• Out
of.52
lo.52
flt.2
ofst
tyP.2
Digital filter
on main input
Digital filter on display
process variable:
acts as hysteresis
Decimal point position for
main input scale, alarm
and remote setpoint
(*) not available for TC,
RTD and PTC scales
Minimum limit of main
input scale
Maximum limit of main
input scale
Offset correction
of main input
Digital filter on aux input
(if enabled)
[see “hrd.1” on Hrd]
Aux analogue input
function (if enabled)
[see “hrd.1” on Hrd]
and enable custom
limitation
Minimum range for aux
input (if enabled)
[see “hrd.1” on Hrd]
Maximum range for aux
input (if enabled)
[see “hrd.1” on Hrd]
Offset correction of aux
input (if enabled)
[see “hrd.1” on Hrd]
Lower limit for local
setpoint and absolute
alarms
Upper limit for local
setpoint and absolute
alarms
+ 8 to select custom linearization
(see table 32 values in Lin)
46
47
48
49
50
51
52
53
54
55
56
57
58
0.0 ... 20.0 sec
0 ... 9.9
scale points
dP_S Format
0
xxxx
1
xxx.x
2
xx.xx (*)
3
x.xxx (*)
min...max input range
selected in tyPE
min...max input range
selected in tyPE
-999 ... 999
scale points
tYP.2
Auxiliary input function
0
None
1
Remote setpoint
2
Analogue remote manual
3
Analogue power reset
4
Current transformer
input for HB
0.0 ... 20.0 sec
Min...max input range selected
in tyP.2
Remote setpoint:
absolute: (range limits)
relative: (-999 ... 999)
Remote manual / Reset power:
(-100.0 ... 100.0%)
Current transformer
(0.0 ... 999.9)
-999 ... 999
scale point
Lo.S ... Hi.S
Lo.S ... Hi.S
al.2.t
al.3.t
al.i.r
al.2.r
al.3.r
al.1.t
64
63
61
Out
Output settings
Select
reference
signal for
alarm 1
Select
reference
signal for
alarm 2
Select
reference
signal for
alarm 3
AL.1.t, AL.2.t, AL.3.t
Alarm
type 1
Alarm
type 2
Alarm
type 3
HB alarm
function
+ 8 to disable on power up until first interception
+ 16 to latch alarm
60
62
65
66
AL.x.t Direct (high limit)
Absolute or
Normal
Inverse (low limit)
Relative
Symmetric
to active setpoint (window)
0
direct
absolute
normal
1
inverse
absolute
normal
2
direct
relative
normal
3
inverse
relative
normal
4
direct
absolute
symmetric
5
inverse
absolute
symmetric
6
direct
relative
symmetric
7
inverse
relative
symmetric
Hb_F Descrizione funzionalità
0
Uscita relè, logica: allarme attivo
ad un valore della corrente di carico
inferiore alla soglia impostata nel
tempo di ON dell’uscita di controllo
1
Uscita relè, logica: allarme attivo ad un
valore della corrente di carico superiore
alla soglia impostata nel tempo di OFF
dell’uscita di controllo
2
Allarme attivo se una delle funzioni 0 e 1
è attiva (OR logico tra le funzioni 0 e 1) (*)
3
Per uscita continua di riscaldamento
7
Per uscita continua di raffreddamento
+ 0 assigned to output Out1 (only for Hb_F= 0, 1, 2)
+ 4 assigned to output Out2 (only for Hb_F= 0, 1, 2)
+ 8 assigned to output Out3 (only for Hb_F= 0, 1, 2)
+ 12 assigned to output Out4 (only for Hb_F= 0, 1, 2)
+ 16 inverse HB alarm
(*) minimum setting is fixed at 12.5% of amperometric full scale
AL.1.r, AL.2.r, AL.3.r
AL.x.r
Variable to compare
Alarm setpoint
0
PV (Process variable)
AL
1
InP.2 (aux input)
AL
2
SSP (active setpoint)
AL (only absolute)
3
PV (Process variable)
InP.2
(aux input)
Out 1
Allocation of
reference signal:
HEAT, COOL,
AL1, AL2, AL3,
repetition of
digital inputs,
programmer
events, end of
cycle
rL.o.1, rL.o.2, rL.o.3, rL.o.4
+ 32 for inverse logic signal output
Out 2
Allocation of
reference signal:
HEAT, COOL,
AL1, AL2, AL3,
repetition of
digital inputs,
programmer
events, end of
cycle
Out 3
Allocation of
reference signal:
HEAT, COOL,
AL1, AL2, AL3,
repetition of
digital inputs,
programmer
events, end of
cycle
67
68
69
rL.o.x Function of main output relay/logic (OUT1)
0
HEAT (control output for heating)
1
COOL (control output for cooling)
2
AL1 - alarm 1
3
AL2 - alarm 2
4
AL3 - alarm 3
5
AL.HB - alarm HB
6
LBA - alarm LBA
7
IN1 - repetition of logic input 1
8
IN2 - repetition of logic input 2
9
-
10
-
11
programmer end of cycle
12
-
13
Repeat Set / Reset
14
(AL1) OR (AL2)
15
(AL1) OR (AL2) OR (AL3)
16
(AL1) AND (AL2)
17
(AL1) AND (AL2) AND (AL3)
18
(HBAL) OR (AL1)
19
(HBAL) OR (AL1) OR (AL2)
20
(HBAL) AND (AL1)
21
(HBAL) AND (AL1) AND (AL2)
22
programmer event 1
23
programmer event 2
24
programmer event 3
25
programmer event 4
26
programmer HBB
27
programmer in START
28
programmer in RESET
29
programmer “RUNNING”
(*) only for rL.o.1.; HB alarm is disabled if associated with Out1 output
64
Heat control output with
fast cycle time (*)
65
Cool control output with
fast cycle time (*)
rl.o.1
rl.o.2
rl.o.3
rl.o.4
Out 4
Allocation of reference signal: HEAT, COOL, AL1, AL2, AL3,
repetition of digital inputs, programmer events, end of cycle
70
dp s
-
lo s
-
xb f
-
lo l
-
filt
fild
xi s
-
xi.52
xi l
-
7