User’s & Technical Manual –
ANALOG LIQUID LEVEL SENSOR ALLS6000
GELEC
Industrial Electronics
PAGE
18
When the differential level (DL) is calibrated, any target level (TL) selection through the
potentiometer, will lead the device to automatically calculate the working region. At this
example for a (TL) selection of 80cm, the working region will be 80cm-70cm.
Notice that with the
se example’s
steps, for every (TL) you select with the potentiometer,
the (DL) will be 12,5% less.
PRESELECTED VALUES
The standard version ALLS6000-S1 can control the liquid level in tanks with height from
10cm to 100cm and has the below preselected values and parameters.
Liquid : Soft Water
High level (HL) : 100 cm
Differential level (DL) : 50% of (TL).
Low level (LL) : 1cm (0+1cm offset)
NOTES
The device measures the hydrostatic pressure of the liquid contained in the tank, so
the tank
’s
volume and shape are not factors that influence the measurement.
The calibration is done for a specific tank height and for a specific liquid. If you use
the same tank with a different liquid, a new calibration has to be done.
In order to have the optimum measurement resolution, it is recommended the high
level to be calibrated near the target level.
According to your unit version, take care not to exceed the recommended liquid
level height. If the sensor-applied pressure is higher than the appropriate, the sensor
will be destroyed.