GE_UPS_OPM_TLE_SCE_M60_M80_1GB_V020.docx
User Manual
TLE Series 600 & 800 CE S1
7.3.1
Events (alarms and messages)
Each of the following listed events, alarm or message, can be displayed on the
LCD screen
, on a
PC
with
the software
“GE Data Protection”
installed or with the monitoring system
“
GE iUPSGuard
”
.
Alarms
and
Messages
are differently specified because the
alarms
are indicating an abnormal
functioning of the UPS (which are additionally signalled with the
LED ALARM
and acoustically with the
buzzer
), while the
messages
indicate the various states of operation of the UPS (stored in the events list,
but not activating the
LED ALARM
and the
acoustical alarm
).
7.3.2
Alarms list
Code
Alarm
Description
4000
SETUP VALUES LOST
Parameters are lost and have been replaced with
default values.
Please call nearest Service Centre for intervention.
4001
REGULATION BOARD FAILURE
A blocked DSP on the Control board causes this
alarm, and consequently the shut-down of Rectifier
and inverter and the opening of K3.
4004
UPS FAILURE ON PARALLEL SYSTEM
The master unit detected the slave unit missing on
the communication bus even though switch Q1 is
still closed.
4006
BUS JA CRC FAILURE
The parallel communication bus system is subject
to high errors rate on channel JA.
4007
BUS JB CRC FAILURE
The parallel communication bus system is subject
to high errors rate on channel JB.
4008
BUS JA FAILURE
There is an interruption in the channel JA of the
parallel communication bus system.
4009
BUS JB FAILURE
There is an interruption in the channel JB of the
parallel communication bus system.
4010
CONNECTIVITY BUS FAILURE
The connectivity communication bus is faulty or
interrupted.
4100
RECTIFIER FUSES FAILURE
The u-switch mounted on the Rectifier input fuses
indicates a blown fuse, and consequently it is shut
down.
Clearance of this condition allows you to restart
the Rectifier.
4102
K4 CLOSING FAILURE
K4 not closed despite a closing command being
issued.
Signalled by auxiliary contact. Rectifier cannot
start.
4103
K4 OPENING FAILURE
K4 not open despite an opening command being
issued.
Signalled by auxiliary contact.
Mains remains connected to Rectifier bridge.
4104
BATTERY FUSES FAILURE
This
function,
when
enabled
on
input
programmable relays (password required), warns
the user about the external Battery Fuses failure or
MCB opening, signalled by NO free contact.
4105
RECTIFIER OVERTEMPERATURE
Temperature sensor indicates a situation of
overtemperature on the Rectifier bridge.
Only the alarm is given.
The Rectifier, when in an Off state, cannot start as
long as this condition persists.