Critical Power
Modifications reserved
Page 108/146
GE_UPS_OPM_TLE_SCE_M60_M80_1GB_V020.docx
User Manual
TLE Series 600 & 800 CE S1
8.1.3
Restore to normal operation after “System shutdown”
with Load not supplied
WARNING !
Please check and ensure the conditions of the connected load are safe before
proceeding, as this procedure will result in the connection of power to the load
circuit(s).
NOTE !
Before performing this operation, make sure that the UPS is in the following status:
“Q1
- UPS Output
switch”
MUST BE CLOSED.
“External Battery Protections”
MUST BE DISCONNECTED.
If
eBoost™
option is available, make sure that
eBoost™ Operation Mode
is disabled
before starting this procedure.
View of the
Synoptic Diagram
after performed the
command “
System shutdown”
with LOAD NOT
SUPPLIED.
1. Restore the command
“
System shutdown”
.
Restore the command
“
System shutdown
” through
the
screen:
Commands 1 / System shutdown /
RESET
.
The
Load
is supplied by the
Mains
through the
Automatic Bypass
.
Rectifier
starts automatically.
LED 1 (Rectifier)
blinking, indicates
Soft-start
.
At the end of
Rectifier Soft-start
the
LED 1 (Rectifier)
remains lit.
The
Synoptic Diagram
must display the status
“
LOAD SUPPLIED BY AUTOMATIC BYPASS
”
.
Continue
►