Critical Power
Modifications reserved
Page 51/53
GE_UPS_ISG_TLE_SUL_40K_M15_1US_V010.docx
Installation Guide TLE Scalable Series 40 - 150 UL S1
6
OPTIONS
WARNING !
The installation and cabling of the options must be performed by QUALIFIED
SERVICE PERSONNEL only.
Refer to the “
Safety Instructions - Installation
” described on
Chapter 1
.
Make sure that the UPS installation is COMPLETELY POWERED DOWN!
6.1
TOP CABLE ENTRY/EXIT SIDECAR AND TOP HAT FASCIA
Fig. 6.1-1 UPS with “TCE & THF
“Top Cable Entry/Exit Sidecar” (TCE) and “Top Hat Fascia” (THF)
Allows the connection of input and output cables from the top of the UPS.
The “Top Cable Entry/Exit Sidecar“ can be located on either side of the UPS
cabinet.
The “Top Cable Entry/Exit Sidecar“ is accessibly from right side (see panel
“G”
in the Fig. 6.1-3).
Dimensions (W x D x H)
TCE:
4.00”x29.84”x48.71” /100x865x1905mm
THF:
4.00”x29.84”x48.71” /102x758x1237mm
Weight
TCE:
88lbs / 40kg
THF:
22lbs / 10kg
Screw torque specifications Tensilock / Torx M5x12:
26Lb-in / 3Nm
Fig. 6.1-2 Top Hat Fascia (THF) assembling
“Top Hat Fascia” (THF) assembling
-
Place the structure “Top Hat Fascia - B” over the
roof “A” of the UPS cabinet.
-
Fix the structure “Top Hat Fascia - B” with the
appropriate screws.