5
Two-channel
parameterization
Please note the following for two-channel parameterization:
Ensure that the values for the switch-off delay for stop category 1 are the same for both
channels. This means that the time must have the same value and the same value range.
Switch-off delay for stop
category 1
The
switch-off delay for stop category 1
is calculated from the "Switch-off delay for stop
category 1" and "Value range of switch-off delay for stop category 1" parameters.
Switch-off delay for stop category 1 =
Switch-off delay for stop category 1 x
Value range of switch-off delay for stop category 1
5.4
Behavior of the relay outputs in the event of
enabled switch-off delay for stop category 1
Depending on the event that causes the relay outputs to be switched off, the
parameterization of the switch-off delay, the time until the relay outputs are actually
switched off can vary.
Value range of switch-off
delay for stop category 1
Value x 10 in ms
Value x 100 in ms
Value in s
Value x 10 in s
Value range/unit for the parameterization of the "Switch-off delay
for stop category 1" parameter.
Please observe the notes below this table.
Enable
(VersaSafe only)
Disabled
Enabled
Disabled (default value): The corresponding safe output is
operated exclusively according to the safety logic.
Enabled: Enable is active; the safe output data is output after
being ANDed with the standard output data of the standard
control system.
See also Section " VersaSafe" on page 2-15.
Table 5-1
Parameterization of relay outputs [...]
Parameterization
Value range
Remark
OUT0 - OUT1
If the switch-off delay for stop category 1 is parameterized with a value less than 150 ms,
this value is rejected as a parameterization error (error code 028x
hex
).
Table 5-2
Switching off the relay outputs according to the trigger event and the
parameterization
Switch off of relay outputs
Influence of
parameterized
Switch off of relay outputs
Switch-off
delay
–
By the safe controller
Yes
Once the parameterized switch-off
delay has elapsed
–
After a bus error
Yes
After the the parameterized
switch-off delay has elapsed
–
After a short circuit, cross
circuit, failure of the supply
voltage or hardware fault
No
Immediately (only stop category 0)
5-4
User manual IC220SDL840 -
May 2018
GFK-2734
Содержание VersaSafe VersaPoint IC220SDL840
Страница 2: ...T h i s p a g e l e f t b l a n k i n t e n t i o n a l l y ...
Страница 6: ...T h i s p a g e l e f t b l a n k i n t e n t i o n a l l y User manual IC220SDL840 May 2018 GFK 2734 ...
Страница 34: ...2 T h i s p a g e l e f t b l a n k i n t e n t i o n a l l y 2 18 User manual IC220SDL840 May 2018 GFK 2734 ...
Страница 48: ...4 T h i s p a g e l e f t b l a n k i n t e n t i o n a l l y 4 8 User manual IC220SDL840 May 2018 GFK 2734 ...
Страница 54: ...5 T h i s p a g e l e f t b l a n k i n t e n t i o n a l l y 5 6 User manual IC220SDL840 May 2018 GFK 2734 ...
Страница 84: ...7 T h i s p a g e l e f t b l a n k i n t e n t i o n a l l y 7 6 User manual IC220SDL840 May 2018 GFK 2734 ...
Страница 88: ...8 T h i s p a g e l e f t b l a n k i n t e n t i o n a l l y 8 4 User manual IC220SDL840 May 2018 GFK 2734 ...
Страница 96: ...10 T h i s p a g e l e f t b l a n k i n t e n t i o n a l l y 10 2 User manual IC220SDL840 May 2018 GFK 2734 ...
Страница 106: ...11 T h i s p a g e l e f t b l a n k i n t e n t i o n a l l y 11 10 User manual IC220SDL840 May 2018 GFK 2734 ...
Страница 120: ...C T h i s p a g e l e f t b l a n k i n t e n t i o n a l l y C 8 User manual IC220SDL840 May 2018 GFK 2734 ...