• Out  

of.52

lo.52

flt.2

ofst

tyP.2

Digital filter

on main input

Digital filter on display 

process variable:

acts as hysteresis

Decimal point position for 

main input scale, alarm 

and remote setpoint

(*) not available for TC, 

RTD and PTC scales

Minimum limit of main 

input scale

Maximum limit of main 

input scale

Offset correction

of main input

Digital filter on aux input

(if enabled)

[see “hrd.1” on Hrd]

Aux analogue input 

function (if enabled) 

[see “hrd.1” on Hrd] 

and enable custom

limitation

Minimum range for aux 

input (if enabled)

[see “hrd.1” on Hrd]

Maximum range for aux 

input (if enabled)

[see “hrd.1” on Hrd]

Offset correction of aux 

input (if enabled)

[see “hrd.1” on Hrd]

Lower limit for local 

setpoint and absolute 

alarms

Upper limit for local 

setpoint and absolute 

alarms

+ 8 to select custom linearization 

(see table 32 values in Lin)

46

47

48

49

50

51

52

53

54

55

56

57

58

0.0 ... 20.0 sec

0 ... 9.9

scale points

dP_S Format

 0 

xxxx

 1 

xxx.x

 2 

xx.xx (*)

 3 

x.xxx (*)

min...max input range 

selected in tyPE

min...max input range 

selected in tyPE

-999 ... 999

scale points

tYP.2 

Auxiliary input function

 0 

None

  1 

Remote setpoint

  2 

Analogue remote manual

  3 

Analogue power reset

  4 

Current transformer

   

input for HB

0.0 ... 20.0 sec

Min...max input range selected 

in tyP.2

Remote setpoint:

 

absolute: (range limits)

 

relative: (-999 ... 999)

Remote manual / Reset power:

 

(-100.0 ... 100.0%)

Current transformer

 

(0.0 ... 999.9)

-999 ... 999

scale point

Lo.S ... Hi.S

Lo.S ... Hi.S

al.2.t

al.3.t

al.i.r

al.2.r

al.3.r

al.1.t

64

63

61

Out 

Output settings

Select 

reference 

signal for 

alarm 1

Select 

reference 

signal for 

alarm 2

Select 

reference 

signal for 

alarm 3

AL.1.t, AL.2.t, AL.3.t

Alarm 

type 1

Alarm 

type 2

Alarm 

type 3

HB alarm

function

+ 8 to disable on power up until first interception

+ 16 to latch alarm

60

62

65

66

 AL.x.t  Direct (high limit) 

Absolute or 

Normal

   

Inverse (low limit) 

Relative 

Symmetric

   

 

to active setpoint  (window)

 0 

direct 

absolute 

normal

 1 

inverse 

absolute 

normal

 2 

direct 

relative 

normal

 3 

inverse 

relative 

normal

 4 

direct 

absolute 

symmetric

 5 

inverse 

absolute 

symmetric

 6 

direct 

relative 

symmetric

 7 

inverse 

relative 

symmetric

 Hb_F  Descrizione  funzionalità

  0 

Uscita relè, logica: allarme attivo

   

ad un valore della corrente di carico

   

inferiore alla soglia impostata nel

   

tempo di ON dell’uscita di controllo

  1 

Uscita relè, logica: allarme attivo ad un

   

valore della corrente di carico superiore 

   

alla soglia impostata nel tempo di OFF 

   

dell’uscita di controllo

  2 

Allarme attivo se una delle funzioni 0 e 1

   

è attiva (OR logico tra le funzioni 0 e 1) (*)

  3 

Per uscita continua di riscaldamento

  7 

Per uscita continua di raffreddamento

 + 0      assigned to output Out1 (only for Hb_F= 0, 1, 2)

 + 4      assigned to output Out2 (only for Hb_F= 0, 1, 2)

 + 8      assigned to output Out3 (only for Hb_F= 0, 1, 2)

 + 12    assigned to output Out4 (only for Hb_F= 0, 1, 2)

 + 16    inverse HB alarm      

(*) minimum setting is fixed at 12.5% of amperometric full scale

AL.1.r, AL.2.r, AL.3.r

 AL.x.r 

Variable to compare 

Alarm setpoint

  0 

PV (Process variable) 

AL

  1 

InP.2 (aux input) 

AL

  2 

SSP (active setpoint) 

AL (only absolute)

  3 

PV (Process variable) 

InP.2 

   

 

(aux input)

Out 1

Allocation of 

reference signal: 

HEAT, COOL, 

AL1, AL2, AL3, 

repetition of 

digital inputs, 

programmer 

events, end of 

cycle

rL.o.1, rL.o.2, rL.o.3, rL.o.4

+ 32 for inverse logic signal output

Out 2

Allocation of 

reference signal: 

HEAT, COOL, 

AL1, AL2, AL3, 

repetition of 

digital inputs, 

programmer 

events, end of 

cycle

Out 3

Allocation of 

reference signal: 

HEAT, COOL, 

AL1, AL2, AL3, 

repetition of 

digital inputs, 

programmer 

events, end of 

cycle

67

68

69

 rL.o.x  Function of main output relay/logic (OUT1)

 0 

HEAT (control output for heating)

 1 

COOL (control output for cooling)

  2 

AL1 - alarm 1

  3 

AL2 - alarm 2

  4 

AL3 - alarm 3

  5 

AL.HB - alarm HB

  6 

LBA - alarm LBA

  7 

IN1 - repetition of logic input 1

  8 

IN2 - repetition of logic input 2

 9 

-

 10 

-

 11 

programmer end of cycle

 12 

-

 13 

Repeat Set / Reset

 14 

(AL1) OR (AL2)

 15 

(AL1) OR (AL2) OR (AL3)

 16 

(AL1) AND (AL2)

 17 

(AL1) AND (AL2) AND (AL3)

 18 

(HBAL) OR (AL1)

 19 

(HBAL) OR (AL1) OR (AL2)

 20 

(HBAL) AND (AL1)

 21 

(HBAL) AND (AL1) AND (AL2)

 22 

programmer event 1

 23 

programmer event 2

 24 

programmer event 3

 25 

programmer event 4

 26 

programmer HBB

 27 

programmer in START

 28 

programmer in RESET

 29 

programmer “RUNNING”

(*) only for rL.o.1.; HB alarm is disabled if associated with Out1 output

 64 

Heat control output with

  

fast cycle time (*)

 65 

Cool control output with

  

fast cycle time (*)

rl.o.1

rl.o.2

rl.o.3

rl.o.4

Out 4

Allocation of reference signal: HEAT, COOL, AL1, AL2, AL3, 

repetition of digital inputs, programmer events, end of cycle

70

dp s

-

lo s

-

xb f

-

lo l

-

filt

fild

xi s

-

xi.52

xi l

-

7

80090G_MHW_1600-1800P_04-2013_ENG

Содержание 1600P

Страница 1: ...range with or without decimal point PTC type on request DIN 43760 Pt100 JPT100 990Ω 25 C Max line resistance for RTD 20Ω Safety detection of short circuit or opening of probes LBA alarm HB alarm C F selection configurable from faceplate Linear scale ranges 1999 to 9999 with configurable decimal point position Thermocouples IEC 584 1 J K R S T B E N Ni Ni18Mo L NiCr CuNi Cold junction error 0 1 C C...

Страница 2: ...r supply isolated 1500V 10 24Vdc max 30mA short circuit protection 9 5 18 20 19 21 22 Out2 AL1 Out1 Main C 32 W1 Transmitter supply GND Vt 1 2 3 4 5 6 7 8 9 10 11 24 25 26 27 28 29 30 31 32 33 22 21 20 19 18 17 16 15 14 13 12 1800 1600 NC NC NC NO NO NO C C PWR 3 1 2 T 3 1 2 T Key Function defined with but 2 parameter M A key Function defined with butt parameter PV Display Indication of process va...

Страница 3: ...eep the F key pressed to scroll the menus Release the F key to select the displayed menu Press the F key to access the parameters Keep the F key pressed to exit any menu Keep F Auto Man keys pressed for 2 sec on any menu to go immediately to level 1 display S3 ON Current setpoint display only LEVEL 1 MENU PASS NO SI Hrd U CAL S4 ON YES NO Custom menu Password User calibration Protection code The a...

Страница 4: ...ON 11 ON ON OFF ON 12 OFF OFF ON ON 13 ON OFF ON ON 14 OFF ON ON ON 15 ON ON ON ON S step hold events Step S advanced through digital input function When digital inputs have state set in this function program automatically advances to next step otherwise it waits at end of previous step function is enabled through SP Pr parameter on Hrd menu d i F 1 and or d i F 2 set to 12 Hold Back Band value sy...

Страница 5: ... control Ctrl 14 has been selected s tvn CFG Enabling self tuning autotuning softstart CFG Control parameters 15 S tun Continuos Self tuning Softstart autotuning 0 NO NO NO 1 YES NO NO 2 NO YES NO 3 YES YES NO 4 NO NO YES 5 YES NO YES 6 7 8 WAIT NO NO 9 GO NO NO 10 WAIT YES NO 11 GO YES NO 12 WAIT NO YES 13 GO NO YES Note 1 Active S tun functionS reset when switching from Automatic to Manual Propo...

Страница 6: ...o local setpoint 2 digital absolute from serial line 3 digital relative to from serial line local setpoint PROBE TC SEnS 0 tYPE Probe type Scale Scale range max Scale range max C F without decimal point with decimal point 0 PTC 990Ω C 55 120 55 0 120 0 1 PTC 990Ω F 67 248 67 0 248 0 2 PTC 990Ω C Custom scale 3 PTC 990Ω F Custom scale tYPE Signal type Scale Max scale range 0 0 50mV linear 1999 9999...

Страница 7: ...lla corrente di carico inferiore alla soglia impostata nel tempo di ON dell uscita di controllo 1 Uscita relè logica allarme attivo ad un valore della corrente di carico superiore alla soglia impostata nel tempo di OFF dell uscita di controllo 2 Allarme attivo se una delle funzioni 0 e 1 è attiva OR logico tra le funzioni 0 e 1 3 Per uscita continua di riscaldamento 7 Per uscita continua di raffre...

Страница 8: ... analogue repetition signal output 2 Out W2 Assignment of signal or reference value PV SP SP PROG DEV DEV IN AUX HEAT COOL AL1 AL2 AL3 serial line value 79 80 81 Hrd sp pr hrd i hrd 2 Hrd Hardware configuration Installation of aux input digital inputs serial interface Installation of relay logic outputs MAIN AL1 AL2 AL3 and analogue outputs W1 W2 16 to enable analogue output W1 32 to enable analog...

Страница 9: ...e 0 10V 2 10V 6 Custom 10V 7 Custom max 50mV Selection of probe type for main input 16 disable function in configuration menu only for butt parameters 8 to enable main input curve 4 point correction alternative to custom linearization See description in Main Input Correction Function section 16 to disable averaging filter on sampled value available from software release 3 05 8 to disable averaging...

Страница 10: ...int value rPt ramp time from 0 0 to 99h59m time base in h m or 99m59s time base in m s set a time that gives a faster or slower variation depending on the initial value and on the final setpoint Sot hold time from 0 0 to 99h59m time base in h m or 99m59s time base in m s Hbb tolerance band symmetrically positioned above and below the setpoint and referenced to the main input or the auxiliary input...

Страница 11: ...d by intercepting the setpoint profile point B1 If interception is not possible as in the case of variable at PV1 program restart occurs at the current time and setpoint If the Hbb control is enabled the programmer time base remains stopped until the variable re enters the set tolerance band symmetrically placed around the setpoint PV1 1 2 3 4 t1 t2 A1 A B1 B PV Set point Step 0 time Display Modif...

Страница 12: ...he output is in OFF state The alarm is reset automatically when alarm conditions have been cleared If AL Hb is set at 0 both types of HB alarm are disabled and the assigned relay is de energized The load current reading is displayed by selecting InP2 level 1 NOTE ON OFF times refer to the cycle time set for the selected output Alarm Hb_F 3 7 for analog output is ON when the load current is lower t...

Страница 13: ...ional band at 0 1 with on off type setting C Switch to automatic and observe the behavior of the variable It will be similar to that in the figure D The PID parameters are calculated s follows Proportional band Peak P B x 100 V max V min V max V min is the scale range Integral time It 1 5 x T Derivative time dt It 4 E Switch the unit to manual set the calculated parameters Return to PID action by ...

Страница 14: ...mmer model the program is in STOP if self tuning is activated when the unit is switched on 14 SELF TUNING 15 AUTO TUNING PID parameters cannot be set if the self tuning function is enabled The function can be one of two types permanent or one shot The first continuously measures system oscillations to find the optimum PID values to reduce such oscillations It does not engage if the oscillations dr...

Страница 15: ...n is applied to linear scales 50mv 10V 20mA Pot The four values are set on the Lin menu as follows A1 St100 B1 St01 A2 St02 B2 St03 Setting is limited to the defined scale LoS HiS on InP menu The offset function oFt parameter on InP menu remains enabled Limits B1 always greater than A1 B1 A1 at least 25 of full scale of selected probe Example Sens 9 TyPE 0 Pt100 natural scale 200 600 dPS 0 LoS 0 H...

Страница 16: ...an isolation transformer be used only for the devices connecting the screen to ground it is important for the electrical system to have a good ground connection voltage between neutral and ground must not exceed 1V and resistance must be less than 6Ohm if the supply voltage is highly variable use a voltage stabilizer for the device use line filters in the vicinity of high frequency generators or a...