Supply voltage U
L
(logic, relay)
Current consumption
360 mA, maximum
Diagnostic indicators
Indirect via green D LED
(see "Local diagnostic and status indicators" on page 2-10)
The safety terminal is supplied with communications power via the bus coupler or a designated power terminal in the station. Potential rout-
ing is used for the communications power in the VersaPoint station. For the technical data, please refer to the data sheet for the bus coupler
or power terminal used.
Supply voltage U
M
(clock outputs)
Nominal voltage
24 V DC according to EN 61131-2 and EN 60204
Tolerance
-15%/+20% including an entire AC voltage component with peak value of 5%
Ripple
3.6 V
PP
Permissible voltage range
19.2 V DC to 30.0 V DC, ripple included
Current consumption
30 mA, typical
Permissible interruption time
10 ms;
Within this time, the output voltage for the clock outputs fails as the clock
outputs are not internally buffered. A dip in the supply voltage can switch off
the safety relay and result in a diagnostic message.
Surge protection
Yes (in the bus coupler/power terminal);
Additional internal surge protection (suppressor diode between U
M
and
GND)
Protection against polarity reversal
Yes (in the bus coupler/power terminal)
Undervoltage detection
No
Diagnostic indicators
None
External fuse protection
8 A slow-blow, maximum
The safety terminal is supplied with main voltage U
M
via the bus coupler or a power terminal in the station. Potential routing is used for the
main voltage in the VersaPoint station. For the technical data, please refer to the data sheet for the bus coupler or power terminal used.
WARNING: Loss of the safety function when using unsuitable power supplies
Only use power supplies according to EN 50178/VDE 0160 (PELV).
NOTE: Module damage due to polarity reversal
Polarity reversal places a burden on the electronics and, despite protection against polarity reversal, can damage the module. Therefore,
polarity reversal must be prevented.
NOTE: Module damage in the event of overload
The power supply unit must be able to supply four times (400%) the nominal current of the external fuse.
Safe digital relay outputs
Number of safety relays
4
Number of floating contacts
8
Supply for the coils
From supply voltage U
L
11-4
User manual IC220SDL840 -
May 2018
GFK-2734
Содержание VersaSafe VersaPoint IC220SDL840
Страница 2: ...T h i s p a g e l e f t b l a n k i n t e n t i o n a l l y ...
Страница 6: ...T h i s p a g e l e f t b l a n k i n t e n t i o n a l l y User manual IC220SDL840 May 2018 GFK 2734 ...
Страница 34: ...2 T h i s p a g e l e f t b l a n k i n t e n t i o n a l l y 2 18 User manual IC220SDL840 May 2018 GFK 2734 ...
Страница 48: ...4 T h i s p a g e l e f t b l a n k i n t e n t i o n a l l y 4 8 User manual IC220SDL840 May 2018 GFK 2734 ...
Страница 54: ...5 T h i s p a g e l e f t b l a n k i n t e n t i o n a l l y 5 6 User manual IC220SDL840 May 2018 GFK 2734 ...
Страница 84: ...7 T h i s p a g e l e f t b l a n k i n t e n t i o n a l l y 7 6 User manual IC220SDL840 May 2018 GFK 2734 ...
Страница 88: ...8 T h i s p a g e l e f t b l a n k i n t e n t i o n a l l y 8 4 User manual IC220SDL840 May 2018 GFK 2734 ...
Страница 96: ...10 T h i s p a g e l e f t b l a n k i n t e n t i o n a l l y 10 2 User manual IC220SDL840 May 2018 GFK 2734 ...
Страница 106: ...11 T h i s p a g e l e f t b l a n k i n t e n t i o n a l l y 11 10 User manual IC220SDL840 May 2018 GFK 2734 ...
Страница 120: ...C T h i s p a g e l e f t b l a n k i n t e n t i o n a l l y C 8 User manual IC220SDL840 May 2018 GFK 2734 ...