3.5 Serial connections
“MODBUS” serial
“CANopen” serial
“PROFIBUS DP” serial
D-SUB connector
9-pin Male
D-SUB Connector
9-pin Female
From CANbus network
Shielded cable 2 pairs 22/24 AWG
CANopen conformity
We advise you to connect a 120
Ω
1/4W resistance between
the "CAN_L" and "CAN_H" signals at both ends of the
CANbus network.
D-SUB Connector
9-pin Male
Shielded cable 1 pair 22 AWG
MODBUS conformity
From Modbus network
It is also advisable to connect the "GND" signal between
Modbus devices having a line distance > 100m.
Shielded cable 1 pair 22 AWG
PROFIBUS conformity
From PROFIBUS
network
We advise you to connect a 220
Ω
1/4W resistance between
the "RxD/TxD-P" and "RxD/TxD-N" signals, a 390
Ω
1/4W
resistance between the "RxD/TxD-P" and "Vp" signals, and a
390
Ω
1/4W resistance between the "RxD/TxD-N" and
"DGND" signals at both ends of the Profibus network.
“DeviceNet” serial
V-
CAN_L
SHIELD
CAN_H
V+
12
3
4
5
Connector 5 pin
From DeviceNet network
Shielded cable 2 pairs 22/24 AWG
DeviceNet conformity
We advise you to connect a 120
Ω
1/4W resistance between
the "CAN_L" and "CAN_H" signals at both ends of the
DeviceNet network.
9
80346B_MHW_GFX-VALVOLE_0709_ENG
TX / RX+
TX / RX-
TX / RX+
TX / RX-
SCH
GND
TX / RX+
TX /
TX / RX-
GND
From previous module
on Modbus network
To next module on
Modbus network
We advise you to connect pins 6 to 7 and pins 8 to 9 on the
connector of the last Geflex on the Modbus network to insert