4.5
VENTILATION AND COOLING
Fig. 4.5-1 Installation on plain floor
Fig. 4.5-2 Installation on raised floor
The heat produced by the UPS is transferred to the environment by its ventilation.
A suitable ventilation or cooling system must be installed to extract the heat from the UPS room.
NOTE !
Do not put anything on the top of the cabinet.
20” (500mm) of air clearance MUST BE LEFT from the top of the UPS for a sufficient
exhausted air exchange, proper cooling, service access and safety.
Air filtering systems could be required when the UPS operates in a dirty environment.
In order to prevent overheating of the UPS, the available air intake flow rate must exceed the total air
exhaust flow rate requirement of the UPS system.
Contact your
Dealer
or the nearest
Service Center
for appropriate solutions.
The below table indicates the heat dissipation at full Load at
PF = 0.9/1
and charged Battery, up to 3280
ft (1000 m) altitude, for cooling air 77°F (25°C) to 86°F (30°C).
UPS model
Losses
Cooling air flow
VFI
SEM (Super Eco Mode)
VFI
PF = 0.9
PF = 1
PF = 0.9
PF = 1
PF = 0.9
PF = 1
TLE Scalable Series 150/40
6005 BTU/hr
1760 kW
6142 BTU/hr
1800 kW
1841 BTU/hr
540 kW
1911 BTU/hr
560 kW
872 CFM
513 m
3
/h
892 CFM
525 m
3
/h
TLE Scalable Series 150/50
7507 BTU/hr
2200 kW
7677 BTU/hr
2250 kW
1962 BTU/hr
575 kW
2047 BTU/hr
600 kW
1090 CFM
642 m
3
/h
1115 CFM
656 m
3
/h
TLE Scalable Series 150/80
11738 BTU/hr
3440 kW
12011 BTU/hr
3520 kW
3139 BTU/hr
920 kW
3276 BTU/hr
960 kW
1705 CFM
1003 m
3
/h
1744 CFM
1027 m
3
/h
TLE Scalable Series 150/100
15013 BTU/hr
4400 kW
15355 BTU/hr
4500 kW
3583 BTU/hr
1050 kW
3753 BTU/hr
1000 kW
2180 CFM
1283 m
3
/h
2230 CFM
1313 m
3
/h
TLE Scalable Series 150/120
18016 BTU/hr
5280 kW
18426 BTU/hr
5400 kW
4299 BTU/hr
1260 kW
4504 BTU/hr
1320 kW
2616 CFM
1540 m
3
/h
2676 CFM
1575 m
3
/h
TLE Scalable Series 150/150
22520 BTU/hr
6600 kW
23544 BTU/hr
6900 kW
5374 BTU/hr
1575 kW
5630 BTU/hr
1650 kW
3271 CFM
1925 m
3
/h
3419 CFM
2013 m
3
/h
NOTE !
The ventilation and cooling system shall be rated as for operation in
VFI mode
.
TLES
_UL_0
40-15
0_S1_
UPS v
entilati
on_Plai
n floo
r_01U
S
Air E
xtrac
tion
Air In
take
Air I
nta
ke
TLES_UL
_040-
150_S
1_UP
S vent
ilation
_Raise
d floo
r_01U
S
Air E
xtra
ction