Supply voltage U
M
Supply the supply voltage at a bus coupler or a power terminal. It is supplied to the safety
module via the VersaPoint potential jumper U
M
.
The supply voltage
U
M
is used to supply the clock outputs. For the technical data for the
supply voltage U
M
, please refer to Section "Supply voltage UM (clock outputs)" on
The maximum current carrying capacity for the main circuit U
M
is 8 A (total current with the
segment circuit that is not used in the safety terminal).
This current carrying capacity can be reduced if certain terminals are used. Please refer to
the information in the terminal-specific data sheets.
If the limit value of the potential jumpers U
M
and U
S
is reached (total current of U
S
and U
M
),
a new power terminal must be used.
Figure 3-1
Supply U
M
with connection to functional earth ground according to
EN 60204-1
WARNING: Loss of the safety function when using unsuitable power supplies
Please observe the points in Section "Electrical safety" on page 1-2.
NOTE: Module damage due to polarity reversal
Polarity reversal places a burden on the electronics and, despite protection against
polarity reversal, can damage the module. Therefore, polarity reversal must be
prevented.
24 V DC
(PELV)
+
-
230 V
24 V
External fuse
8 A, maximum
U für Einspeisung am Buskoppler
oder einer Einspeiseklemme
M
GND der Einspeisung am Buskoppler
oder einer Einspeiseklemme
77220003
U für Einspeisung am Buskoppler
oder einer Einspeiseklemme (wird in der
Klemme
nicht benötigt)
S
IB IL 24 PSDOR 4-PAC
Bei Verwendung des sicherheitsgerichteten Segmentkreises:
GND der Klemme IB IL 24 PSDOR 4-PAC
U
S
for supply at a bus coupler or a power
terminal (not required in the safety terminal)
GND for supply at a bus coupler or a power
terminal
When using the safety-related segment circuit:
GND of the IB IL 24 PSDOR 4-PAC terminal
U
M
for supply at a bus coupler or a power terminal
WARNING:
Loss of functional safety due to parasitic voltages
Supply the supply voltages U
M
and U
S
at a bus coupler and/or a power terminal from the
same power supply unit, so that the loads of IC220SDL840 are not affected by parasitic
voltages in the event of an error.
3-2
User manual IC220SDL840 -
May 2018
GFK-2734
Содержание VersaSafe VersaPoint IC220SDL840
Страница 2: ...T h i s p a g e l e f t b l a n k i n t e n t i o n a l l y ...
Страница 6: ...T h i s p a g e l e f t b l a n k i n t e n t i o n a l l y User manual IC220SDL840 May 2018 GFK 2734 ...
Страница 34: ...2 T h i s p a g e l e f t b l a n k i n t e n t i o n a l l y 2 18 User manual IC220SDL840 May 2018 GFK 2734 ...
Страница 48: ...4 T h i s p a g e l e f t b l a n k i n t e n t i o n a l l y 4 8 User manual IC220SDL840 May 2018 GFK 2734 ...
Страница 54: ...5 T h i s p a g e l e f t b l a n k i n t e n t i o n a l l y 5 6 User manual IC220SDL840 May 2018 GFK 2734 ...
Страница 84: ...7 T h i s p a g e l e f t b l a n k i n t e n t i o n a l l y 7 6 User manual IC220SDL840 May 2018 GFK 2734 ...
Страница 88: ...8 T h i s p a g e l e f t b l a n k i n t e n t i o n a l l y 8 4 User manual IC220SDL840 May 2018 GFK 2734 ...
Страница 96: ...10 T h i s p a g e l e f t b l a n k i n t e n t i o n a l l y 10 2 User manual IC220SDL840 May 2018 GFK 2734 ...
Страница 106: ...11 T h i s p a g e l e f t b l a n k i n t e n t i o n a l l y 11 10 User manual IC220SDL840 May 2018 GFK 2734 ...
Страница 120: ...C T h i s p a g e l e f t b l a n k i n t e n t i o n a l l y C 8 User manual IC220SDL840 May 2018 GFK 2734 ...