Critical Power
Modifications reserved
Page 69/146
GE_UPS_OPM_TLE_SCE_M60_M80_1GB_V020.docx
User Manual
TLE Series 600 & 800 CE S1
NOTE !
To operationalize this function, in case that the UPS was provided with one or
more cards
“P4
-
Customer Interface”
, there must be on each card the following:
- Remove the cable short-circuiting terminals
X2 / 1, 2
(see
Fig. 5.11-3)
.
- Remove the
Jumper JP2
(see
Fig. 5.11-3)
.
Fig. 5.11-3 X2 terminal block and Jumper JP2 on the P4
–
Customer Interface Board
When the
“
EPO - Emergency Power Off
”
has been activated, the system must be restored as
follows:
Realise the push-button
“
EPO - Emergency Power Off
”
(contact on
XA / EPO-1, EPO-
2 is closed
again).
Perform the
“Inverter OFF”
command from the screen:
Commands 1 / Inverter /
OFF
.
(see
User Manual
to
Section 7.5)
.
In case of a Parallel System
perform the “Inverter OFF” command from the
screen
“Commands 1 / Inverter / OFF”
of each unit connected on the Parallel Bus
and having its output switch
“Q1
-
UPS Output”
closed.