User’s & Technical Manual –
ANALOG LIQUID LEVEL SENSOR ALLS6000
GELEC
Industrial Electronics
PAGE
22
NOTE
When the power is interrupted and the liquid level is between the (TL) and the (DL), the
relay will be deactivated. After the power is restored, if the device operates in filling mode,
the relay will be activated and the tank will fill up to the (TL). If the device operates in
draining mode, the relay will remain deactivated until the level comes up to the (TL) and
then it will be activated for the drain to begin.
13.
INSTALLATION
Place the
ALLS6000
in an
appropriate location. Do not
install in a dusty, humid, or
vibrating environment. Do not
place it near heater, or air
conditioner. Keep it away from
air, steam, open flame, extremely
high or low temperature, and
humidity. Keep liquids away from
the
ALLS6000
. Spillage into the
cabinet may result to fire, electric
shock, or equipment damage. Do
not block the ventilated slots
above and below the unit.
If a small object or liquid falls/spills into the
ALLS6000
cabinet, unplug the unit
immediately. Have the unit checked by a qualified service engineer before using it again.
The
ALLS6000
is composed of an electronic board and a plastic box suitable for electrical
and electronic devices. At the rear there is a clip for the mounting. The unit is made to be
installed inside an electrical control panel, placed on a mounting rail of Ω type DIN
NS32/NS35. In the rearward there is a clip for the mechanical mounting (lock) on the rail,
with the release hook at the bottom.
A 30mm extra space below the unit is needed for the air pipes and 15mm on top of it, for
the connection wires. Ensure that the connected air pipes at the bottom of the unit are
smoothly curved and not bended. In order to avoid liquid suction into the air pipes, install
the device on a higher point than your vessel.
fig. 22