembly
instructions for preparation and
connection of
fl
are connections!
2. Push the
fl
ared tube onto the
fl
are
connection.
3. Screw on union nut.
4. Use connection
fi
ttings resistant to and
suitable for the ambient conditions.
Installation - PrimeLock connections:
1. Preparation of the tube by mounting
the sleeve (observe manufacturer's
instructions:
www.entegris
fl
uidhandling.com /
Product.aspx?G=1905.
2. Push together PrimeLock connection
with prepared tube.
3. Tighten PrimeLock union nut.
Observe appropriate regulations for
connections!
After the installation:
G
Reactivate all safety and protective
devices.
G
Check the function and tightness of
installed valves at regular intervals.
11.2 Operation
Optical position indicator
Valve open
Valve closed
11.3 Control functions
The following control functions are available:
Control function 1
Normally closed
(
NC
)
:
Valve resting position: closed by
spring force. Activation of the actuator
(connector 2) opens the valve. When the
actuator is vented, the valve is closed by
spring force.
Control function 2
Normally open
(
NO
)
:
Valve resting position: opened by
spring force. Activation of the actuator
(connector 4) closes the valve. When the
actuator is vented, the valve is opened by
spring force.
Control function 3
Double acting
(
DA
)
:
Valve resting position: undefined. The
valve is opened and closed by activating
the respective control medium connectors
(connector 2: open / connector 4: close).
38 / 48