sp.ty
type
Setpoint type:
LOC/REM, Select type
of remote setpoint
[0...7]
Probe type, signal, enable custom linearization,
and main input scale
tYPE Probe type
Scale
Scale range max.
Scale range max.
(C/F)
without decimal point
with decimal point
0
J (Fe-CuNi)
C
0 / 1000
0.0 / 999.9
1
J (Fe-CuNi)
F
32 / 1832
32.0 / 999.9
2
K (NiCr-Ni)
C
0 / 1300
0.0 / 999.9
3
K (NiCr-Ni)
F
32 / 2372
32.0 / 999.9
4
R (Pt13Rh - Pt)
C
0 / 1750
Not available
5
R (Pt13Rh - Pt)
F
32 / 3182
Not available
6
S (Pt10Rh - Pt)
C
0 / 1750
Not available
7
S (Pt10Rh - Pt)
F
32 / 3182
Not available
8
T (Cu-CuNi)
C
-200 / 400
-199.9 / 400.0
9
T (Cu-CuNi)
F
-328 / 752
-199.9 / 752.0
10
B (Pt30Rh - Pt6Rh)
C
44 / 1800
Not available
11
B (Pt30Rh - Pt6Rh)
F
111 / 3272
Not available
12
E (NiCr-CuNi)
C
-100 / 750
-100.0 / 750.0
13
E (NiCr-CuNi)
F
-148 / 1382
-148.0 / 999.9
14
N (NiCrSi-NiSi)
C
0 / 1300
0.0 / 999.9
15
N (NiCrSi-NiSi)
F
32 / 2372
32.0 / 999.9
16
(Ni - Ni18Mo)
C
0 / 1100
0.0 / 999.9
17
(Ni - Ni18Mo)
F
32 / 2012
32.0 / 999.9
18
L - GOST (NiCr-CuNi)
C
0 / 600
0.0 / 600.0
19
L - GOST (NiCr-CuNi)
F
32 / 1112
32.0 / 999.9
20
TC
C
Custom scale
(*)
21
TC
F
Custom scale
(*)
tYPE Probe type
Scale
Scale range max.
Scale range max.
(C/F)
without decimal point
with decimal point
0
PT100
C
-200 / 850
-199.9 / 850.0
1
PT100
F
-328 / 1562
-199.9 / 999.9
2
JPT100 (JIS C 1609/81) C
-200 / 600
-199.9 / 600.0
3
JPT100 (JIS C 1609/81) F
-328 / 1112
-199.9 / 999.9
4
RTD
C
Custom scale
(*)
5
RTD
F
Custom scale
(*)
(*) Linearization and scale limit settings (with or without decimal point) are
selectable from PC via serial line
PROBE: RTD 3 wires (SEnS=1)
PROBE: PTC (SEnS=2)
(on request, instead of RTD 3 wires)
• InP
InP
Input settings
44
45
SP.tY
Type of
Absolute
remote setpoint
Relative
0
analogue (InP.2)
absolute
1
analogue (InP.2)
relative to
local setpoint
2
digital
absolute
(from serial line)
3 digital relative
to
(from serial line)
local setpoint
PROBE: TC (SEnS=0)
tYPE Probe type
Scale
Scale range max.
Scale range max.
(C/F)
without decimal point
with decimal point
0
PTC 990Ω
C
-55 ... 120
-55.0 ... 120.0
1
PTC 990Ω
F
-67 ... 248
-67.0 ... 248.0
2
PTC 990Ω
C
Custom scale
(*)
3
PTC 990Ω
F
Custom scale
(*)
tYPE Signal type
Scale
Max. scale range
0
0...50mV
linear
-1999 / 9999
1
0...50mV
custom linear
see table 32 values in Lin
2
10...50mV
linear
-1999 / 9999
3
10...50mV
custom linear
see table 32 values in Lin
PROBE: VOLTAGE 50mV (SEnS=3)
tYPE Signal type
Scale
Scale range max.
0
0...20mA
linear
-1999 / 9999
1
0...20mA
custom linear
see table 32 values in Lin
2
4...20mA
linear
-1999 / 9999
3
4...20mA
custom linear
see table 32 values in Lin
PROBE: CURRENT 20mA or TRANSMITTER (SEnS=4)
tYPE Signal type
Scal
Scale range max.
0
0...10V
lineare
-1999 / 9999
1
0...10V
custom linear
see table 32 values in Lin
2
2...10V
linear
-1999 / 9999
3
2...10V
custom linear
see table 32 values in Lin
PROBE: CURRENT 10V or TRANSMITTER (SEnS=5)
tYPE
Signal type
Scale
Scale range max.
0
Custom 0...10V
linear
-1999 / 9999
1
Custom 0...10V
custom linear see table 32
values in Lin
PROBE: CUSTOM 10V (SEnS=6)
tYPE
Signal type
Scale
Scale range max.
0
Custom
linear
-1999 / 9999
1
Custom
custom linear
see table 32
values in Lin
PROBE: CUSTOM 50mV, 20mA (SEnS=7)
(ode
ser.p
bavd
• Ser
Ser
Unit identification code for serial
communication (if enabled)
[see “hrd.1” in Hrd]
Serial communication
Serial interface
protocol
CENCAL, MODBUS
Selects
Baudrate
38
39
40
0 ... 9999
SEr.P Serial protocol
0
CENCAL GEFRAN
1
MODBUS RTU
bAud Baudrate CENCAL Interface
MODBUS Interface
0
1200
485 / 232
485
1
2400
485 / 232
485
2
4800
485 / 232
485
3
9600
485 / 232
485
4 19200
485 / 232
485
Parity selection
(MODBUS only)
101
_PAr Parity
0
No parity
1
Odd
2
Even
par
-
6
80090G_MHW_1600-1800P_04-2013_ENG