GEMÜ 649 eSyDrive
16 Network connection
16 Network connection
16.1 Network settings
The network interface has the following default settings:
IP address: 192.168.2.1
Subnet screen: 255.255.252.0
The default settings can be changed. See the eSy-Web operat-
ing instructions.
16.2 Connecting the network
1. Connect the network plug and cables with the electrical
connection X2 of the product.
2. Change the IP address using the web server.
16.3 Resetting the network settings
1. Ensure that the "ON-Site" DIP switch
8
is not in the "ON"
position.
2. Press and hold down the "OPEN" button
9
for at least 8 s.
ð
LED 1 flashes fast in blue.
3. Press the "INIT/CLOSE" button
10
.
ð
Network settings are reset in the default settings.
17 Commissioning
17.1 Commissioning on the device
1. Ensure that the "ON-Site" DIP switch
8
is not in the "ON"
position.
2. Press and hold down the "INIT/CLOSE" button
10
for at
least 8 s.
ð
Initialisation of the actuator begins.
3. Green and orange LEDs flash alternately.
ð
Initialisation is completed.
ð
Commissioning is completed.
17.2 Commissioning via the eSy-Web web interface
●
See separate eSy-Web operating instructions.
17.3 Commissioning via digital input
ü
The function of input 3 is set to init.
1. Connect 24 V signal briefly (max. 2 s) to connection X3 on
pins 7 and 4.
ð
Initialisation of the actuator begins.
2. Green and orange LEDs flash alternately.
ð
Initialisation is completed.
ð
Commissioning is completed.
18 Operation
18.1 Operation on the device
18.1.1 Moving the valve to the open position
1. Move the "ON-Site" DIP switch
8
to the "ON" position.
ð
Control on the device is activated.
2. Press the "OPEN" button
9
.
ð
The valve moves slowly to the open position.
3. Also press the "INIT/CLOSE" button
10
.
ð
The valve moves quickly to the open position.
ð
If the valve is fully opened, the high visibility LEDs are
lit in green.
4. Move the "ON-Site" DIP switch
8
to the "OFF" position.
ð
Control on the device is deactivated.
ð
The valve is in the open position.
18.1.2 Moving the valve to the closed position
1. Move the "ON-Site" DIP switch
8
to the "ON" position.
ð
Control on the device is activated.
2. Press the "INIT/CLOSE" button
10
.
ð
The valve moves slowly to the closed position.
3. Also press the "OPEN" button
9
.
ð
The valve moves quickly to the closed position.
ð
If the valve is fully closed, the high visibility LEDs are lit
in orange.
4. Move the "ON-Site" DIP switch
8
to the "OFF" position.
ð
Control on the device is deactivated.
ð
The valve is in the closed position.
18.2 Operation via the web server
See separate "eSy-Web" operating instructions.
18.3 Manual override
WARNING
Rotating cover!
▶
Risk of crushing.
●
Disconnect the power supply before
using the manual override.
1. Disconnect the power supply.
2. Turn housing cover
3
clockwise.
3. Remove housing cover
3
.
3
4. Place the actuator of housing cover
12
in the starting
point for manual override.
Содержание 649 eSyDrive
Страница 24: ...9 2 5 www gemu group com 24 48 GEM 649 eSyDrive 9 Dimensions...
Страница 26: ...9 2 7 www gemu group com 26 48 GEM 649 eSyDrive 9 Dimensions...
Страница 30: ...10 www gemu group com 30 48 GEM 649 eSyDrive 10...
Страница 37: ...www gemu group com 37 48 GEM 649 eSyDrive 15 6 15 Electrical connection...