Critical Power
Modifications reserved
Page 98/146
GE_UPS_OPM_TLE_SCE_M60_M80_1GB_V020.docx
User Manual
TLE Series 600 & 800 CE S1
Module shutdown
Module shutdown
Load Off command for a single UPS.
ATTENTION !
THIS COMMAND WILL IMMEDIATELY DISCONNECT THE
LOAD
.
“
Module shutdown
”
cannot disconnect the UPS from the
Load
with
“Q2
-
Manual Bypass switch”
(only if provided by customer)
closed.
For the RPA Parallel System
In an RPA Parallel System, the “Module shutdown” command disconnects the
Load to the selected unit only (switch Q1 closed).
Module shutdown RESET
“M
odule shutdown
”
restore command for an individual UPS.
Led Module shutdown status
Shows the
“Module shutdown”
status: ACTIVE / NOT ACTIVE
System shutdown
System shutdown
Load Off command for an
RPA Parallel System
.
ATTENTION !
THIS COMMAND WILL IMMEDIATELY DISCONNECT THE
LOAD
.
“
System shutdown
”
cannot disconnect the
RPA Parallel System
from the
Load
with
Q2
(only if provided by customer) closed.
For the RPA Parallel System
If
“
System shutdown
”
is pressed on one unit connected to the Parallel Bus
(switch Q1 closed), all the units are separated from the Load.
System shutdown RESET
“System shutdown”
restore command for a
RPA Parallel System
.
For the RPA Parallel System
The “
System shutdown RESET
”
must be done only on one unit connected to the
parallel bus (switch Q1 closed).
Led System shutdown status
Shows the
“System shutdown”
status: ACTIVE / NOT ACTIVE
Booster
Only for
Service Centre
.